14 AWG Wire — Amp Rating, Ampacity & Diameter
Ampacity, geometry, resistance, conduit fill and maximum run length for 14 AWG conductors in copper and aluminium.
Quick answer
Copper 75 °C
18A
Aluminium 75 °C
14A
Diameter
0.0641in
Circular mils
4,107
Full specification
| Size designation | 14 AWG |
|---|---|
| AWG gauge number | 14 |
| Circular mils | 4,107 |
| kcmil | 4.11 |
| Bare diameter (in) | 0.0641 |
| Bare diameter (mm) | 1.628 |
| Cross-section (mm²) | 2.08 |
| THHN/THWN-2 OD (in) | 0.111 |
| Insulated area (sq in) | 0.0097 |
| Copper resistance (Ω/1000 ft) | 2.5252 |
| Aluminium resistance (Ω/1000 ft) | 4.1393 |
| Max standard breaker (Cu, 75 °C) | 15 A |
Ampacity with derating
Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 20 A | 18 A | 16 A | 14 A |
| 6 | 16 A | 15 A | 13 A | 11 A |
| 9 | 14 A | 13 A | 11 A | 10 A |
| 15 | 10 A | 9 A | 8 A | 7 A |
| 25 | 9 A | 8 A | 7 A | 6 A |
Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 18 A. Run your own conditions.
Maximum run length at 3% voltage drop
One-way distance for 14 AWG copper before drop exceeds 3%.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 10 A | 57 ft | 114 ft | 114 ft | 264 ft |
| 15 A | 38 ft | 76 ft | 76 ft | 176 ft |
| 20 A | 28 ft | 57 ft | 57 ft | 132 ft |
| 30 A | 19 ft | 38 ft | 38 ft | 88 ft |
| 40 A | 14 ft | 28 ft | 28 ft | 66 ft |
| 50 A | 11 ft | 22 ft | 22 ft | 52 ft |
How many 14 AWG conductors fit in conduit
Maximum count of this size alone, at the fill percentage matching the resulting count.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 12 | 22 | 35 | 61 | 84 | 138 | 242 | 365 | 400 | 400 |
| IMC | 14 | 24 | 39 | 68 | 91 | 150 | 212 | 327 | 400 | 400 |
| RMC | 12 | 22 | 36 | 63 | 85 | 140 | 201 | 309 | 400 | 400 |
| PVC Sch 40 | 11 | 20 | 34 | 60 | 82 | 136 | 194 | 300 | 400 | 400 |
| PVC Sch 80 | 8 | 16 | 28 | 51 | 70 | 118 | 170 | 266 | 359 | 400 |
14 AWG copper ampacity vs aluminium ampacity
Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.
| Material | 60 °C (TW, NM-B) | 75 °C (THW, THWN, XHHW) | 90 °C (THHN, THWN-2, XHHW-2) |
|---|---|---|---|
| Copper | 15 A | 18 A | 20 A |
| Aluminium | 12 A | 14 A | 16 A |
The 14 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 18 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 20 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.
Aluminium of the same size carries roughly 78% of the copper value (14 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.
Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.
Neighbouring sizes
Compare 14 AWG with the sizes immediately above and below it before sizing a circuit.
Circuits that use 14 AWG
Breaker ratings whose smallest copper conductor at 75 °C terminations is 14 AWG.
14 AWG amp rating, diameter and metric equivalent
The amp rating for 14 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 15 A on a 60 °C conductor, 18 A at 75 °C and 20 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.
Geometrically, 14 AWG is 0.0641 in (1.63 mm) in bare diameter, which is 4,107 circular mils. The cross sectional area works out to 2.08 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.
American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.
14 AWG in millimetres — diameter, mm² and the metric equivalent
AWG is a gauge number, not a dimension, so metric shops need the conversion before ordering.
| Bare diameter | 1.628 mm (0.0641 in) |
|---|---|
| Cross-sectional area | 2.08 mm² |
| Nearest IEC 60228 size at or above | 2.5 mm² |
| Insulated OD (THHN/THWN-2) | 2.82 mm (0.111 in) |
14 AWG measures 1.63 mm across the bare copper, which is 2.08 mm² of cross-section. Substituting 2.5 mm² cable is the safe direction because it is the first standard metric size that is not smaller; going the other way — for example calling 14 AWG the same as 1.5 mm² — under-sizes the conductor. Metric cable is also specified by area while AWG is specified by gauge step, so the two systems never coincide exactly.
Source & method: Diameter from the ASTM B258 gauge formula; area converted arithmetically. No code table is reproduced.
How many watts can 14 AWG wire handle?
Watts are amps times volts, so the wattage depends entirely on the system voltage.
| System | Max watts (non-continuous) | Max watts (continuous, 80%) |
|---|---|---|
| 12 V DC | 180 W | 144 W |
| 24 V DC | 360 W | 288 W |
| 120 V AC, 1-phase | 1,800 W | 1,440 W |
| 240 V AC, 1-phase | 3,600 W | 2,880 W |
| 277 V AC, 1-phase | 4,155 W | 3,324 W |
Low-voltage DC is the case where this table misleads if used alone. At 12 V the wattage looks generous, but voltage drop — not heat — sets the real limit, because a 3% allowance is only 0.36 V. For any 12 V or 24 V run longer than a few feet, size on drop with the voltage drop calculator and treat the wattage above as a ceiling you will rarely reach.
14/2 and 14/3 cable — what the second number means
Cable designations count insulated current-carrying conductors, not total wires.
