300 kcmil Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 300 kcmil conductors in copper and aluminium.

Quick answer

300 kcmil copper carries about 289 A at 75 °C (245 A at 60 °C, 326 A at 90 °C). The bare conductor is 0.5477 in (13.91 mm) and 300,000 circular mils, with 0.0346 Ω per 1000 ft. It pairs with a 250 A breaker at 75 °C terminations.

Copper 75 °C

289A

Aluminium 75 °C

225A

Diameter

0.5477in

Circular mils

300,000

Full specification

Size designation300 kcmil
AWG gauge numbern/a (kcmil size)
Circular mils300,000
kcmil300.00
Bare diameter (in)0.5477
Bare diameter (mm)13.912
Cross-section (mm²)152.00
THHN/THWN-2 OD (in)0.766
Insulated area (sq in)0.4608
Copper resistance (Ω/1000 ft)0.0346
Aluminium resistance (Ω/1000 ft)0.0567
Max standard breaker (Cu, 75 °C)250 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3326 A298 A266 A230 A
6261 A238 A213 A184 A
9228 A208 A186 A161 A
15163 A149 A133 A115 A
25147 A134 A120 A104 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 289 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 300 kcmil copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A4,186 ft8,372 ft8,378 ft19,335 ft
15 A2,790 ft5,581 ft5,585 ft12,890 ft
20 A2,093 ft4,186 ft4,189 ft9,667 ft
30 A1,395 ft2,790 ft2,792 ft6,445 ft
40 A1,046 ft2,093 ft2,094 ft4,833 ft
50 A837 ft1,674 ft1,675 ft3,867 ft

Calculate your exact run

How many 300 kcmil conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT112571012
IMC111346911
RMC111246811
PVC Sch 4011246810
PVC Sch 801113579

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 300 kcmil wire carry?
300 kcmil copper is estimated at 245 A at 60 °C, 289 A at 75 °C and 326 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 225 A at 75 °C.
What breaker size goes with 300 kcmil copper?
The largest standard overcurrent device that 300 kcmil copper supports at 75 °C is 250 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 300 kcmil wire?
The bare conductor is 0.5477 inches (13.912 mm) in diameter, which is 300,000 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.766 inches.
What is the resistance of 300 kcmil wire?
About 0.0346 ohms per 1000 feet for copper and 0.0567 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 300 kcmil wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 300 kcmil copper stays under 3% voltage drop for about 2093 feet one-way. Doubling the voltage roughly doubles the allowable distance.