12 AWG Wire — Amp Rating, Ampacity & Diameter
Ampacity, geometry, resistance, conduit fill and maximum run length for 12 AWG conductors in copper and aluminium.
Quick answer
Copper 75 °C
24A
Aluminium 75 °C
19A
Diameter
0.0808in
Circular mils
6,530
Full specification
| Size designation | 12 AWG |
|---|---|
| AWG gauge number | 12 |
| Circular mils | 6,530 |
| kcmil | 6.53 |
| Bare diameter (in) | 0.0808 |
| Bare diameter (mm) | 2.052 |
| Cross-section (mm²) | 3.31 |
| THHN/THWN-2 OD (in) | 0.130 |
| Insulated area (sq in) | 0.0133 |
| Copper resistance (Ω/1000 ft) | 1.5882 |
| Aluminium resistance (Ω/1000 ft) | 2.6034 |
| Max standard breaker (Cu, 75 °C) | 20 A |
Ampacity with derating
Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 27 A | 25 A | 22 A | 19 A |
| 6 | 22 A | 20 A | 18 A | 15 A |
| 9 | 19 A | 17 A | 15 A | 13 A |
| 15 | 14 A | 12 A | 11 A | 10 A |
| 25 | 12 A | 11 A | 10 A | 9 A |
Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 24 A. Run your own conditions.
Maximum run length at 3% voltage drop
One-way distance for 12 AWG copper before drop exceeds 3%.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 10 A | 91 ft | 182 ft | 182 ft | 420 ft |
| 15 A | 60 ft | 121 ft | 121 ft | 280 ft |
| 20 A | 45 ft | 91 ft | 91 ft | 210 ft |
| 30 A | 30 ft | 60 ft | 60 ft | 140 ft |
| 40 A | 22 ft | 45 ft | 45 ft | 105 ft |
| 50 A | 18 ft | 36 ft | 36 ft | 84 ft |
How many 12 AWG conductors fit in conduit
Maximum count of this size alone, at the fill percentage matching the resulting count.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 | 347 | 400 |
| IMC | 10 | 17 | 28 | 49 | 67 | 109 | 154 | 238 | 318 | 400 |
| RMC | 9 | 16 | 26 | 45 | 62 | 102 | 146 | 225 | 301 | 388 |
| PVC Sch 40 | 8 | 15 | 25 | 43 | 59 | 99 | 141 | 219 | 293 | 378 |
| PVC Sch 80 | 6 | 12 | 20 | 37 | 51 | 86 | 124 | 194 | 261 | 339 |
12 AWG copper ampacity vs aluminium ampacity
Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.
| Material | 60 °C (TW, NM-B) | 75 °C (THW, THWN, XHHW) | 90 °C (THHN, THWN-2, XHHW-2) |
|---|---|---|---|
| Copper | 20 A | 24 A | 27 A |
| Aluminium | 16 A | 19 A | 21 A |
The 12 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 24 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 27 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.
Aluminium of the same size carries roughly 79% of the copper value (19 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.
Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.
Neighbouring sizes
Compare 12 AWG with the sizes immediately above and below it before sizing a circuit.
Circuits that use 12 AWG
Breaker ratings whose smallest copper conductor at 75 °C terminations is 12 AWG.
12 AWG amp rating, diameter and metric equivalent
The amp rating for 12 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 20 A on a 60 °C conductor, 24 A at 75 °C and 27 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.
Geometrically, 12 AWG is 0.0808 in (2.05 mm) in bare diameter, which is 6,530 circular mils. The cross sectional area works out to 3.31 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.
American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.
12 AWG in millimetres — diameter, mm² and the metric equivalent
AWG is a gauge number, not a dimension, so metric shops need the conversion before ordering.
| Bare diameter | 2.052 mm (0.0808 in) |
|---|---|
| Cross-sectional area | 3.31 mm² |
| Nearest IEC 60228 size at or above | 4 mm² |
| Insulated OD (THHN/THWN-2) | 3.30 mm (0.130 in) |
12 AWG measures 2.05 mm across the bare copper, which is 3.31 mm² of cross-section. Substituting 4 mm² cable is the safe direction because it is the first standard metric size that is not smaller; going the other way — for example calling 12 AWG the same as 2.5 mm² — under-sizes the conductor. Metric cable is also specified by area while AWG is specified by gauge step, so the two systems never coincide exactly.
Source & method: Diameter from the ASTM B258 gauge formula; area converted arithmetically. No code table is reproduced.
How many watts can 12 AWG wire handle?
Watts are amps times volts, so the wattage depends entirely on the system voltage.
| System | Max watts (non-continuous) | Max watts (continuous, 80%) |
|---|---|---|
| 12 V DC | 240 W | 192 W |
| 24 V DC | 480 W | 384 W |
| 120 V AC, 1-phase | 2,400 W | 1,920 W |
| 240 V AC, 1-phase | 4,800 W | 3,840 W |
| 277 V AC, 1-phase | 5,540 W | 4,432 W |
Low-voltage DC is the case where this table misleads if used alone. At 12 V the wattage looks generous, but voltage drop — not heat — sets the real limit, because a 3% allowance is only 0.36 V. For any 12 V or 24 V run longer than a few feet, size on drop with the voltage drop calculator and treat the wattage above as a ceiling you will rarely reach.
12/2 and 12/3 cable — what the second number means
Cable designations count insulated current-carrying conductors, not total wires.
A cable marked 12/2 contains two insulated 12 AWG conductors — one ungrounded, one grounded — plus a bare equipment grounding conductor that is not counted in the name. 12/3 adds a third insulated conductor, typically red, for switch legs, travellers or a second hot leg. The ampacity is identical in both cases, because it is a property of the conductor size and insulation, not the conductor count: still 20 A on the 60 °C basis that non-metallic sheathed cable is held to.
