PVC Conduit Fill Chart
Maximum conductor count for PVC Schedule 40 and Schedule 80 raceway, computed from published internal diameters and nominal THHN outside diameters.
Quick answer
PVC conduit worked examples
1/2 in PVC Schedule 40 fill is 8 12 AWG THHN or 5 10 AWG. In 1 in Schedule 40, 6 #6 conductors fit; the same trade size in Schedule 80 takes 5.
Schedule 80 shares the outside diameter of Schedule 40 but the thicker wall costs roughly 15 to 25% of the usable area, so a run sized on a Schedule 40 chart can fail if the installed pipe is Schedule 80 — common where the raceway is exposed to physical damage. Check the print stamp on the pipe before you count.
PVC Schedule 40 — maximum THHN/THWN-2 conductors
Same-size conductors only. Mixed sizes need the conduit fill calculator.
| Wire size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 11 | 20 | 34 | 60 | 82 | 136 | 194 | 200 | 200 | 200 |
| 12 AWG | 8 | 15 | 25 | 43 | 59 | 99 | 141 | 200 | 200 | 200 |
| 10 AWG | 5 | 9 | 15 | 27 | 37 | 62 | 88 | 137 | 184 | 200 |
| 8 AWG | 3 | 5 | 9 | 15 | 21 | 35 | 51 | 79 | 106 | 137 |
| 6 AWG | 1 | 4 | 6 | 11 | 15 | 25 | 37 | 57 | 76 | 99 |
| 4 AWG | 1 | 1 | 4 | 7 | 9 | 15 | 22 | 35 | 47 | 60 |
| 3 AWG | 1 | 1 | 3 | 5 | 8 | 13 | 19 | 29 | 40 | 51 |
| 2 AWG | 1 | 1 | 2 | 5 | 6 | 11 | 16 | 25 | 33 | 43 |
| 1 AWG | — | 1 | 1 | 3 | 5 | 8 | 12 | 18 | 24 | 32 |
| 1/0 AWG | — | 1 | 1 | 3 | 4 | 7 | 10 | 15 | 20 | 27 |
| 2/0 AWG | — | 1 | 1 | 2 | 3 | 5 | 8 | 13 | 17 | 22 |
| 3/0 AWG | — | 1 | 1 | 1 | 2 | 4 | 7 | 10 | 14 | 18 |
| 4/0 AWG | — | — | 1 | 1 | 1 | 4 | 5 | 8 | 12 | 15 |
PVC Schedule 80 — maximum THHN/THWN-2 conductors
Same-size conductors only. Mixed sizes need the conduit fill calculator.
| Wire size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 8 | 16 | 28 | 51 | 70 | 118 | 170 | 200 | 200 | 200 |
| 12 AWG | 6 | 12 | 20 | 37 | 51 | 86 | 124 | 194 | 200 | 200 |
| 10 AWG | 4 | 7 | 13 | 23 | 32 | 54 | 77 | 121 | 164 | 200 |
| 8 AWG | 1 | 4 | 7 | 13 | 18 | 31 | 44 | 70 | 94 | 122 |
| 6 AWG | 1 | 3 | 5 | 9 | 13 | 22 | 32 | 50 | 68 | 88 |
| 4 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 19 | 31 | 42 | 54 |
| 3 AWG | 1 | 1 | 2 | 5 | 7 | 11 | 16 | 26 | 35 | 46 |
| 2 AWG | — | 1 | 1 | 4 | 5 | 9 | 14 | 22 | 30 | 38 |
| 1 AWG | — | 1 | 1 | 3 | 4 | 7 | 10 | 16 | 22 | 28 |
| 1/0 AWG | — | 1 | 1 | 2 | 3 | 6 | 8 | 13 | 18 | 24 |
| 2/0 AWG | — | — | 1 | 1 | 3 | 5 | 7 | 11 | 15 | 20 |
| 3/0 AWG | — | — | 1 | 1 | 2 | 4 | 6 | 9 | 13 | 16 |
| 4/0 AWG | — | — | 1 | 1 | 1 | 3 | 5 | 7 | 10 | 13 |
PVC conduit internal area by trade size
| Trade size | PVC Sch 40 area | PVC Sch 80 area |
|---|---|---|
| 1/2" | 0.285 (0.114) | 0.217 (0.087) |
| 3/4" | 0.508 (0.203) | 0.409 (0.164) |
| 1" | 0.832 (0.333) | 0.688 (0.275) |
| 1-1/4" | 1.453 (0.581) | 1.237 (0.495) |
| 1-1/2" | 1.986 (0.794) | 1.711 (0.684) |
| 2" | 3.291 (1.316) | 2.874 (1.150) |
| 2-1/2" | 4.695 (1.878) | 4.119 (1.647) |
| 3" | 7.268 (2.907) | 6.442 (2.577) |
| 3-1/2" | 9.737 (3.895) | 8.688 (3.475) |
| 4" | 12.554 (5.022) | 11.258 (4.503) |
Source & method: Area is A = π × (id / 2)². Internal diameters are nominal published product dimensions; see the methodology page.
