Ampacity Chart — Cable Ampacity Table
Allowable current by conductor size at each insulation rating, with live ambient temperature and bundling adjustment.
Quick answer
Adjust to see the derated columns update. 30 °C and three conductors is the un-derated baseline.
Copper ampacity by size
Base values at 30 °C ambient with three current-carrying conductors, plus the derated result at 30 °C with 3 conductors.
| Size | 60 °C | 75 °C | 90 °C | Derated (30 °C, 3 cond.) |
|---|---|---|---|---|
| 18 AWG | 8 A | 10 A | 11 A | 11 A |
| 16 AWG | 11 A | 13 A | 15 A | 15 A |
| 14 AWG | 15 A | 18 A | 20 A | 20 A |
| 12 AWG | 20 A | 24 A | 27 A | 27 A |
| 10 AWG | 27 A | 32 A | 37 A | 37 A |
| 8 AWG | 37 A | 44 A | 49 A | 49 A |
| 6 AWG | 50 A | 59 A | 67 A | 67 A |
| 4 AWG | 68 A | 80 A | 90 A | 90 A |
| 3 AWG | 79 A | 93 A | 105 A | 105 A |
| 2 AWG | 92 A | 108 A | 122 A | 122 A |
| 1 AWG | 107 A | 126 A | 142 A | 142 A |
| 1/0 AWG | 124 A | 146 A | 165 A | 165 A |
| 2/0 AWG | 144 A | 170 A | 192 A | 192 A |
| 3/0 AWG | 168 A | 198 A | 223 A | 223 A |
| 4/0 AWG | 195 A | 230 A | 260 A | 260 A |
| 250 kcmil | 217 A | 257 A | 289 A | 289 A |
| 300 kcmil | 245 A | 289 A | 326 A | 326 A |
| 350 kcmil | 271 A | 319 A | 360 A | 360 A |
| 400 kcmil | 295 A | 348 A | 393 A | 393 A |
| 500 kcmil | 341 A | 403 A | 454 A | 454 A |
| 600 kcmil | 384 A | 454 A | 511 A | 511 A |
| 750 kcmil | 444 A | 524 A | 591 A | 591 A |
Source & method: Method and calibration error are documented on the methodology page. Conductor geometry is computed from the ASTM B258 AWG formula.
Copper versus aluminium at the same load
| Target load | Copper | Aluminium |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 30 A | 10 AWG | 8 AWG |
| 40 A | 8 AWG | 6 AWG |
| 50 A | 6 AWG | 4 AWG |
| 60 A | 4 AWG | 4 AWG |
| 70 A | 4 AWG | 3 AWG |
| 90 A | 3 AWG | 1 AWG |
| 100 A | 2 AWG | 1/0 AWG |
| 125 A | 1 AWG | 2/0 AWG |
| 150 A | 2/0 AWG | 3/0 AWG |
| 175 A | 3/0 AWG | 4/0 AWG |
| 200 A | 4/0 AWG | 250 kcmil |
Ampacity is only half the sizing question. On long runs voltage drop usually governs — check the run with the voltage drop calculator.
Reading the ampacity table in the real world
Ampacity of a conductor is the current it can carry continuously without pushing its insulation past its temperature rating. The ampacity table above is organised the way the National Electric Code (NEC) organises its own: by conductor material, by insulation temperature column, and then adjusted by correction factors. Cable ampacity for a finished assembly follows the same conductor values, with the cable's own temperature rating as the ceiling.
Two adjustments apply before the number is usable. Correction factors for ambient temperature scale the value whenever the surroundings are hotter or cooler than 30 °C — roughly 0.91 at 40 °C and 0.71 at 50 °C on a 90 °C conductor. Adjustment for the number of current-carrying conductors applies from four upward: 0.80 for 4 to 6, 0.70 for 7 to 9, 0.50 for 10 to 20. Both multiply together, which is how a 30 A conductor legitimately lands near 17 A in a hot, crowded raceway.
Small conductors are limited by rule rather than by physics. 14 AWG copper is treated as 15 amps, 12 AWG as 20 amps and 10 AWG as 30 amps for overcurrent protection, even though the 90 °C column computes higher. Those three sizes cover most lighting circuits and receptacle branch circuits. Larger sizes read straight off the table: ampacity of #4 copper is about 80 A at 75 °C, and 750 MCM ampacity is around 524 A copper at the same rating.
Overcurrent protection is the other half of the pairing. The breaker protects the conductor, so its rating must not exceed the corrected ampacity, with the standard rounding-up allowance for smaller circuits. Undersized conductors behind an oversized breaker are the classic path to insulation breakdown and fire hazards, because the conductor cooks long before the device trips. Terminations cap it too: most equipment is rated 75 °C, so the 90 °C column is for derating math only.
Frequently asked
- What is ampacity?
- Ampacity is the maximum current a conductor can carry continuously without exceeding its insulation temperature rating. It depends on conductor size and material, insulation rating, ambient temperature and how many conductors are bundled together.
- How many amps can 12 AWG copper carry?
- 12 AWG copper is estimated at 20 A at 60 °C, 24 A at 75 °C and 27 A at 90 °C, before ambient or bundling derating. In practice 12 AWG is used on 20 A branch circuits.
- Why is aluminium ampacity lower than copper?
- Aluminium has about 61% of copper's conductivity, so the same cross-section carries roughly 78% of the current for the same temperature rise. Aluminium conductors are typically sized one to two steps larger than copper for the same load.
- Does the 90 °C column mean I can load the wire to that value?
- No. The 90 °C column is used for derating calculations. The final ampacity is limited by the temperature rating of the terminations, which is commonly 75 °C on equipment rated over 100 A and 60 °C on some smaller devices.
- Is this the same as the NEC ampacity table?
- No. Code tables are copyrighted, so these values come from a published physics model calibrated against standard practice. They track within a few percent for common sizes, but the adopted code is the legal authority and must be checked before installation.
Related charts & calculators
- Wire Gauge ChartAWG diameter, circular mils, resistance and amp capacity in one table.
- Wire Size ChartWhat size wire for each breaker rating and typical circuit.
- kcmil Wire Size ChartMCM to AWG conversion, circular mils, resistance and ampacity for 250-750 kcmil.
- Conduit Fill ChartMaximum THHN conductors per trade size for every raceway type.
- EMT Conduit Fill ChartConductor counts and internal areas for electrical metallic tubing.
- PVC Conduit Fill ChartSchedule 40 and Schedule 80 conductor counts and usable areas.