Read the higher-temperature figures as insulation and calculation properties, not as usable circuit ratings. The insulation used in NM-B is a 90 °C material, and the same copper conductor with 90 °C insulation installed in a raceway computes to a higher ampacity — but a non-metallic sheathed cable assembly must be applied at the 60 °C ampacity of 20 A. On top of that, 12 AWG copper is limited to a 20 A overcurrent device by the small-conductor rule, which applies to 14, 12 and 10 AWG copper regardless of insulation, with only narrow listed exceptions such as certain motor and A/C equipment circuits. So the 27 A in the 90 °C column above is a calculated value for a 90 °C-rated conductor, used as the starting point for derating — never as a load limit for 12/2 NM-B. In practice a standard residential 12/2 NM-B circuit is protected at no more than 20 A, and the load on it must stay within that.
That is also why 12/2 NM-B and 12 AWG THHN in conduit are not interchangeable on paper: THHN computes to 24 A where every termination in the circuit is listed for 75 °C, while the NM cable stays at 20 A regardless of the breaker it lands on. Termination temperature is a ceiling in both cases — 90 °C insulation on equipment with 75 °C lugs is still read from the 75 °C column. Separately, where more than three current-carrying conductors run together in one raceway or cable, or cables are bundled together for more than 24 inches so that more than three current-carrying conductors share the bundle, ampacity adjustment applies to all of them — which lowers these numbers further, never raises them.
Solid versus stranded does not change ampacity either. Solid 12 AWG is standard in residential branch circuits; stranded is used where the conductor must flex or be pulled around tight bends. Both have the same 6,530 circular mils of copper, though stranded has a slightly larger overall diameter, which matters for conduit fill and for termination lugs.
What 12 AWG means
12 AWG is a gauge designation, not a measurement. The number counts the drawing dies historically used to pull the wire down to size, so it runs backwards: a higher number is a thinner conductor. Each single step changes diameter by about 12.2% and area by about 26%, which is why moving from 12 AWG to the next size up is a meaningful jump in both cost and capacity rather than a rounding change.
Written forms you will see for the same conductor include 12 AWG, 12 ga, 12 gauge and #12. They are identical. What is not identical is the cable assembly the conductor ships in, the insulation rated on it, or the termination temperature at the breaker — all three can lower the usable ampacity below the 24 A that 12 AWG copper reaches at 75 °C.
Where 12 AWG actually gets used — and why it is the default upsize
12 AWG is the workhorse of North American branch-circuit wiring: protected at 20 A in ordinary building wiring by the same small-conductor rule that caps 14 AWG at 15 A, and used for every circuit type where 15 A is not enough. Kitchen and dining small-appliance circuits, laundry receptacles, bathroom receptacle circuits, garage and workshop outlets, and nearly all commercial receptacle work land here.
The reason it is the default upsize is voltage drop, not current. A 20 A load on 12 AWG copper holds 3% drop far enough to cover most residential home runs, and stepping from 14 to 12 buys roughly 60% more circular mils for a marginal increase in material cost. Many electricians pull 12 AWG throughout and set the device rating per circuit rather than stocking two cable sizes.
12 AWG is also where the 60/75/90 °C column distinction starts to bite in a way installers notice. Inside 12/2 or 12/3 NM-B the conductor is read at the 60 °C column, while the same copper in THHN in conduit at 40 °C ambient derates from the 90 °C base — two very different numbers for the same wire, and the source of most argument about what 12 AWG 'is' rated for.
Continuous loads are the other trap. A load running three hours or more is designed at 125%, so a 20 A device on 12 AWG supports only 16 A of continuous current. That is exactly why a 16 A EV charger, a commercial lighting run, or a long-cycle heater lands on 12 AWG at 20 A while a nominally identical 20 A intermittent load does not need the same margin.
Frequently asked
- How many amps can 12 AWG wire carry?
- 12 AWG copper is estimated at 20 A at 60 °C, 24 A at 75 °C and 27 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 19 A at 75 °C.
- What is the amp rating for 12 gauge wire?
- Use 24 A for 12 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 20 A instead when the conductor is inside NM-B cable, and treat 27 A as the derating base only. Aluminium of the same size is about 19 A at 75 °C.
- What breaker size goes with 12 AWG copper?
- The largest standard overcurrent device that 12 AWG copper supports at 75 °C is 20 A. For a continuous load, the load itself must not exceed 80% of that rating.
- What is the diameter of 12 AWG wire?
- The bare conductor is 0.0808 inches (2.052 mm) in diameter, which is 6,530 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.130 inches.
- What is the resistance of 12 AWG wire?
- About 1.5882 ohms per 1000 feet for copper and 2.6034 ohms per 1000 feet for aluminium, at 75 °C.
- How far can I run 12 AWG wire?
- Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 12 AWG copper stays under 3% voltage drop for about 45 feet one-way. Doubling the voltage roughly doubles the allowable distance.
Related charts & calculators
- kcmil Wire Size ChartMCM to AWG conversion, circular mils, resistance and ampacity for 250-750 kcmil.
- Conduit Fill ChartMaximum THHN conductors per trade size for every raceway type.
- EMT Conduit Fill ChartConductor counts and internal areas for electrical metallic tubing.
- PVC Conduit Fill ChartSchedule 40 and Schedule 80 conductor counts and usable areas.
- Rigid Conduit Fill ChartRMC and IMC conductor counts per trade size, side by side.
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.