What Size Wire for a 45 Amp Breaker?

Conductor size, aluminium equivalent, derating and maximum run length for a 45 amp circuit — all derived from published conductor geometry and the voltage-drop formula.

Quick answer

A 45 amp circuit needs 6 AWG copper with 75 °C terminations, or 6 AWG aluminium. 6 AWG copper applies where equipment terminals are limited to 60 °C. Voltage drop reaches 3% at roughly 162 ft one-way on 240 V and 81 ft on 120 V.
Formula estimate — source: Power-law ampacity model fitted to conductor heat dissipation; ASTM B258 geometry

Copper @ 75 °C

6 AWG

Copper @ 60 °C

6 AWG

Aluminium @ 75 °C

6 AWG

3% drop @ 240 V

162ft

Conductor options for 45 A

Estimated ampacity of each candidate size, so you can see the margin you are buying.

Material / ratingMinimum sizeEstimated ampacityMargin over 45 A
Copper, 60 °C6 AWG50 A+5 A
Copper, 75 °C6 AWG59 A+14 A
Copper, 90 °C8 AWG49 A+4 A
Aluminium, 75 °C6 AWG46 A+1 A
Aluminium, 90 °C6 AWG52 A+7 A
Ampacity estimated as I = 0.0670 × cmil^0.6505, scaled for insulation rating and material.

Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.

Maximum run length on 6 AWG copper

One-way distance before voltage drop passes the 3% and 5% guidelines.

System3% limit5% limitDrop @ 100 ft
120 V 1Ø81 ft135 ft3.69%
240 V 1Ø162 ft271 ft1.84%
208 V 3Ø162 ft271 ft1.84%
480 V 3Ø375 ft626 ft0.8%

Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 6 AWG is 26,251 circular mils and 0.3951 Ω per 1000 ft at 20 °C.

Wire size by run length for 45 A

Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.

One-way run120 V 1Ø240 V 1Ø480 V 3Ø
50 ft6 AWG6 AWG6 AWG
75 ft6 AWG6 AWG6 AWG
100 ft4 AWG6 AWG6 AWG
150 ft3 AWG6 AWG6 AWG
200 ft2 AWG4 AWG6 AWG
250 ft1 AWG4 AWG6 AWG
300 ft1/0 AWG3 AWG6 AWG
Sized on both criteria at once: estimated 75 C ampacity and 3% voltage drop at the stated one-way distance.

Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.

Hot attics, conduit runs and bundling

What a 45 A circuit actually needs once ambient temperature and conductor count are applied.

Ambient3 conductors4–6 conductors7–9 conductors
30 °C6 AWG6 AWG4 AWG
40 °C6 AWG4 AWG4 AWG
50 °C4 AWG4 AWG3 AWG
60 °C4 AWG2 AWG1 AWG

Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 45 A.

Where 45 A circuits are actually used

45 A shows up on electric heat, larger air handlers with multiple heat-strip stages, and equipment nameplates that specify a 45 A maximum device. As a standard overcurrent device size it exists, but as a designed branch circuit it is rare outside HVAC.

Multi-stage electric heat is the case to watch. Strip heat is a continuous load and is staged, so the design current is 125% of the total energised at once, not of the whole bank. Getting that wrong in either direction either trips on the coldest night of the year or leaves a conductor protected above its rating.

Aluminium is uncommon at 45 A: the equipment terminals on air handlers and heat kits are frequently listed for copper only, and the conductor lands in a compact junction box with little bending room. Check the equipment label for conductor material and terminal temperature before pricing the feeder.

Continuous loads

A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 45 A continuous becomes 56.3 A of design current, which lands on a 60 A overcurrent device and 6 AWG copper.

Frequently asked

What size wire do I need for a 45 amp breaker?
6 AWG copper is the smallest conductor our model estimates at or above 45 A using a 75 °C insulation rating; 6 AWG is required if the terminations are limited to 60 °C. In aluminium the equivalent is 6 AWG. Verify against the code edition adopted locally before installing.
Can I use aluminium wire on a 45 amp circuit?
Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 45 A circuit steps up to 6 AWG and uses K = 21.2 in the voltage-drop formula instead of 12.9.
How far can a 45 amp circuit run?
On 6 AWG copper the 3% voltage-drop guideline is reached near 81 ft one-way at 120 V and 162 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
Is a 45 amp breaker sized at 100% of the load?
Only for non-continuous loads. A continuous load is designed at 125%, so 45 A of continuous current becomes 56.3 A of design current and lands on a 60 A device with conductors sized to match.
What is typically on a 45 amp circuit?
Commonly cooktops, mid-size heat pumps. The load type also drives the receptacle and disconnect ratings, not just the conductor size.

Other breaker sizes

More on 6 AWG

Related charts & calculators