Conduit Fill Calculator

Fill percentage against the 53 / 31 / 40 rule, the maximum conductor count for the raceway you picked, and the smallest trade size that legally holds your pull.

Quick answer

Allowable conduit fill is 53% for one conductor, 31% for two, and 40% for three or more. Fill percent is total conductor area divided by the raceway's internal area, where both areas come from A = π × (diameter / 2)². Pick the raceway family below and the calculator applies that pipe's published internal diameter.

Pre-computed charts by conduit type

Want a table instead of one answer? Each raceway family has its own chart.

Raceway and conductors

A = π × (d / 2)²  ·  fill% = (n × Awire) / Aconduit

12 AWG THHN nominal OD 0.130" = 0.0133 sq in each.

Result

Fill

17.5%

Allowed (3+ wires)

40%

Conduit area

0.3039sq in

Max conductors this size

9

4 conductors are within the 40% limit for 1/2" EMT.

Smallest EMT that holds 4 × 12 AWG THHN: 1/2"

Conductor area used: 0.0531 sq in of 0.1216 sq in permitted.

Published standard — source: UL 797 / ANSI C80.3 nominal dimensions

Where the numbers come from

The calculator solves one pull at a time. Pre-computed counts for every wire size against every trade size live on the chart pages, so they are not repeated here.

Each conductor's area is π × (OD / 2)² using the manufacturer's nominal insulated outside diameter. The raceway's usable area is its internal area multiplied by the fill percentage that matches the conductor count — 53% at one, 31% at two, 40% at three or more. The maximum count is the largest n where n × Awire stays inside that usable area, which is why the limit shifts when the count crosses from two to three.

Looking for a printable table rather than a single answer? The conduit fill chart lists maximum conductors per trade size for EMT, IMC, RMC and PVC, and each wire size there links to its own per-size conduit fill page.

Internal area by trade size

Trade sizeInternal dia. (in)Total area (sq in)53% (1 wire)31% (2 wires)40% (3+ wires)
1"1.0490.86430.45810.26790.3457
2"2.0673.35561.77851.04021.3422
3"3.3568.84574.68822.74223.5383
4"4.33414.75267.81894.57335.9010
1/2"0.6220.30390.16110.09420.1216
3/4"0.8240.53330.28260.16530.2133
1-1/4"1.3801.49570.79270.46370.5983
1-1/2"1.6102.03581.07900.63110.8143
2-1/2"2.7315.85783.10461.81592.3431
3-1/2"3.83411.54506.11893.57894.6180

Frequently asked

What is the maximum conduit fill percentage?
One conductor may fill 53% of the raceway's internal area, two conductors 31%, and three or more conductors 40%. Short nipples of 24 inches or less are permitted 60% fill.
How is conduit fill calculated?
Compute the internal area of the conduit as A = pi x (id/2)^2, compute the area of each conductor from its insulated outside diameter the same way, multiply by the conductor count, then divide the total conductor area by the conduit area.
Can I calculate fill for mixed conductor sizes?
Yes — sum the area of each group separately. Run the calculator once per size, add the conductor areas together, and compare the total against the raceway's 40% usable area. Fixed chart counts only cover same-size pulls, which is the main reason to use a calculator instead of a table.
Do I count the ground wire in conduit fill?
Yes. All conductors occupy space, so the equipment grounding conductor counts toward the fill area even though it is not counted as a current-carrying conductor for ampacity derating.