1 AWG Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 1 AWG conductors in copper and aluminium.

Quick answer

1 AWG copper carries about 126 A at 75 °C (107 A at 60 °C, 142 A at 90 °C). The bare conductor is 0.2893 in (7.35 mm) and 83,693 circular mils, with 0.1239 Ω per 1000 ft. It pairs with a 125 A breaker at 75 °C terminations.

Copper 75 °C

126A

Aluminium 75 °C

98A

Diameter

0.2893in

Circular mils

83,693

Full specification

Size designation1 AWG
AWG gauge number1
Circular mils83,693
kcmil83.69
Bare diameter (in)0.2893
Bare diameter (mm)7.348
Cross-section (mm²)42.41
THHN/THWN-2 OD (in)0.446
Insulated area (sq in)0.1562
Copper resistance (Ω/1000 ft)0.1239
Aluminium resistance (Ω/1000 ft)0.2031
Max standard breaker (Cu, 75 °C)125 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3142 A130 A116 A100 A
6114 A104 A93 A80 A
999 A91 A81 A70 A
1571 A65 A58 A50 A
2564 A58 A52 A45 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 126 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 1 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A1,167 ft2,335 ft2,337 ft5,394 ft
15 A778 ft1,557 ft1,558 ft3,596 ft
20 A583 ft1,167 ft1,168 ft2,697 ft
30 A389 ft778 ft779 ft1,798 ft
40 A291 ft583 ft584 ft1,348 ft
50 A233 ft467 ft467 ft1,078 ft

Calculate your exact run

How many 1 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT11135814222937
IMC11145913202734
RMC11135812192532
PVC Sch 401135812182432
PVC Sch 801134710162228

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 1 AWG wire carry?
1 AWG copper is estimated at 107 A at 60 °C, 126 A at 75 °C and 142 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 98 A at 75 °C.
What breaker size goes with 1 AWG copper?
The largest standard overcurrent device that 1 AWG copper supports at 75 °C is 125 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 1 AWG wire?
The bare conductor is 0.2893 inches (7.348 mm) in diameter, which is 83,693 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.446 inches.
What is the resistance of 1 AWG wire?
About 0.1239 ohms per 1000 feet for copper and 0.2031 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 1 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 1 AWG copper stays under 3% voltage drop for about 583 feet one-way. Doubling the voltage roughly doubles the allowable distance.