6 AWG Wire Specs
Ampacity, geometry, resistance, conduit fill and maximum run length for 6 AWG conductors in copper and aluminium.
Quick answer
Copper 75 °C
59A
Aluminium 75 °C
46A
Diameter
0.1620in
Circular mils
26,251
Full specification
| Size designation | 6 AWG |
|---|---|
| AWG gauge number | 6 |
| Circular mils | 26,251 |
| kcmil | 26.25 |
| Bare diameter (in) | 0.1620 |
| Bare diameter (mm) | 4.115 |
| Cross-section (mm²) | 13.30 |
| THHN/THWN-2 OD (in) | 0.254 |
| Insulated area (sq in) | 0.0507 |
| Copper resistance (Ω/1000 ft) | 0.3951 |
| Aluminium resistance (Ω/1000 ft) | 0.6476 |
| Max standard breaker (Cu, 75 °C) | 50 A |
Ampacity with derating
Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 67 A | 61 A | 55 A | 47 A |
| 6 | 54 A | 49 A | 44 A | 38 A |
| 9 | 47 A | 43 A | 38 A | 33 A |
| 15 | 34 A | 31 A | 27 A | 24 A |
| 25 | 30 A | 28 A | 25 A | 21 A |
Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 59 A. Run your own conditions.
Maximum run length at 3% voltage drop
One-way distance for 6 AWG copper before drop exceeds 3%.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 10 A | 366 ft | 732 ft | 733 ft | 1,691 ft |
| 15 A | 244 ft | 488 ft | 488 ft | 1,127 ft |
| 20 A | 183 ft | 366 ft | 366 ft | 845 ft |
| 30 A | 122 ft | 244 ft | 244 ft | 563 ft |
| 40 A | 91 ft | 183 ft | 183 ft | 422 ft |
| 50 A | 73 ft | 146 ft | 146 ft | 338 ft |
How many 6 AWG conductors fit in conduit
Maximum count of this size alone, at the fill percentage matching the resulting count.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 1 | 4 | 6 | 11 | 16 | 26 | 46 | 69 | 91 | 116 |
| IMC | 2 | 4 | 7 | 12 | 17 | 28 | 40 | 62 | 83 | 107 |
| RMC | 1 | 4 | 7 | 12 | 16 | 26 | 38 | 59 | 79 | 101 |
| PVC Sch 40 | 1 | 4 | 6 | 11 | 15 | 25 | 37 | 57 | 76 | 99 |
| PVC Sch 80 | 1 | 3 | 5 | 9 | 13 | 22 | 32 | 50 | 68 | 88 |
Neighbouring sizes
Frequently asked
- How many amps can 6 AWG wire carry?
- 6 AWG copper is estimated at 50 A at 60 °C, 59 A at 75 °C and 67 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 46 A at 75 °C.
- What breaker size goes with 6 AWG copper?
- The largest standard overcurrent device that 6 AWG copper supports at 75 °C is 50 A. For a continuous load, the load itself must not exceed 80% of that rating.
- What is the diameter of 6 AWG wire?
- The bare conductor is 0.1620 inches (4.115 mm) in diameter, which is 26,251 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.254 inches.
- What is the resistance of 6 AWG wire?
- About 0.3951 ohms per 1000 feet for copper and 0.6476 ohms per 1000 feet for aluminium, at 75 °C.
- How far can I run 6 AWG wire?
- Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 6 AWG copper stays under 3% voltage drop for about 183 feet one-way. Doubling the voltage roughly doubles the allowable distance.
Materials for this size
Materials for this size
Wire, cable and terminations for 6 AWG.
- THHN/THWN-2 6 AWG copper6 AWG copperBuilding wire in the size this page covers (6 AWG copper).Check price on Amazon →
- NM-B cable 6 AWG6 AWGRomex-type cable for dry indoor branch circuits at this size.Check price on Amazon →
- Wire connectors for 6 AWG6 AWGPush-in or twist-on connectors rated for this conductor size.Check price on Amazon →
- Terminal lugs & anti-oxidantCopper-rated mechanical lugs for panel and disconnect terminations.Check price on Amazon →
Links go to Amazon search results, not a single listing — confirm ratings, insulation type and listing details before buying, and make sure the part is approved for your application.
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.