16 AWG Wire — Amp Rating, Ampacity & Diameter
Ampacity, geometry, resistance, conduit fill and maximum run length for 16 AWG conductors in copper and aluminium.
Quick answer
Copper 75 °C
13A
Aluminium 75 °C
10A
Diameter
0.0508in
Circular mils
2,583
Full specification
| Size designation | 16 AWG |
|---|---|
| AWG gauge number | 16 |
| Circular mils | 2,583 |
| kcmil | 2.58 |
| Bare diameter (in) | 0.0508 |
| Bare diameter (mm) | 1.290 |
| Cross-section (mm²) | 1.31 |
| THHN/THWN-2 OD (in) | 0.096 |
| Insulated area (sq in) | 0.0072 |
| Copper resistance (Ω/1000 ft) | 4.0151 |
| Aluminium resistance (Ω/1000 ft) | 6.5815 |
| Max standard breaker (Cu, 75 °C) | Below branch-circuit ratings |
Ampacity with derating
Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 15 A | 14 A | 12 A | 11 A |
| 6 | 12 A | 11 A | 10 A | 8 A |
| 9 | 11 A | 10 A | 9 A | 7 A |
| 15 | 8 A | 7 A | 6 A | 5 A |
| 25 | 7 A | 6 A | 6 A | 5 A |
Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 13 A. Run your own conditions.
Maximum run length at 3% voltage drop
One-way distance for 16 AWG copper before drop exceeds 3%.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 10 A | 36 ft | 72 ft | 72 ft | 166 ft |
| 15 A | 24 ft | 48 ft | 48 ft | 110 ft |
| 20 A | 18 ft | 36 ft | 36 ft | 83 ft |
| 30 A | 12 ft | 24 ft | 24 ft | 55 ft |
| 40 A | 9 ft | 18 ft | 18 ft | 41 ft |
| 50 A | 7 ft | 14 ft | 14 ft | 33 ft |
How many 16 AWG conductors fit in conduit
Maximum count of this size alone, at the fill percentage matching the resulting count.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 16 | 29 | 47 | 82 | 112 | 185 | 323 | 400 | 400 | 400 |
| IMC | 18 | 32 | 52 | 91 | 122 | 200 | 283 | 400 | 400 | 400 |
| RMC | 17 | 30 | 49 | 84 | 114 | 188 | 268 | 400 | 400 | 400 |
| PVC Sch 40 | 15 | 28 | 45 | 80 | 109 | 181 | 259 | 400 | 400 | 400 |
| PVC Sch 80 | 12 | 22 | 38 | 68 | 94 | 158 | 227 | 356 | 400 | 400 |
16 AWG copper ampacity vs aluminium ampacity
Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.
| Material | 60 °C (TW, NM-B) | 75 °C (THW, THWN, XHHW) | 90 °C (THHN, THWN-2, XHHW-2) |
|---|---|---|---|
| Copper | 11 A | 13 A | 15 A |
| Aluminium | 9 A | 10 A | 12 A |
The 16 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 13 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 15 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.
Aluminium of the same size carries roughly 77% of the copper value (10 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.
Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.
Neighbouring sizes
Compare 16 AWG with the sizes immediately above and below it before sizing a circuit.
16 AWG amp rating, diameter and metric equivalent
The amp rating for 16 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 11 A on a 60 °C conductor, 13 A at 75 °C and 15 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.
Geometrically, 16 AWG is 0.0508 in (1.29 mm) in bare diameter, which is 2,583 circular mils. The cross sectional area works out to 1.31 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.
American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.
Where 16 AWG actually gets used
16 AWG lives in cords and control wiring: extension cords and tool cords, appliance leads, motor control and interlock wiring, and fixture whips. It is used as flexible stranded cord conductor far more often than as a conductor pulled in raceway.
Cord ampacity is a different question from raceway ampacity, because a coiled or bundled cord cannot shed heat the way a single conductor in open air can. That is why a 16 AWG extension cord that is fine at 10 A for a short run overheats coiled on a reel, and why cord length and gauge are printed together on the tag.
Frequently asked
- How many amps can 16 AWG wire carry?
- 16 AWG copper is estimated at 11 A at 60 °C, 13 A at 75 °C and 15 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 10 A at 75 °C.
- What is the amp rating for 16 gauge wire?
- Use 13 A for 16 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 11 A instead when the conductor is inside NM-B cable, and treat 15 A as the derating base only. Aluminium of the same size is about 10 A at 75 °C.
- What breaker size goes with 16 AWG copper?
- 16 AWG is below the smallest standard branch-circuit device rating and is normally used for control, signal or fixture wiring rather than a protected branch circuit.
- What is the diameter of 16 AWG wire?
- The bare conductor is 0.0508 inches (1.290 mm) in diameter, which is 2,583 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.096 inches.
- What is the resistance of 16 AWG wire?
- About 4.0151 ohms per 1000 feet for copper and 6.5815 ohms per 1000 feet for aluminium, at 75 °C.
- How far can I run 16 AWG wire?
- Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 16 AWG copper stays under 3% voltage drop for about 18 feet one-way. Doubling the voltage roughly doubles the allowable distance.
Related charts & calculators
- Rigid Conduit Fill ChartRMC and IMC conductor counts per trade size, side by side.
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.