16 AWG Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 16 AWG conductors in copper and aluminium.

Quick answer

16 AWG copper carries about 13 A at 75 °C (11 A at 60 °C, 15 A at 90 °C). The bare conductor is 0.0508 in (1.29 mm) and 2,583 circular mils, with 4.0151 Ω per 1000 ft.

Copper 75 °C

13A

Aluminium 75 °C

10A

Diameter

0.0508in

Circular mils

2,583

Full specification

Size designation16 AWG
AWG gauge number16
Circular mils2,583
kcmil2.58
Bare diameter (in)0.0508
Bare diameter (mm)1.290
Cross-section (mm²)1.31
THHN/THWN-2 OD (in)0.096
Insulated area (sq in)0.0072
Copper resistance (Ω/1000 ft)4.0151
Aluminium resistance (Ω/1000 ft)6.5815
Max standard breaker (Cu, 75 °C)Below branch-circuit ratings
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
315 A14 A12 A11 A
612 A11 A10 A8 A
911 A10 A9 A7 A
158 A7 A6 A5 A
257 A6 A6 A5 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 13 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 16 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A36 ft72 ft72 ft166 ft
15 A24 ft48 ft48 ft110 ft
20 A18 ft36 ft36 ft83 ft
30 A12 ft24 ft24 ft55 ft
40 A9 ft18 ft18 ft41 ft
50 A7 ft14 ft14 ft33 ft

Calculate your exact run

How many 16 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT16294782112185323400400400
IMC18325291122200283400400400
RMC17304984114188268400400400
PVC Sch 4015284580109181259400400400
PVC Sch 801222386894158227356400400

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 16 AWG wire carry?
16 AWG copper is estimated at 11 A at 60 °C, 13 A at 75 °C and 15 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 10 A at 75 °C.
What breaker size goes with 16 AWG copper?
16 AWG is below the smallest standard branch-circuit device rating and is normally used for control, signal or fixture wiring rather than a protected branch circuit.
What is the diameter of 16 AWG wire?
The bare conductor is 0.0508 inches (1.290 mm) in diameter, which is 2,583 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.096 inches.
What is the resistance of 16 AWG wire?
About 4.0151 ohms per 1000 feet for copper and 6.5815 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 16 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 16 AWG copper stays under 3% voltage drop for about 18 feet one-way. Doubling the voltage roughly doubles the allowable distance.