400 kcmil Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 400 kcmil conductors in copper and aluminium.

Quick answer

400 kcmil copper carries about 348 A at 75 °C (295 A at 60 °C, 393 A at 90 °C). The bare conductor is 0.6325 in (16.07 mm) and 400,000 circular mils, with 0.0259 Ω per 1000 ft. It pairs with a 300 A breaker at 75 °C terminations.

Copper 75 °C

348A

Aluminium 75 °C

272A

Diameter

0.6325in

Circular mils

400,000

Full specification

Size designation400 kcmil
AWG gauge numbern/a (kcmil size)
Circular mils400,000
kcmil400.00
Bare diameter (in)0.6325
Bare diameter (mm)16.065
Cross-section (mm²)202.71
THHN/THWN-2 OD (in)0.864
Insulated area (sq in)0.5863
Copper resistance (Ω/1000 ft)0.0259
Aluminium resistance (Ω/1000 ft)0.0425
Max standard breaker (Cu, 75 °C)300 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3393 A359 A321 A278 A
6314 A287 A257 A222 A
9275 A251 A224 A194 A
15197 A179 A160 A139 A
25177 A161 A144 A125 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 348 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 400 kcmil copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A5,581 ft11,162 ft11,171 ft25,780 ft
15 A3,720 ft7,441 ft7,447 ft17,186 ft
20 A2,790 ft5,581 ft5,585 ft12,890 ft
30 A1,860 ft3,720 ft3,723 ft8,593 ft
40 A1,395 ft2,790 ft2,792 ft6,445 ft
50 A1,116 ft2,232 ft2,234 ft5,156 ft

Calculate your exact run

How many 400 kcmil conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT11136710
IMC1113579
RMC1113568
PVC Sch 401113468
PVC Sch 801112457

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 400 kcmil wire carry?
400 kcmil copper is estimated at 295 A at 60 °C, 348 A at 75 °C and 393 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 272 A at 75 °C.
What breaker size goes with 400 kcmil copper?
The largest standard overcurrent device that 400 kcmil copper supports at 75 °C is 300 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 400 kcmil wire?
The bare conductor is 0.6325 inches (16.065 mm) in diameter, which is 400,000 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.864 inches.
What is the resistance of 400 kcmil wire?
About 0.0259 ohms per 1000 feet for copper and 0.0425 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 400 kcmil wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 400 kcmil copper stays under 3% voltage drop for about 2790 feet one-way. Doubling the voltage roughly doubles the allowable distance.