3 AWG Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 3 AWG conductors in copper and aluminium.

Quick answer

3 AWG copper carries about 93 A at 75 °C (79 A at 60 °C, 105 A at 90 °C). The bare conductor is 0.2294 in (5.83 mm) and 52,635 circular mils, with 0.1970 Ω per 1000 ft. It pairs with a 90 A breaker at 75 °C terminations.

Copper 75 °C

93A

Aluminium 75 °C

73A

Diameter

0.2294in

Circular mils

52,635

Full specification

Size designation3 AWG
AWG gauge number3
Circular mils52,635
kcmil52.63
Bare diameter (in)0.2294
Bare diameter (mm)5.827
Cross-section (mm²)26.67
THHN/THWN-2 OD (in)0.352
Insulated area (sq in)0.0973
Copper resistance (Ω/1000 ft)0.1970
Aluminium resistance (Ω/1000 ft)0.3230
Max standard breaker (Cu, 75 °C)90 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3105 A96 A86 A74 A
684 A77 A69 A59 A
974 A67 A60 A52 A
1553 A48 A43 A37 A
2547 A43 A39 A33 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 93 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 3 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A734 ft1,468 ft1,470 ft3,392 ft
15 A489 ft979 ft980 ft2,261 ft
20 A367 ft734 ft735 ft1,696 ft
30 A244 ft489 ft490 ft1,130 ft
40 A183 ft367 ft367 ft848 ft
50 A146 ft293 ft294 ft678 ft

Calculate your exact run

How many 3 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT113681324364760
IMC113691421324356
RMC113681419304152
PVC Sch 40113581319294051
PVC Sch 80112571116263546

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 3 AWG wire carry?
3 AWG copper is estimated at 79 A at 60 °C, 93 A at 75 °C and 105 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 73 A at 75 °C.
What breaker size goes with 3 AWG copper?
The largest standard overcurrent device that 3 AWG copper supports at 75 °C is 90 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 3 AWG wire?
The bare conductor is 0.2294 inches (5.827 mm) in diameter, which is 52,635 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.352 inches.
What is the resistance of 3 AWG wire?
About 0.1970 ohms per 1000 feet for copper and 0.3230 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 3 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 3 AWG copper stays under 3% voltage drop for about 367 feet one-way. Doubling the voltage roughly doubles the allowable distance.