Rigid Conduit Fill Chart (RMC & IMC)

Maximum conductor count for rigid metal conduit (RMC) and intermediate metal conduit (IMC), computed from published internal diameters and nominal THHN outside diameters.

Quick answer

1/2 inch RMC holds 9 12 AWG THHN conductors and 3/4 inch holds 16. IMC has a thinner wall and slightly more usable area, holding 10 and 17 in the same trade sizes. Fill limits are 40% for three or more conductors, 31% for two and 53% for one.

RMC (rigid metal conduit) — maximum THHN/THWN-2 conductors

Same-size conductors only. Mixed sizes need the conduit fill calculator.

Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1222366385140200200200200
12 AWG916264562102146200200200
10 AWG5101628396492142189200
8 AWG3591622375381109140
6 AWG147121626385979101
4 AWG1247101623364862
3 AWG113681419304152
2 AWG113571116253444
1 AWG11135812192532
1/0 AWG1134710162127
2/0 AWG112368131823
3/0 AWG111357111519
4/0 AWG1114691215
Counts computed at 53% for one conductor, 31% for two and 40% for three or more.
Published standard — source: RMC (rigid metal conduit) internal diameters from the product standard; conductor OD from nominal THHN dimensions

IMC (intermediate metal conduit) — maximum THHN/THWN-2 conductors

Same-size conductors only. Mixed sizes need the conduit fill calculator.

Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1424396891150200200200200
12 AWG1017284967109154200200200
10 AWG6111831426897150200200
8 AWG36101724395686115148
6 AWG247121728406283107
4 AWG1247101724385166
3 AWG113691421324356
2 AWG113571217273647
1 AWG11145913202734
1/0 AWG1134711172229
2/0 AWG112469141924
3/0 AWG111357111520
4/0 AWG1124691316
Counts computed at 53% for one conductor, 31% for two and 40% for three or more.
Published standard — source: IMC (intermediate metal conduit) internal diameters from the product standard; conductor OD from nominal THHN dimensions

Rigid conduit internal area by trade size

Trade sizeRMC areaIMC area
1/2"0.314 (0.125)0.342 (0.137)
3/4"0.549 (0.220)0.586 (0.235)
1"0.887 (0.355)0.959 (0.384)
1-1/4"1.526 (0.610)1.647 (0.659)
1-1/2"2.071 (0.829)2.225 (0.890)
2"3.408 (1.363)3.631 (1.452)
2-1/2"4.866 (1.946)5.135 (2.054)
3"7.499 (3.000)7.922 (3.169)
3-1/2"10.010 (4.004)10.584 (4.234)
4"12.883 (5.153)13.631 (5.452)
Total internal cross-sectional area in square inches, with the 40% usable figure in brackets.

Source & method: Area is A = π × (id / 2)². Internal diameters are nominal published product dimensions; see the methodology page.

Conductor outside diameters used

SizeInsulated OD (in)Area (sq in)
18 AWG0.0840.0055
16 AWG0.0960.0072
14 AWG0.1110.0097
12 AWG0.1300.0133
10 AWG0.1640.0211
8 AWG0.2160.0366
6 AWG0.2540.0507
4 AWG0.3240.0824
3 AWG0.3520.0973
2 AWG0.3840.1158
1 AWG0.4460.1562
1/0 AWG0.4860.1855
2/0 AWG0.5320.2223
3/0 AWG0.5810.2651
4/0 AWG0.6420.3237
250 kcmil0.7110.3970
300 kcmil0.7660.4608
350 kcmil0.8170.5242
400 kcmil0.8640.5863
500 kcmil0.9490.7073
600 kcmil1.0510.8676
750 kcmil1.1581.0532
Nominal THHN/THWN-2 insulated outside diameter and the area each conductor consumes.

Frequently asked

How many 12 AWG wires fit in 1/2 inch RMC?
Using nominal THHN outside diameters and the 40% fill rule, 9 12 AWG conductors fit in 1/2 inch RMC. Every conductor counts, including the neutral and the equipment grounding conductor.
What is the maximum fill percentage for rigid conduit?
40% of the internal cross-sectional area for three or more conductors, 31% for exactly two and 53% for a single conductor. Nipples 24 inches or shorter are permitted at 60%.
What size rigid conduit do I need for three 10 AWG conductors?
Three 10 AWG THHN conductors need at least 1/2 inch RMC at 40% fill. Add a fourth conductor and re-check, because the count changes the usable area.
Does the ground wire count toward conduit fill?
Yes. Fill counts every conductor in the raceway. Grounds are excluded only from the ampacity adjustment count for current-carrying conductors, never from fill.
Where do these rigid conduit numbers come from?
Internal diameters are published product dimensions from the relevant ANSI/UL/ASTM product standards. Area is computed as pi times radius squared, and the conductor count is the largest whole number that fits inside the applicable fill percentage. No code table is reproduced.

Mixed conductor sizes

These tables cover one conductor size at a time. Use the conduit fill calculator for mixed sizes, or see the full conduit fill chart for every raceway type side by side.