6 AWG Wire — Amp Rating, Ampacity & Diameter

Ampacity, geometry, resistance, conduit fill and maximum run length for 6 AWG conductors in copper and aluminium.

Quick answer

6 AWG copper carries about 59 A at 75 °C (50 A at 60 °C, 67 A at 90 °C). The bare conductor is 0.1620 in (4.11 mm) and 26,251 circular mils, with 0.3951 Ω per 1000 ft. It pairs with a 50 A breaker at 75 °C terminations.

Copper 75 °C

59A

Aluminium 75 °C

46A

Diameter

0.1620in

Circular mils

26,251

Full specification

Size designation6 AWG
AWG gauge number6
Circular mils26,251
kcmil26.25
Bare diameter (in)0.1620
Bare diameter (mm)4.115
Cross-section (mm²)13.30
THHN/THWN-2 OD (in)0.254
Insulated area (sq in)0.0507
Copper resistance (Ω/1000 ft)0.3951
Aluminium resistance (Ω/1000 ft)0.6476
Max standard breaker (Cu, 75 °C)50 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
367 A61 A55 A47 A
654 A49 A44 A38 A
947 A43 A38 A33 A
1534 A31 A27 A24 A
2530 A28 A25 A21 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 59 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 6 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A366 ft732 ft733 ft1,691 ft
15 A244 ft488 ft488 ft1,127 ft
20 A183 ft366 ft366 ft845 ft
30 A122 ft244 ft244 ft563 ft
40 A91 ft183 ft183 ft422 ft
50 A73 ft146 ft146 ft338 ft

Calculate your exact run

How many 6 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT146111626466991116
IMC247121728406283107
RMC147121626385979101
PVC Sch 4014611152537577699
PVC Sch 801359132232506888

Mix conductor sizes in the fill calculator

6 AWG copper ampacity vs aluminium ampacity

Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.

Material60 °C (TW, NM-B)75 °C (THW, THWN, XHHW)90 °C (THHN, THWN-2, XHHW-2)
Copper50 A59 A67 A
Aluminium39 A46 A52 A

The 6 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 59 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 67 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.

Aluminium of the same size carries roughly 78% of the copper value (46 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.

Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.

Neighbouring sizes

Compare 6 AWG with the sizes immediately above and below it before sizing a circuit.

SizeCu 75 °CAl 75 °CDiameter (in)Circular mils
10 AWG32 A25 A0.101910,383
8 AWG44 A34 A0.128516,510
6 AWG (this page)59 A46 A0.162026,251
4 AWG80 A62 A0.204341,741
3 AWG93 A73 A0.229452,635

Circuits that use 6 AWG

Breaker ratings whose smallest copper conductor at 75 °C terminations is 6 AWG.

6 AWG amp rating, diameter and metric equivalent

The amp rating for 6 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 50 A on a 60 °C conductor, 59 A at 75 °C and 67 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.

Geometrically, 6 AWG is 0.1620 in (4.11 mm) in bare diameter, which is 26,251 circular mils. The cross sectional area works out to 13.30 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.

American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.

Where 6 AWG actually gets used

6 AWG is the standard 55 to 65 A conductor: 60 A subpanel feeders, larger ranges, 48 A Level 2 EV charging on a 60 A circuit, and grounding electrode conductors on services up to 200 A. It is also where copper cost starts to push installations toward aluminium equivalents, since aluminium of the same ampacity is substantially cheaper per foot.

Pulling tension and conduit fill become real design inputs at 6 AWG. Three current-carrying conductors plus an equipment ground in 3/4" EMT is already near the fill limit, and long pulls with multiple bends often force 1" raceway for a circuit that would otherwise fit — a raceway decision driven by geometry, not by the conductor's rating.

Frequently asked

How many amps can 6 AWG wire carry?
6 AWG copper is estimated at 50 A at 60 °C, 59 A at 75 °C and 67 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 46 A at 75 °C.
What is the amp rating for 6 gauge wire?
Use 59 A for 6 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 50 A instead when the conductor is inside NM-B cable, and treat 67 A as the derating base only. Aluminium of the same size is about 46 A at 75 °C.
What breaker size goes with 6 AWG copper?
The largest standard overcurrent device that 6 AWG copper supports at 75 °C is 50 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 6 AWG wire?
The bare conductor is 0.1620 inches (4.115 mm) in diameter, which is 26,251 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.254 inches.
What is the resistance of 6 AWG wire?
About 0.3951 ohms per 1000 feet for copper and 0.6476 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 6 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 6 AWG copper stays under 3% voltage drop for about 183 feet one-way. Doubling the voltage roughly doubles the allowable distance.