400 kcmil Wire — Amp Rating, Ampacity & Diameter

Ampacity, geometry, resistance, conduit fill and maximum run length for 400 kcmil conductors in copper and aluminium.

Quick answer

400 kcmil copper carries about 348 A at 75 °C (295 A at 60 °C, 393 A at 90 °C). The bare conductor is 0.6325 in (16.07 mm) and 400,000 circular mils, with 0.0259 Ω per 1000 ft. It pairs with a 300 A breaker at 75 °C terminations.

Copper 75 °C

348A

Aluminium 75 °C

272A

Diameter

0.6325in

Circular mils

400,000

Full specification

Size designation400 kcmil
AWG gauge numbern/a (kcmil size)
Circular mils400,000
kcmil400.00
Bare diameter (in)0.6325
Bare diameter (mm)16.065
Cross-section (mm²)202.71
THHN/THWN-2 OD (in)0.864
Insulated area (sq in)0.5863
Copper resistance (Ω/1000 ft)0.0259
Aluminium resistance (Ω/1000 ft)0.0425
Max standard breaker (Cu, 75 °C)300 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3393 A359 A321 A278 A
6314 A287 A257 A222 A
9275 A251 A224 A194 A
15197 A179 A160 A139 A
25177 A161 A144 A125 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 348 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 400 kcmil copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A5,581 ft11,162 ft11,171 ft25,780 ft
15 A3,720 ft7,441 ft7,447 ft17,186 ft
20 A2,790 ft5,581 ft5,585 ft12,890 ft
30 A1,860 ft3,720 ft3,723 ft8,593 ft
40 A1,395 ft2,790 ft2,792 ft6,445 ft
50 A1,116 ft2,232 ft2,234 ft5,156 ft

Calculate your exact run

How many 400 kcmil conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT———11136710
IMC———1113579
RMC———1113568
PVC Sch 40———1113468
PVC Sch 80———1112457

Mix conductor sizes in the fill calculator

400 kcmil copper ampacity vs aluminium ampacity

Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.

Material60 °C (TW, NM-B)75 °C (THW, THWN, XHHW)90 °C (THHN, THWN-2, XHHW-2)
Copper295 A348 A393 A
Aluminium230 A272 A306 A

The 400 kcmil copper ampacity figure you use on a real circuit is the 75 °C column, 348 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 393 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.

Aluminium of the same size carries roughly 78% of the copper value (272 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.

Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.

Neighbouring sizes

Compare 400 kcmil with the sizes immediately above and below it before sizing a circuit.

SizeCu 75 °CAl 75 °CDiameter (in)Circular mils
300 kcmil289 A225 A0.5477300,000
350 kcmil319 A249 A0.5916350,000
400 kcmil (this page)348 A272 A0.6325400,000
500 kcmil403 A314 A0.7071500,000
600 kcmil454 A354 A0.7746600,000

400 kcmil amp rating, diameter and metric equivalent

The amp rating for 400 kcmil wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 295 A on a 60 °C conductor, 348 A at 75 °C and 393 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.

Geometrically, 400 kcmil is 0.6325 in (16.07 mm) in bare diameter, which is 400,000 circular mils. The cross sectional area works out to 202.68 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.

American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.

Where 400 kcmil actually gets used

400 kcmil handles roughly 335 A in copper and 270 A in aluminium, and it typically appears on 350 A to 400 A service and feeder work: large commercial services, chiller feeds and main switchboard conductors.

At this size the entire design is dominated by terminations and geometry. Lug pads, bus stabs, bending space inside enclosures and the minimum radius of the conductor all constrain the layout, and the wire bending space required at the terminals frequently dictates a larger enclosure than the current would suggest.

Aluminium is the norm at 400 kcmil for cost and weight, especially on long runs where the weight of copper affects support spacing in cable tray and vertical risers. Copper survives where space is tight and the smaller conductor diameter for the same ampacity buys a smaller raceway.

Frequently asked

How many amps can 400 kcmil wire carry?
400 kcmil copper is estimated at 295 A at 60 °C, 348 A at 75 °C and 393 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 272 A at 75 °C.
What is the ampacity of 400 kcmil copper?
Use 348 A for 400 kcmil copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 295 A instead when the conductor is inside NM-B cable, and treat 393 A as the derating base only. Aluminium of the same size is about 272 A at 75 °C.
What breaker size goes with 400 kcmil copper?
The largest standard overcurrent device that 400 kcmil copper supports at 75 °C is 300 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 400 kcmil wire?
The bare conductor is 0.6325 inches (16.065 mm) in diameter, which is 400,000 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.864 inches.
What is the resistance of 400 kcmil wire?
About 0.0259 ohms per 1000 feet for copper and 0.0425 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 400 kcmil wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 400 kcmil copper stays under 3% voltage drop for about 2790 feet one-way. Doubling the voltage roughly doubles the allowable distance.