Conductor outside diameters used
| Size | Insulated OD (in) | Area (sq in) |
|---|---|---|
| 18 AWG | 0.084 | 0.0055 |
| 16 AWG | 0.096 | 0.0072 |
| 14 AWG | 0.111 | 0.0097 |
| 12 AWG | 0.130 | 0.0133 |
| 10 AWG | 0.164 | 0.0211 |
| 8 AWG | 0.216 | 0.0366 |
| 6 AWG | 0.254 | 0.0507 |
| 4 AWG | 0.324 | 0.0824 |
| 3 AWG | 0.352 | 0.0973 |
| 2 AWG | 0.384 | 0.1158 |
| 1 AWG | 0.446 | 0.1562 |
| 1/0 AWG | 0.486 | 0.1855 |
| 2/0 AWG | 0.532 | 0.2223 |
| 3/0 AWG | 0.581 | 0.2651 |
| 4/0 AWG | 0.642 | 0.3237 |
| 250 kcmil | 0.711 | 0.3970 |
| 300 kcmil | 0.766 | 0.4608 |
| 350 kcmil | 0.817 | 0.5242 |
| 400 kcmil | 0.864 | 0.5863 |
| 500 kcmil | 0.949 | 0.7073 |
| 600 kcmil | 1.051 | 0.8676 |
| 750 kcmil | 1.158 | 1.0532 |
Frequently asked
- How many 12 AWG wires fit in 1/2 inch PVC Sch 40?
- Using nominal THHN outside diameters and the 40% fill rule, 8 12 AWG conductors fit in 1/2 inch PVC Sch 40. Every conductor counts, including the neutral and the equipment grounding conductor.
- What is the maximum fill percentage for PVC conduit?
- 40% of the internal cross-sectional area for three or more conductors, 31% for exactly two and 53% for a single conductor. Nipples 24 inches or shorter are permitted at 60%.
- What size PVC conduit do I need for three 10 AWG conductors?
- Three 10 AWG THHN conductors need at least 1/2 inch PVC Sch 40 at 40% fill. Add a fourth conductor and re-check, because the count changes the usable area.
- Does the ground wire count toward conduit fill?
- Yes. Fill counts every conductor in the raceway. Grounds are excluded only from the ampacity adjustment count for current-carrying conductors, never from fill.
- Where do these PVC conduit numbers come from?
- Internal diameters are published product dimensions from the relevant ANSI/UL/ASTM product standards. Area is computed as pi times radius squared, and the conductor count is the largest whole number that fits inside the applicable fill percentage. No code table is reproduced.
Mixed conductor sizes
These tables cover one conductor size at a time. Use the conduit fill calculator for mixed sizes, or see the full conduit fill chart for every raceway type side by side.
Related charts & calculators
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.
- Wire Gauge ChartAWG diameter, circular mils, resistance and amp capacity in one table.
- Wire Size ChartWhat size wire for each breaker rating and typical circuit.
- kcmil Wire Size ChartMCM to AWG conversion, circular mils, resistance and ampacity for 250-750 kcmil.
- Conduit Fill ChartMaximum THHN conductors per trade size for every raceway type.
- EMT Conduit Fill ChartConductor counts and internal areas for electrical metallic tubing.