8 AWG Wire — Amp Rating, Ampacity & Diameter
Ampacity, geometry, resistance, conduit fill and maximum run length for 8 AWG conductors in copper and aluminium.
Quick answer
Copper 75 °C
44A
Aluminium 75 °C
34A
Diameter
0.1285in
Circular mils
16,510
Full specification
| Size designation | 8 AWG |
|---|---|
| AWG gauge number | 8 |
| Circular mils | 16,510 |
| kcmil | 16.51 |
| Bare diameter (in) | 0.1285 |
| Bare diameter (mm) | 3.264 |
| Cross-section (mm²) | 8.37 |
| THHN/THWN-2 OD (in) | 0.216 |
| Insulated area (sq in) | 0.0366 |
| Copper resistance (Ω/1000 ft) | 0.6282 |
| Aluminium resistance (Ω/1000 ft) | 1.0297 |
| Max standard breaker (Cu, 75 °C) | 40 A |
Ampacity with derating
Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 49 A | 45 A | 40 A | 35 A |
| 6 | 39 A | 36 A | 32 A | 28 A |
| 9 | 34 A | 31 A | 28 A | 24 A |
| 15 | 25 A | 22 A | 20 A | 17 A |
| 25 | 22 A | 20 A | 18 A | 16 A |
Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 44 A. Run your own conditions.
Maximum run length at 3% voltage drop
One-way distance for 8 AWG copper before drop exceeds 3%.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 10 A | 230 ft | 460 ft | 461 ft | 1,064 ft |
| 15 A | 153 ft | 307 ft | 307 ft | 709 ft |
| 20 A | 115 ft | 230 ft | 230 ft | 532 ft |
| 30 A | 76 ft | 153 ft | 153 ft | 354 ft |
| 40 A | 57 ft | 115 ft | 115 ft | 266 ft |
| 50 A | 46 ft | 92 ft | 92 ft | 212 ft |
How many 8 AWG conductors fit in conduit
Maximum count of this size alone, at the fill percentage matching the resulting count.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 3 | 5 | 9 | 16 | 22 | 36 | 63 | 96 | 126 | 161 |
| IMC | 3 | 6 | 10 | 17 | 24 | 39 | 56 | 86 | 115 | 148 |
| RMC | 3 | 5 | 9 | 16 | 22 | 37 | 53 | 81 | 109 | 140 |
| PVC Sch 40 | 3 | 5 | 9 | 15 | 21 | 35 | 51 | 79 | 106 | 137 |
| PVC Sch 80 | 1 | 4 | 7 | 13 | 18 | 31 | 44 | 70 | 94 | 122 |
8 AWG copper ampacity vs aluminium ampacity
Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.
| Material | 60 °C (TW, NM-B) | 75 °C (THW, THWN, XHHW) | 90 °C (THHN, THWN-2, XHHW-2) |
|---|---|---|---|
| Copper | 37 A | 44 A | 49 A |
| Aluminium | 29 A | 34 A | 39 A |
The 8 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 44 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 49 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.
Aluminium of the same size carries roughly 77% of the copper value (34 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.
Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.
Neighbouring sizes
Compare 8 AWG with the sizes immediately above and below it before sizing a circuit.
Circuits that use 8 AWG
Breaker ratings whose smallest copper conductor at 75 °C terminations is 8 AWG.
8 AWG amp rating, diameter and metric equivalent
The amp rating for 8 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 37 A on a 60 °C conductor, 44 A at 75 °C and 49 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.
Geometrically, 8 AWG is 0.1285 in (3.26 mm) in bare diameter, which is 16,510 circular mils. The cross sectional area works out to 8.37 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.
American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.
Where 8 AWG actually gets used
8 AWG covers 40 to 50 A work: ranges and cooktops on smaller installations, Level 2 EV chargers at 32 A continuous, hot tubs and spa panels, welders, and feeders to detached garage subpanels. At this size the conductor is nearly always stranded and pulled as THHN/THWN-2 in raceway or as SER/SE cable rather than NM-B.
The 75 °C termination limit dominates from here up. The 90 °C insulation rating on the conductor is a derating base only — the breaker lug, the panel bus and the appliance terminal block are what cap the usable ampacity, which is why the 75 °C column is the number that appears on nearly every 8 AWG installation drawing.
Frequently asked
- How many amps can 8 AWG wire carry?
- 8 AWG copper is estimated at 37 A at 60 °C, 44 A at 75 °C and 49 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 34 A at 75 °C.
- What is the amp rating for 8 gauge wire?
- Use 44 A for 8 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 37 A instead when the conductor is inside NM-B cable, and treat 49 A as the derating base only. Aluminium of the same size is about 34 A at 75 °C.
- What breaker size goes with 8 AWG copper?
- The largest standard overcurrent device that 8 AWG copper supports at 75 °C is 40 A. For a continuous load, the load itself must not exceed 80% of that rating.
- What is the diameter of 8 AWG wire?
- The bare conductor is 0.1285 inches (3.264 mm) in diameter, which is 16,510 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.216 inches.
- What is the resistance of 8 AWG wire?
- About 0.6282 ohms per 1000 feet for copper and 1.0297 ohms per 1000 feet for aluminium, at 75 °C.
- How far can I run 8 AWG wire?
- Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 8 AWG copper stays under 3% voltage drop for about 115 feet one-way. Doubling the voltage roughly doubles the allowable distance.
Related charts & calculators
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.
- Wire Gauge ChartAWG diameter, circular mils, resistance and amp capacity in one table.
- Wire Size ChartWhat size wire for each breaker rating and typical circuit.
- kcmil Wire Size ChartMCM to AWG conversion, circular mils, resistance and ampacity for 250-750 kcmil.