10 AWG Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 10 AWG conductors in copper and aluminium.

Quick answer

10 AWG copper carries about 32 A at 75 °C (27 A at 60 °C, 37 A at 90 °C). The bare conductor is 0.1019 in (2.59 mm) and 10,383 circular mils, with 0.9988 Ω per 1000 ft. It pairs with a 30 A breaker at 75 °C terminations.

Copper 75 °C

32A

Aluminium 75 °C

25A

Diameter

0.1019in

Circular mils

10,383

Full specification

Size designation10 AWG
AWG gauge number10
Circular mils10,383
kcmil10.38
Bare diameter (in)0.1019
Bare diameter (mm)2.588
Cross-section (mm²)5.26
THHN/THWN-2 OD (in)0.164
Insulated area (sq in)0.0211
Copper resistance (Ω/1000 ft)0.9988
Aluminium resistance (Ω/1000 ft)1.6373
Max standard breaker (Cu, 75 °C)30 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
337 A34 A30 A26 A
630 A27 A24 A21 A
926 A24 A21 A18 A
1519 A17 A15 A13 A
2517 A15 A14 A12 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 32 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 10 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A144 ft289 ft289 ft669 ft
15 A96 ft193 ft193 ft446 ft
20 A72 ft144 ft144 ft334 ft
30 A48 ft96 ft96 ft223 ft
40 A36 ft72 ft72 ft167 ft
50 A28 ft57 ft57 ft133 ft

Calculate your exact run

How many 10 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT51016283863110167218279
IMC6111831426897150200258
RMC5101628396492142189243
PVC Sch 40591527376288137184237
PVC Sch 80471323325477121164213

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 10 AWG wire carry?
10 AWG copper is estimated at 27 A at 60 °C, 32 A at 75 °C and 37 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 25 A at 75 °C.
What breaker size goes with 10 AWG copper?
The largest standard overcurrent device that 10 AWG copper supports at 75 °C is 30 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 10 AWG wire?
The bare conductor is 0.1019 inches (2.588 mm) in diameter, which is 10,383 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.164 inches.
What is the resistance of 10 AWG wire?
About 0.9988 ohms per 1000 feet for copper and 1.6373 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 10 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 10 AWG copper stays under 3% voltage drop for about 72 feet one-way. Doubling the voltage roughly doubles the allowable distance.

Materials for this size

Related charts & calculators