3/0 AWG Wire — Amp Rating, Ampacity & Diameter

Ampacity, geometry, resistance, conduit fill and maximum run length for 3/0 AWG conductors in copper and aluminium.

Quick answer

3/0 AWG copper carries about 198 A at 75 °C (168 A at 60 °C, 223 A at 90 °C). The bare conductor is 0.4096 in (10.40 mm) and 167,806 circular mils, with 0.0618 Ω per 1000 ft. It pairs with a 175 A breaker at 75 °C terminations.

Copper 75 °C

198A

Aluminium 75 °C

154A

Diameter

0.4096in

Circular mils

167,806

Full specification

Size designation3/0 AWG
AWG gauge number3/0
Circular mils167,806
kcmil167.81
Bare diameter (in)0.4096
Bare diameter (mm)10.404
Cross-section (mm²)85.01
THHN/THWN-2 OD (in)0.581
Insulated area (sq in)0.2651
Copper resistance (Ω/1000 ft)0.0618
Aluminium resistance (Ω/1000 ft)0.1013
Max standard breaker (Cu, 75 °C)175 A
Published standard — source: Geometry computed from the ASTM B258 AWG formula; resistance from standard resistivityFormula estimate — source: Ampacity from the site model

Ampacity with derating

Estimated ampacity from the 90 °C column at various ambient temperatures and conductor counts.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3223 A204 A182 A158 A
6178 A163 A146 A126 A
9156 A143 A127 A110 A
15112 A102 A91 A79 A
25100 A92 A82 A71 A

Source & method: The governing value is also capped by the termination rating, commonly 75 °C, which for this size is 198 A. Run your own conditions.

Maximum run length at 3% voltage drop

One-way distance for 3/0 AWG copper before drop exceeds 3%.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
10 A2,341 ft4,682 ft4,686 ft10,815 ft
15 A1,560 ft3,121 ft3,124 ft7,210 ft
20 A1,170 ft2,341 ft2,343 ft5,407 ft
30 A780 ft1,560 ft1,562 ft3,605 ft
40 A585 ft1,170 ft1,171 ft2,703 ft
50 A468 ft936 ft937 ft2,163 ft

Calculate your exact run

How many 3/0 AWG conductors fit in conduit

Maximum count of this size alone, at the fill percentage matching the resulting count.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT—111358131722
IMC—111357111520
RMC—111357111519
PVC Sch 40—111247101418
PVC Sch 80——1124691316

Mix conductor sizes in the fill calculator

3/0 AWG copper ampacity vs aluminium ampacity

Ampacity by conductor material and insulation temperature rating, at 30 °C ambient with no more than three current-carrying conductors.

Material60 °C (TW, NM-B)75 °C (THW, THWN, XHHW)90 °C (THHN, THWN-2, XHHW-2)
Copper168 A198 A223 A
Aluminium131 A154 A174 A

The 3/0 AWG copper ampacity figure you use on a real circuit is the 75 °C column, 198 A, because breakers and lugs on most equipment are listed for 75 °C even when the conductor insulation is rated 90 °C. The 90 °C value, 223 A, is the starting point for ambient and conductor-count derating only — you derate from 90 °C, then cap the answer at the termination rating.

Aluminium of the same size carries roughly 78% of the copper value (154 A at 75 °C), so an aluminium feeder is normally stepped up one to two sizes to match a copper circuit. NM-B cable is always read from the 60 °C column regardless of the temperature stamped on the conductor insulation.

Source & method: Values are model estimates from conductor geometry and resistivity — see methodology and verify against the NEC edition enforced locally.

Neighbouring sizes

Compare 3/0 AWG with the sizes immediately above and below it before sizing a circuit.

SizeCu 75 °CAl 75 °CDiameter (in)Circular mils
1/0 AWG146 A114 A0.3249105,535
2/0 AWG170 A133 A0.3648133,077
3/0 AWG (this page)198 A154 A0.4096167,806
4/0 AWG230 A180 A0.4600211,600
250 kcmil257 A200 A0.5000250,000

Circuits that use 3/0 AWG

Breaker ratings whose smallest copper conductor at 75 °C terminations is 3/0 AWG.

3/0 AWG amp rating, diameter and metric equivalent

The amp rating for 3/0 AWG wire depends on the insulation temperature rating, not on the conductor alone. Copper ampacity is about 168 A on a 60 °C conductor, 198 A at 75 °C and 223 A at 90 °C, all at 30 °C ambient with no more than three current-carrying conductors in the raceway. The carrying capacity drops from there in hot spaces or crowded conduit, and terminations rated 75 °C cap what you can actually use.

Geometrically, 3/0 AWG is 0.4096 in (10.40 mm) in bare diameter, which is 167,806 circular mils. The cross sectional area works out to 85.03 mm², so the nearest IEC 60228 metric conductor is the next standard size at or above that figure — AWG sizes and mm² sizes never line up exactly, so round up rather than to the closest value.

American Wire Gauge (AWG) is a standard specification for the sizes of solid round wires used as electrical conductors, and the AWG number counts the drawing operations used to reach the diameter. That is why larger gauges are thinner wire and why standardized wire steps follow a fixed ratio: one AWG step changes diameter by about 12.2% and area by about 26%. Above 1 AWG the American standard continues 1/0 to 4/0, then switches to kcmil for anything larger.

Where 3/0 actually gets used

3/0 is a commercial and industrial feeder size: copper 3/0 supports roughly 200 A feeders, and aluminium 3/0 lands around 175 A. It appears in panelboard feeds, transformer secondary conductors and large equipment feeders far more often than in dwellings.

The reason 3/0 is less common than 4/0 in residential work is the service allowance: a dwelling service or main power feeder may be sized against a reduced percentage of the rating, which puts 4/0 aluminium at 200 A and leaves 3/0 without an obvious residential home. Non-dwelling feeders get no such allowance, which is exactly where 3/0 earns its place.

Parallel conductor sets start to be considered near this size. Two smaller conductors per phase can be easier to pull, easier to terminate and cheaper in raceway than one very large conductor, but parallel sets must be the same length, material, size and insulation, and each set needs its own termination provision.

Frequently asked

How many amps can 3/0 AWG wire carry?
3/0 AWG copper is estimated at 168 A at 60 °C, 198 A at 75 °C and 223 A at 90 °C, at 30 °C ambient with no more than three current-carrying conductors. Aluminium of the same size is about 154 A at 75 °C.
What is the amp rating for 3/0 gauge wire?
Use 198 A for 3/0 AWG copper on equipment with 75 °C terminations, which covers most breakers and panel lugs. Read 168 A instead when the conductor is inside NM-B cable, and treat 223 A as the derating base only. Aluminium of the same size is about 154 A at 75 °C.
What breaker size goes with 3/0 AWG copper?
The largest standard overcurrent device that 3/0 AWG copper supports at 75 °C is 175 A. For a continuous load, the load itself must not exceed 80% of that rating.
What is the diameter of 3/0 AWG wire?
The bare conductor is 0.4096 inches (10.404 mm) in diameter, which is 167,806 circular mils. With THHN/THWN-2 insulation the nominal outside diameter is about 0.581 inches.
What is the resistance of 3/0 AWG wire?
About 0.0618 ohms per 1000 feet for copper and 0.1013 ohms per 1000 feet for aluminium, at 75 °C.
How far can I run 3/0 AWG wire?
Distance depends on load and voltage. At 20 A on a 120 V single-phase circuit, 3/0 AWG copper stays under 3% voltage drop for about 1170 feet one-way. Doubling the voltage roughly doubles the allowable distance.