6 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 6 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 183 ft one-way. Full table by load, voltage and distance.

Quick answer

6 AWG copper reaches 3% voltage drop at about 183 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 1.97 V (1.64%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 26,251 circular mils.

3% limit @ 20 A, 120 V

183ft

3% limit @ 20 A, 240 V

366ft

Drop @ 100 ft, 20 A

1.97V

Ω / 1000 ft (Cu)

0.3951

Maximum one-way run length at 3% drop

Copper 6 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A732 ft1,465 ft1,466 ft3,383 ft
10 A366 ft732 ft733 ft1,691 ft
15 A244 ft488 ft488 ft1,127 ft
20 A183 ft366 ft366 ft845 ft
25 A146 ft293 ft293 ft676 ft
30 A122 ft244 ft244 ft563 ft
40 A91 ft183 ft183 ft422 ft
50 A73 ft146 ft146 ft338 ft
60 A61 ft122 ft122 ft281 ft
80 A45 ft91 ft91 ft211 ft
100 A36 ft73 ft73 ft169 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.2%0.31%0.41%0.61%
50 ft0.41%0.61%0.82%1.23%
75 ft0.61%0.92%1.23%1.84%
100 ft0.82%1.23%1.64%2.46%
150 ft1.23%1.84%2.46%3.69%
200 ft1.64%2.46%3.28%4.91%
300 ft2.46%3.69%4.91%7.37%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 6 AWG wire?
At 20 A on a 120 V single-phase circuit, 6 AWG copper stays under 3% voltage drop for about 183 ft one-way. At 240 V the same load reaches roughly 366 ft, because allowable drop scales with system voltage.
What is the voltage drop of 6 AWG wire per 100 feet?
About 1.97 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 6 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.