3 AWG Wire — Amp Rating, Ampacity & Diameter

Ampacity, geometry, resistance, conduit fill and maximum run length for 3 AWG conductors in copper and aluminium.

Quick answer

3 AWG copper carries about 93 A at 75 °C (79 A at 60 °C, 105 A at 90 °C). The bare conductor is 0.2294 in (5.83 mm) and 52,635 circular mils, with 0.1970 Ω per 1000 ft. It pairs with a 90 A breaker at 75 °C terminations.

Copper 75 °C

93A

Aluminium 75 °C

73A

Diameter

0.2294in

Circular mils

52,635

Full specification

Size designation3 AWG
AWG gauge number3
Circular mils52,635
kcmil52.63
Bare diameter (in)0.2294
Bare diameter (mm)5.827
Cross-section (mm²)26.67
THHN/THWN-2 OD (in)0.352
Insulated area (sq in)0.0973
Copper resistance (Ω/1000 ft)0.1970
Aluminium resistance (Ω/1000 ft)0.3230
Max standard breaker (Cu, 75 °C)90 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3105 A96 A86 A74 A
684 A77 A69 A59 A
974 A67 A60 A52 A
1553 A48 A43 A37 A
2547 A43 A39 A33 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 93 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 3 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A734 ft1,468 ft1,470 ft3,392 ft
15 A489 ft979 ft980 ft2,261 ft
20 A367 ft734 ft735 ft1,696 ft
30 A244 ft489 ft490 ft1,130 ft
40 A183 ft367 ft367 ft848 ft
50 A146 ft293 ft294 ft678 ft

Calculate your exact run

How many 3 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT113681324364760
IMC113691421324356
RMC113681419304152
PVC Sch 40113581319294051
PVC Sch 80112571116263546

Mix conductor sizes in the fill calculator

3 AWG copper ampacity vs aluminium ampacity

Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.

Material60 °C (TW, NM-B)75 °C (THW, THWN, XHHW)90 °C (THHN, THWN-2, XHHW-2)
Copper79 A93 A105 A
Aluminium62 A73 A82 A

The 3 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 93 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 105 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.

Aluminium of the same size carries roughly 78% of the copper value (73 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.

Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.

Neighbouring sizes

Compare 3 AWG with the sizes immediately above and below it before sizing a circuit.

SizeCu 75 °CAl 75 °CDiameter (in)Circular mils
6 AWG59 A46 A0.162026,251
4 AWG80 A62 A0.204341,741
3 AWG (this page)93 A73 A0.229452,635
2 AWG108 A84 A0.257666,371
1 AWG126 A98 A0.289383,693

Circuits that use 3 AWG

Breaker ratings whose smallest copper conductor at 75 °C terminations is 3 AWG.

3 AWG amp rating, diameter and metric equivalent

The amp rating for 3 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 79 A on a 60 °C conductor, 93 A at 75 °C and 105 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.

Geometrically, 3 AWG is 0.2294 in (5.83 mm) in bare diameter, which is 52,635 circular mils. The cross sectional area works out to 26.67 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.

American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.

Why 3 AWG is specified so rarely

3 AWG exists in the gauge series and is manufactured, but it is a stocking gap in most supply houses. Designers step from 4 AWG to 2 AWG because the standard overcurrent devices bracket the interval and the cost difference between 3 and 2 is small compared with the risk of a non-stock item delaying a pull.

Where 3 AWG does appear, it is usually on engineered drawings that sized the conductor exactly against a calculated load or a voltage-drop budget rather than rounding to the next stocked size, or as a grounding electrode conductor on a service where the electrode conductor requirement fell between sizes.

The practical takeaway: if a calculation returns 3 AWG, verify local availability before committing, and check whether 2 AWG changes anything downstream. Upsizing costs a little material; it never costs ampacity, though it can change the required conduit trade size and the lug range at both ends.

Frequently asked

How many amps can 3 AWG wire carry?
3 AWG copper is estimated at 79 A at 60 °C, 93 A at 75 °C and 105 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 73 A at 75 °C.
What is the amp rating for 3 gauge wire?
Use 93 A for 3 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 79 A instead when the conductor is inside NM-B cable, and treat 105 A as the derating base only. Aluminium of the same size is about 73 A at 75 °C.
What breaker size goes with 3 AWG copper?
The largest standard overcurrent device that 3 AWG copper supports at 75 °C is 90 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 3 AWG wire?
The bare conductor is 0.2294 inches (5.827 mm) in diameter, which is 52,635 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.352 inches.
What is the resistance of 3 AWG wire?
About 0.1970 ohms per 1000 feet for copper and 0.3230 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 3 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 3 AWG copper stays under 3% voltage drop for about 367 feet one-way. Doubling the voltage roughly doubles the allowable distance.