2 AWG Wire Specs

Ampacity, geometry, resistance, conduit fill and maximum run length for 2 AWG conductors in copper and aluminium.

Quick answer

2 AWG copper carries about 108 A at 75 °C (92 A at 60 °C, 122 A at 90 °C). The bare conductor is 0.2576 in (6.54 mm) and 66,371 circular mils, with 0.1563 Ω per 1000 ft. It pairs with a 100 A breaker at 75 °C terminations.

Copper 75 °C

108A

Aluminium 75 °C

84A

Diameter

0.2576in

Circular mils

66,371

Full specification

Size designation2 AWG
AWG gauge number2
Circular mils66,371
kcmil66.37
Bare diameter (in)0.2576
Bare diameter (mm)6.543
Cross-section (mm²)33.62
THHN/THWN-2 OD (in)0.384
Insulated area (sq in)0.1158
Copper resistance (Ω/1000 ft)0.1563
Aluminium resistance (Ω/1000 ft)0.2561
Max standard breaker (Cu, 75 °C)100 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3122 A111 A100 A86 A
698 A89 A80 A69 A
985 A78 A70 A60 A
1561 A56 A50 A43 A
2555 A50 A45 A39 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 108 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 2 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A926 ft1,852 ft1,853 ft4,277 ft
15 A617 ft1,234 ft1,235 ft2,851 ft
20 A463 ft926 ft926 ft2,138 ft
30 A308 ft617 ft617 ft1,425 ft
40 A231 ft463 ft463 ft1,069 ft
50 A185 ft370 ft370 ft855 ft

Calculate your exact run

How many 2 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT112571120303950
IMC113571217273647
RMC113571116253444
PVC Sch 40112561116253343
PVC Sch 801145914223038

Mix conductor sizes in the fill calculator

Neighbouring sizes

Frequently asked

How many amps can 2 AWG wire carry?
2 AWG copper is estimated at 92 A at 60 °C, 108 A at 75 °C and 122 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 84 A at 75 °C.
What breaker size goes with 2 AWG copper?
The largest standard overcurrent device that 2 AWG copper supports at 75 °C is 100 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 2 AWG wire?
The bare conductor is 0.2576 inches (6.543 mm) in diameter, which is 66,371 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.384 inches.
What is the resistance of 2 AWG wire?
About 0.1563 ohms per 1000 feet for copper and 0.2561 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 2 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 2 AWG copper stays under 3% voltage drop for about 463 feet one-way. Doubling the voltage roughly doubles the allowable distance.