A cable marked 14/2 contains two insulated 14 AWG conductors — one ungrounded, one grounded — plus a bare equipment grounding conductor that is not counted in the name. 14/3 adds a third insulated conductor, typically red, for switch legs, travellers or a second hot leg. The ampacity is identical in both cases, because it is a property of the conductor size and insulation, not the conductor count: still 15 A on the 60 °C basis that non-metallic sheathed cable is held to.
Read the higher-temperature figures as insulation and calculation properties, not as usable circuit ratings. The insulation used in NM-B is a 90 °C material, and the same copper conductor with 90 °C insulation installed in a raceway computes to a higher ampacity — but a non-metallic sheathed cable assembly must be applied at the 60 °C ampacity of 15 A. On top of that, 14 AWG copper is limited to a 15 A overcurrent device by the small-conductor rule, which applies to 14, 12 and 10 AWG copper regardless of insulation, with only narrow listed exceptions such as certain motor and A/C equipment circuits. So the 20 A in the 90 °C column above is a calculated value for a 90 °C-rated conductor, used as the starting point for derating — never as a load limit for 14/2 NM-B. In practice a standard residential 14/2 NM-B circuit is protected at no more than 15 A, and the load on it must stay within that.
That is also why 14/2 NM-B and 14 AWG THHN in conduit are not interchangeable on paper: THHN computes to 18 A where every termination in the circuit is listed for 75 °C, while the NM cable stays at 15 A regardless of the breaker it lands on. Termination temperature is a ceiling in both cases — 90 °C insulation on equipment with 75 °C lugs is still read from the 75 °C column. Separately, where more than three current-carrying conductors run together in one raceway or cable, or cables are bundled together for more than 24 inches so that more than three current-carrying conductors share the bundle, ampacity adjustment applies to all of them — which lowers these numbers further, never raises them.
Solid versus stranded does not change ampacity either. Solid 14 AWG is standard in residential branch circuits; stranded is used where the conductor must flex or be pulled around tight bends. Both have the same 4,107 circular mils of copper, though stranded has a slightly larger overall diameter, which matters for conduit fill and for termination lugs.
What 14 AWG means
14 AWG is a gauge designation, not a measurement. The number counts the drawing dies historically used to pull the wire down to size, so it runs backwards: a higher number is a thinner conductor. Each single step changes diameter by about 12.2% and area by about 26%, which is why moving from 14 AWG to the next size up is a meaningful jump in both cost and capacity rather than a rounding change.
Written forms you will see for the same conductor include 14 AWG, 14 ga, 14 gauge and #14. They are identical. What is not identical is the cable assembly the conductor ships in, the insulation rated on it, or the termination temperature at the breaker — all three can lower the usable ampacity below the 18 A that 14 AWG copper reaches at 75 °C.
Where 14 AWG actually gets used — and where it must not
14 AWG is the smallest conductor permitted on a general-purpose branch circuit in ordinary dwelling wiring, and it is protected at 15 A regardless of what the ampacity model returns for the bare copper. That cap is a small-conductor rule, not a thermal one: the conductor itself dissipates more than 15 A of heat, but the terminations, the cable jacket and the fault-current assumptions behind residential wiring methods all assume a 15 A device.
In practice it shows up as 14/2 and 14/3 NM-B for lighting circuits, bedroom and living-area receptacles, smoke-detector loops, switch legs and fixture whips. It is also the standard size for 15 A receptacle circuits in older housing stock, which is why so much rewiring work involves deciding whether to keep an existing 14 AWG home run or pull 12 AWG and step the breaker up.
The failure mode is almost always the splice or the device, not the wire. 14 AWG is stiff enough to break at a back-stab receptacle terminal and thin enough that an under-torqued screw terminal heats badly under a 12 A space-heater load. It is also the size most often found on an over-fused circuit: a 20 A breaker feeding 14 AWG is the single most common branch-circuit violation found during inspection.
Where 14 AWG is genuinely wrong: any 20 A circuit, kitchen small-appliance circuits, laundry receptacles, bathroom receptacle circuits, and any long run where 3% voltage drop matters more than ampacity. On a 100 ft run at 12 A on 120 V, 14 AWG is already near the drop guideline, which is why garage and outbuilding lighting is usually pulled in 12 AWG even at a 15 A device.
Frequently asked
- How many amps can 14 AWG wire carry?
- 14 AWG copper is estimated at 15 A at 60 °C, 18 A at 75 °C and 20 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 14 A at 75 °C.
- What is the amp rating for 14 gauge wire?
- Use 18 A for 14 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 15 A instead when the conductor is inside NM-B cable, and treat 20 A as the derating base only. Aluminium of the same size is about 14 A at 75 °C.
- What breaker size goes with 14 AWG copper?
- The largest standard overcurrent device that 14 AWG copper supports at 75 °C is 15 A. For a continuous load, the load itself must not exceed 80% of that rating.
- What is the diameter of 14 AWG wire?
- The bare conductor is 0.0641 inches (1.628 mm) in diameter, which is 4,107 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.111 inches.
- What is the resistance of 14 AWG wire?
- About 2.5252 ohms per 1000 feet for copper and 4.1393 ohms per 1000 feet for aluminium, at 75 °C.
- How far can I run 14 AWG wire?
- Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 14 AWG copper stays under 3% voltage drop for about 28 feet one-way. Doubling the voltage roughly doubles the allowable distance.
Related charts & calculators
- EMT Conduit Fill ChartConductor counts and internal areas for electrical metallic tubing.
- PVC Conduit Fill ChartSchedule 40 and Schedule 80 conductor counts and usable areas.
- Rigid Conduit Fill ChartRMC and IMC conductor counts per trade size, side by side.
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.