1 AWG Wire — Amp Rating, Ampacity & Diameter

Ampacity, geometry, resistance, conduit fill and maximum run length for 1 AWG conductors in copper and aluminium.

Quick answer

1 AWG copper carries about 126 A at 75 °C (107 A at 60 °C, 142 A at 90 °C). The bare conductor is 0.2893 in (7.35 mm) and 83,693 circular mils, with 0.1239 Ω per 1000 ft. It pairs with a 125 A breaker at 75 °C terminations.

Copper 75 °C

126A

Aluminium 75 °C

98A

Diameter

0.2893in

Circular mils

83,693

Full specification

Size designation1 AWG
AWG gauge number1
Circular mils83,693
kcmil83.69
Bare diameter (in)0.2893
Bare diameter (mm)7.348
Cross-section (mm²)42.41
THHN/THWN-2 OD (in)0.446
Insulated area (sq in)0.1562
Copper resistance (Ω/1000 ft)0.1239
Aluminium resistance (Ω/1000 ft)0.2031
Max standard breaker (Cu, 75 °C)125 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3142 A130 A116 A100 A
6114 A104 A93 A80 A
999 A91 A81 A70 A
1571 A65 A58 A50 A
2564 A58 A52 A45 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 126 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 1 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A1,167 ft2,335 ft2,337 ft5,394 ft
15 A778 ft1,557 ft1,558 ft3,596 ft
20 A583 ft1,167 ft1,168 ft2,697 ft
30 A389 ft778 ft779 ft1,798 ft
40 A291 ft583 ft584 ft1,348 ft
50 A233 ft467 ft467 ft1,078 ft

Calculate your exact run

How many 1 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT11135814222937
IMC11145913202734
RMC11135812192532
PVC Sch 40—1135812182432
PVC Sch 80—1134710162228

Mix conductor sizes in the fill calculator

1 AWG copper ampacity vs aluminium ampacity

Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.

Material60 °C (TW, NM-B)75 °C (THW, THWN, XHHW)90 °C (THHN, THWN-2, XHHW-2)
Copper107 A126 A142 A
Aluminium83 A98 A111 A

The 1 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 126 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 142 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.

Aluminium of the same size carries roughly 78% of the copper value (98 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.

Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.

Neighbouring sizes

Compare 1 AWG with the sizes immediately above and below it before sizing a circuit.

SizeCu 75 °CAl 75 °CDiameter (in)Circular mils
3 AWG93 A73 A0.229452,635
2 AWG108 A84 A0.257666,371
1 AWG (this page)126 A98 A0.289383,693
1/0 AWG146 A114 A0.3249105,535
2/0 AWG170 A133 A0.3648133,077

Circuits that use 1 AWG

Breaker ratings whose smallest copper conductor at 75 °C terminations is 1 AWG.

1 AWG amp rating, diameter and metric equivalent

The amp rating for 1 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 107 A on a 60 °C conductor, 126 A at 75 °C and 142 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.

Geometrically, 1 AWG is 0.2893 in (7.35 mm) in bare diameter, which is 83,693 circular mils. The cross sectional area works out to 42.41 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.

American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.

Where 1 AWG actually gets used

1 AWG is another interval size, used mainly where a calculated feeder lands between 2 AWG and 1/0. In copper it serves feeders in the 130 to 150 A range; in aluminium it appears on 110 to 125 A panel feeders where the designer did not want to jump straight to 1/0.

It matters most in retrofit work. When an existing raceway cannot be enlarged, 1 AWG sometimes buys the ampacity needed to reuse the conduit where 1/0 would not fit at the applicable fill percentage. That single geometric fact is why the size survives on drawings at all.

Termination hardware is the other consideration: many 100 to 125 A panel main lugs are listed over a range that ends near 1 AWG or 1/0, so the panel label, not the conductor table, decides whether a given size can legally land there.

Frequently asked

How many amps can 1 AWG wire carry?
1 AWG copper is estimated at 107 A at 60 °C, 126 A at 75 °C and 142 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 98 A at 75 °C.
What is the amp rating for 1 gauge wire?
Use 126 A for 1 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 107 A instead when the conductor is inside NM-B cable, and treat 142 A as the derating base only. Aluminium of the same size is about 98 A at 75 °C.
What breaker size goes with 1 AWG copper?
The largest standard overcurrent device that 1 AWG copper supports at 75 °C is 125 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 1 AWG wire?
The bare conductor is 0.2893 inches (7.348 mm) in diameter, which is 83,693 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.446 inches.
What is the resistance of 1 AWG wire?
About 0.1239 ohms per 1000 feet for copper and 0.2031 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 1 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 1 AWG copper stays under 3% voltage drop for about 583 feet one-way. Doubling the voltage roughly doubles the allowable distance.