18 AWG Wire — Amp Rating, Ampacity & Diameter
Ampacity, geometry, resistance, conduit fill and maximum run length for 18 AWG conductors in copper and aluminium.
Quick answer
Copper 75 °C
10A
Aluminium 75 °C
8A
Diameter
0.0403in
Circular mils
1,624
Full specification
| Size designation | 18 AWG |
|---|---|
| AWG gauge number | 18 |
| Circular mils | 1,624 |
| kcmil | 1.62 |
| Bare diameter (in) | 0.0403 |
| Bare diameter (mm) | 1.024 |
| Cross-section (mm²) | 0.82 |
| THHN/THWN-2 OD (in) | 0.084 |
| Insulated area (sq in) | 0.0055 |
| Copper resistance (Ω/1000 ft) | 6.3861 |
| Aluminium resistance (Ω/1000 ft) | 10.4680 |
| Max standard breaker (Cu, 75 °C) | Below branch-circuit ratings |
Ampacity with derating
Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 11 A | 10 A | 9 A | 8 A |
| 6 | 9 A | 8 A | 7 A | 6 A |
| 9 | 8 A | 7 A | 6 A | 5 A |
| 15 | 6 A | 5 A | 4 A | 4 A |
| 25 | 5 A | 5 A | 4 A | 3 A |
Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 10 A. Run your own conditions.
Maximum run length at 3% voltage drop
One-way distance for 18 AWG copper before drop exceeds 3%.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 10 A | 22 ft | 45 ft | 45 ft | 104 ft |
| 15 A | 15 ft | 30 ft | 30 ft | 69 ft |
| 20 A | 11 ft | 22 ft | 22 ft | 52 ft |
| 30 A | 7 ft | 15 ft | 15 ft | 34 ft |
| 40 A | 5 ft | 11 ft | 11 ft | 26 ft |
| 50 A | 4 ft | 9 ft | 9 ft | 20 ft |
How many 18 AWG conductors fit in conduit
Maximum count of this size alone, at the fill percentage matching the resulting count.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 21 | 38 | 62 | 107 | 146 | 242 | 400 | 400 | 400 | 400 |
| IMC | 24 | 42 | 69 | 118 | 160 | 262 | 370 | 400 | 400 | 400 |
| RMC | 22 | 39 | 64 | 110 | 149 | 245 | 351 | 400 | 400 | 400 |
| PVC Sch 40 | 20 | 36 | 60 | 104 | 143 | 237 | 338 | 400 | 400 | 400 |
| PVC Sch 80 | 15 | 29 | 49 | 89 | 123 | 207 | 297 | 400 | 400 | 400 |
18 AWG copper ampacity vs aluminium ampacity
Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.
| Material | 60 °C (TW, NM-B) | 75 °C (THW, THWN, XHHW) | 90 °C (THHN, THWN-2, XHHW-2) |
|---|---|---|---|
| Copper | 8 A | 10 A | 11 A |
| Aluminium | 6 A | 8 A | 9 A |
The 18 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 10 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 11 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.
Aluminium of the same size carries roughly 80% of the copper value (8 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.
Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.
Neighbouring sizes
Compare 18 AWG with the sizes immediately above and below it before sizing a circuit.
18 AWG amp rating, diameter and metric equivalent
The amp rating for 18 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 8 A on a 60 °C conductor, 10 A at 75 °C and 11 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.
Geometrically, 18 AWG is 0.0403 in (1.02 mm) in bare diameter, which is 1,624 circular mils. The cross sectional area works out to 0.82 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.
American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.
Where 18 AWG actually gets used
18 AWG is not branch-circuit wire. It appears as fixture wire inside luminaires, as flexible cord conductors on small appliances, as control and signal conductors, and in class 2 low-voltage circuits such as thermostats and doorbells, where the power source itself limits the available current.
Because the conductor is small, mechanical damage rather than heating is the usual failure: broken strands at a crimp, a nicked conductor in a fixture canopy, a strand bridging a terminal. Supports, strain relief and the correct crimp barrel matter more here than any ampacity calculation.
Frequently asked
- How many amps can 18 AWG wire carry?
- 18 AWG copper is estimated at 8 A at 60 °C, 10 A at 75 °C and 11 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 8 A at 75 °C.
- What is the amp rating for 18 gauge wire?
- Use 10 A for 18 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 8 A instead when the conductor is inside NM-B cable, and treat 11 A as the derating base only. Aluminium of the same size is about 8 A at 75 °C.
- What breaker size goes with 18 AWG copper?
- 18 AWG is below the smallest standard branch-circuit device rating and is normally used for control, signal or fixture wiring rather than a protected branch circuit.
- What is the diameter of 18 AWG wire?
- The bare conductor is 0.0403 inches (1.024 mm) in diameter, which is 1,624 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.084 inches.
- What is the resistance of 18 AWG wire?
- About 6.3861 ohms per 1000 feet for copper and 10.4680 ohms per 1000 feet for aluminium, at 75 °C.
- How far can I run 18 AWG wire?
- Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 18 AWG copper stays under 3% voltage drop for about 11 feet one-way. Doubling the voltage roughly doubles the allowable distance.
Related charts & calculators
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.
- Allen Wrench Size ChartHex key sizes with SAE and metric cross-reference.
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.