6 AWG Wire — Amp Rating, Ampacity & Diameter
Ampacity, geometry, resistance, conduit fill and maximum run length for 6 AWG conductors in copper and aluminium.
Quick answer
Copper 75 °C
59A
Aluminium 75 °C
46A
Diameter
0.1620in
Circular mils
26,251
Full specification
| Size designation | 6 AWG |
|---|---|
| AWG gauge number | 6 |
| Circular mils | 26,251 |
| kcmil | 26.25 |
| Bare diameter (in) | 0.1620 |
| Bare diameter (mm) | 4.115 |
| Cross-section (mm²) | 13.30 |
| THHN/THWN-2 OD (in) | 0.254 |
| Insulated area (sq in) | 0.0507 |
| Copper resistance (Ω/1000 ft) | 0.3951 |
| Aluminium resistance (Ω/1000 ft) | 0.6476 |
| Max standard breaker (Cu, 75 °C) | 50 A |
Ampacity with derating
Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 67 A | 61 A | 55 A | 47 A |
| 6 | 54 A | 49 A | 44 A | 38 A |
| 9 | 47 A | 43 A | 38 A | 33 A |
| 15 | 34 A | 31 A | 27 A | 24 A |
| 25 | 30 A | 28 A | 25 A | 21 A |
Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 59 A. Run your own conditions.
Maximum run length at 3% voltage drop
One-way distance for 6 AWG copper before drop exceeds 3%.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 10 A | 366 ft | 732 ft | 733 ft | 1,691 ft |
| 15 A | 244 ft | 488 ft | 488 ft | 1,127 ft |
| 20 A | 183 ft | 366 ft | 366 ft | 845 ft |
| 30 A | 122 ft | 244 ft | 244 ft | 563 ft |
| 40 A | 91 ft | 183 ft | 183 ft | 422 ft |
| 50 A | 73 ft | 146 ft | 146 ft | 338 ft |
How many 6 AWG conductors fit in conduit
Maximum count of this size alone, at the fill percentage matching the resulting count.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 1 | 4 | 6 | 11 | 16 | 26 | 46 | 69 | 91 | 116 |
| IMC | 2 | 4 | 7 | 12 | 17 | 28 | 40 | 62 | 83 | 107 |
| RMC | 1 | 4 | 7 | 12 | 16 | 26 | 38 | 59 | 79 | 101 |
| PVC Sch 40 | 1 | 4 | 6 | 11 | 15 | 25 | 37 | 57 | 76 | 99 |
| PVC Sch 80 | 1 | 3 | 5 | 9 | 13 | 22 | 32 | 50 | 68 | 88 |
6 AWG copper ampacity vs aluminium ampacity
Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.
| Material | 60 °C (TW, NM-B) | 75 °C (THW, THWN, XHHW) | 90 °C (THHN, THWN-2, XHHW-2) |
|---|---|---|---|
| Copper | 50 A | 59 A | 67 A |
| Aluminium | 39 A | 46 A | 52 A |
The 6 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 59 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 67 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.
Aluminium of the same size carries roughly 78% of the copper value (46 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.
Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.
Neighbouring sizes
Compare 6 AWG with the sizes immediately above and below it before sizing a circuit.
Circuits that use 6 AWG
Breaker ratings whose smallest copper conductor at 75 °C terminations is 6 AWG.
6 AWG amp rating, diameter and metric equivalent
The amp rating for 6 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 50 A on a 60 °C conductor, 59 A at 75 °C and 67 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.
Geometrically, 6 AWG is 0.1620 in (4.11 mm) in bare diameter, which is 26,251 circular mils. The cross sectional area works out to 13.30 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.
American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.
Where 6 AWG actually gets used
6 AWG is the standard 55 to 65 A conductor: 60 A subpanel feeders, larger ranges, 48 A Level 2 EV charging on a 60 A circuit, and grounding electrode conductors on services up to 200 A. It is also where copper cost starts to push installations toward aluminium equivalents, since aluminium of the same ampacity is substantially cheaper per foot.
Pulling tension and conduit fill become real design inputs at 6 AWG. Three current-carrying conductors plus an equipment ground in 3/4" EMT is already near the fill limit, and long pulls with multiple bends often force 1" raceway for a circuit that would otherwise fit — a raceway decision driven by geometry, not by the conductor's rating.
Frequently asked
- How many amps can 6 AWG wire carry?
- 6 AWG copper is estimated at 50 A at 60 °C, 59 A at 75 °C and 67 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 46 A at 75 °C.
- What is the amp rating for 6 gauge wire?
- Use 59 A for 6 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 50 A instead when the conductor is inside NM-B cable, and treat 67 A as the derating base only. Aluminium of the same size is about 46 A at 75 °C.
- What breaker size goes with 6 AWG copper?
- The largest standard overcurrent device that 6 AWG copper supports at 75 °C is 50 A. For a continuous load, the load itself must not exceed 80% of that rating.
- What is the diameter of 6 AWG wire?
- The bare conductor is 0.1620 inches (4.115 mm) in diameter, which is 26,251 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.254 inches.
- What is the resistance of 6 AWG wire?
- About 0.3951 ohms per 1000 feet for copper and 0.6476 ohms per 1000 feet for aluminium, at 75 °C.
- How far can I run 6 AWG wire?
- Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 6 AWG copper stays under 3% voltage drop for about 183 feet one-way. Doubling the voltage roughly doubles the allowable distance.
Related charts & calculators
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.
- Wire Gauge ChartAWG diameter, circular mils, resistance and amp capacity in one table.