Voltage Drop Calculator

Percent drop, end-of-run voltage, the smallest conductor that stays under 3%, and how far your current conductor can actually go.

Quick answer

Voltage drop for a single-phase circuit is VD = 2 × K × I × L / cmil, where K is 12.9 for copper and 21.2 for aluminium, I is amps, L is the one-way run in feet and cmil is the conductor area in circular mils. Three-phase replaces the 2 with 1.732. Keep branch circuits at or under 3% drop, and feeder plus branch at or under 5% combined.

Circuit inputs

VD = 2 x K x I x L / cmil

Result

Voltage drop

7.90V

Percent drop

6.58%

Voltage at load

112.1V

Max length at 3%

45ft

Over 5% — this run needs a larger conductor.

Ampacity check: 12 AWG copper is estimated at 24 A at 75 °C, against your 20 A load.

Smallest conductor that satisfies both 3% drop and ampacity: 8 AWG.

Published standard — source: Classic voltage drop formula with standard trade constant K

Maximum one-way run length at 3% drop

Size10 A15 A20 A30 A40 A50 A60 A80 A100 A
145738
12916045
10144967248
82301531157657
63662441831229173
45823882911941451169772
373448936724418314612291
292661746330823118515411592
11167778583389291233194145116
1/01472981736490368294245184147
2/018561237928618464371309232185
3/0234115601170780585468390292234
4/0295219681476984738590492369295
Copper conductors, 120 V single phase, at the 3% branch-circuit guideline. Values in feet.

Source & method: Length solved from the same formula: L = (V × 3% × cmil) / (multiplier × K × I). Cells marked — exceed the estimated ampacity of that conductor at 75 °C, so the run length is irrelevant. Ampacity estimates are described on the methodology page.

Frequently asked

What is the formula for voltage drop?
For single phase, VD = 2 x K x I x L / cmil. For three phase, VD = 1.732 x K x I x L / cmil. K is 12.9 for copper and 21.2 for aluminium, I is the load current in amps, L is the one-way run length in feet, and cmil is the conductor cross-sectional area in circular mils.
How much voltage drop is acceptable?
The widely used guideline is 3% maximum on a branch circuit and 5% total for feeder plus branch circuit combined. These are recommendations rather than hard requirements in the NEC, but inspectors and engineers expect designs to meet them.
Does voltage drop use one-way or round-trip length?
Enter the one-way length. The factor of 2 in the single-phase formula already accounts for current flowing out and back, so doubling the length yourself would double the calculated drop.
What size wire do I need for a 100 ft run at 20 amps?
At 120 V single phase, 20 A over 100 ft one-way, 12 AWG copper drops roughly 4.4% which exceeds the 3% guideline. 10 AWG copper drops about 2.8% and is the usual choice for that run.
Why does aluminium need a larger conductor?
Aluminium has about 61% the conductivity of copper, so its voltage drop constant K is 21.2 against 12.9 for copper. For the same current, length and percent drop, aluminium typically needs to be one to two sizes larger.

Gear for long runs

Related charts & calculators