Breaker Size Calculator
Load in watts or amps, the 125% continuous multiplier, the next standard breaker rating, and the smallest conductor that carries it.
Quick answer
To size a breaker: multiply the load current by 1.25 for a continuous load, then round up to the next standard rating (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A and up). A 5,000 W load at 240 V draws 20.8 A, becomes 26 A at 125%, and lands on a 30 A breaker with 10 AWG copper.
Load
I = W / (V × 1) · design = I × 1.25
Result
Load current
20.8A
Design current
26.0A
Breaker size
30 A
Minimum conductor
10 AWG
10 AWG copper is estimated at 32 A at 75 °C, against a design current of 26.0 A.
Check voltage drop separately — on long runs the conductor usually has to grow beyond what ampacity alone requires. Run the voltage drop calculator.
Formula estimate — source: 125% continuous-load multiplier with standard device ratings; conductor from the site ampacity model
Breaker size and conductor by load current
| Load (A) | Design at 125% (A) | Breaker (A) | Min. copper conductor |
|---|---|---|---|
| 10 | 12.5 | 15 | 14 AWG |
| 12 | 15.0 | 15 | 14 AWG |
| 16 | 20.0 | 20 | 12 AWG |
| 20 | 25.0 | 25 | 10 AWG |
| 24 | 30.0 | 30 | 10 AWG |
| 30 | 37.5 | 40 | 8 AWG |
| 40 | 50.0 | 50 | 6 AWG |
| 48 | 60.0 | 60 | 4 AWG |
| 60 | 75.0 | 80 | 4 AWG |
| 70 | 87.5 | 90 | 3 AWG |
| 80 | 100.0 | 100 | 2 AWG |
| 100 | 125.0 | 125 | 1 AWG |
| 125 | 156.3 | 175 | 2/0 AWG |
| 150 | 187.5 | 200 | 3/0 AWG |
Source & method: Standard overcurrent device ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A and upward. Conductor selection uses the ampacity model on the methodology page.
Typical circuit ampacity headroom
| Copper size | Est. ampacity 60 °C | Est. ampacity 75 °C | Est. ampacity 90 °C | Max continuous load at 75 °C |
|---|---|---|---|---|
| 14 | 15 A | 18 A | 20 A | 14 A |
| 12 | 20 A | 24 A | 27 A | 19 A |
| 10 | 27 A | 32 A | 37 A | 25 A |
| 8 | 37 A | 44 A | 49 A | 35 A |
| 6 | 50 A | 59 A | 67 A | 47 A |
| 4 | 68 A | 80 A | 90 A | 64 A |
| 3 | 79 A | 93 A | 105 A | 74 A |
| 2 | 92 A | 108 A | 122 A | 86 A |
| 1 | 107 A | 126 A | 142 A | 100 A |
| 1/0 | 124 A | 146 A | 165 A | 116 A |
| 2/0 | 144 A | 170 A | 192 A | 136 A |
| 3/0 | 168 A | 198 A | 223 A | 158 A |
| 4/0 | 195 A | 230 A | 260 A | 184 A |
Frequently asked
- How do I calculate breaker size?
- Find the load current, multiply by 1.25 for a continuous load, then round up to the next standard overcurrent device rating. Standard ratings are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175 and 200 amps and upward.
- Why multiply the load by 125%?
- A continuous load is one expected to run for three hours or more. The overcurrent device and conductors must be sized at 125% of that load so the breaker is not operating at its thermal limit indefinitely.
- What breaker size do I need for 5000 watts at 240 volts?
- 5000 W / 240 V is 20.8 A. At 125% that is 26 A, so the next standard breaker is 30 A, typically on 10 AWG copper.
- Can a breaker be larger than the wire rating?
- Generally no. The overcurrent device protects the conductor, so the breaker rating must not exceed the conductor's ampacity after derating. Limited exceptions exist for motor circuits and taps, which are outside what this calculator covers.
- What is the 80% rule for breakers?
- A standard breaker should carry no more than 80% of its rating continuously, which is the inverse of the 125% sizing multiplier. A 20 A breaker is therefore good for a 16 A continuous load.
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.
- Allen Wrench Size ChartHex key sizes with SAE and metric cross-reference.