600 kcmil Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 600 kcmil conductors in copper and aluminium.

Quick answer

600 kcmil copper carries about 454 A at 75 °C (384 A at 60 °C, 511 A at 90 °C). The bare conductor is 0.7746 in (19.67 mm) and 600,000 circular mils, with 0.0173 Ω per 1000 ft. It pairs with a 450 A breaker at 75 °C terminations.

Copper 75 °C

454A

Aluminium 75 °C

354A

Diameter

0.7746in

Circular mils

600,000

Full specification

Size designation600 kcmil
AWG gauge numbern/a (kcmil size)
Circular mils600,000
kcmil600.00
Bare diameter (in)0.7746
Bare diameter (mm)19.675
Cross-section (mm²)304.03
THHN/THWN-2 OD (in)1.051
Insulated area (sq in)0.8676
Copper resistance (Ω/1000 ft)0.0173
Aluminium resistance (Ω/1000 ft)0.0283
Max standard breaker (Cu, 75 °C)450 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3511 A467 A417 A361 A
6409 A373 A334 A289 A
9358 A327 A292 A253 A
15256 A233 A208 A181 A
25230 A210 A188 A163 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 454 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 600 kcmil copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A8,372 ft16,744 ft16,757 ft38,670 ft
15 A5,581 ft11,162 ft11,171 ft25,780 ft
20 A4,186 ft8,372 ft8,378 ft19,335 ft
30 A2,790 ft5,581 ft5,585 ft12,890 ft
40 A2,093 ft4,186 ft4,189 ft9,667 ft
50 A1,674 ft3,348 ft3,351 ft7,734 ft

Calculate your exact run

How many 600 kcmil conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT112456
IMC1111346
RMC111345
PVC Sch 40111345
PVC Sch 80111245

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 600 kcmil wire carry?
600 kcmil copper is estimated at 384 A at 60 °C, 454 A at 75 °C and 511 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 354 A at 75 °C.
What breaker size goes with 600 kcmil copper?
The largest standard overcurrent device that 600 kcmil copper supports at 75 °C is 450 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 600 kcmil wire?
The bare conductor is 0.7746 inches (19.675 mm) in diameter, which is 600,000 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 1.051 inches.
What is the resistance of 600 kcmil wire?
About 0.0173 ohms per 1000 feet for copper and 0.0283 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 600 kcmil wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 600 kcmil copper stays under 3% voltage drop for about 4186 feet one-way. Doubling the voltage roughly doubles the allowable distance.