6 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 6 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 183 ft one-way. Full table by load, voltage and distance.
Quick answer
6 AWG copper reaches 3% voltage drop at about 183 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 1.97 V (1.64%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 26,251 circular mils.
3% limit @ 20 A, 120 V
183ft
3% limit @ 20 A, 240 V
366ft
Drop @ 100 ft, 20 A
1.97V
Ω / 1000 ft (Cu)
0.3951
Maximum one-way run length at 3% drop
Copper 6 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 732 ft | 1,465 ft | 1,466 ft | 3,383 ft |
| 10 A | 366 ft | 732 ft | 733 ft | 1,691 ft |
| 15 A | 244 ft | 488 ft | 488 ft | 1,127 ft |
| 20 A | 183 ft | 366 ft | 366 ft | 845 ft |
| 25 A | 146 ft | 293 ft | 293 ft | 676 ft |
| 30 A | 122 ft | 244 ft | 244 ft | 563 ft |
| 40 A | 91 ft | 183 ft | 183 ft | 422 ft |
| 50 A | 73 ft | 146 ft | 146 ft | 338 ft |
| 60 A | 61 ft | 122 ft | 122 ft | 281 ft |
| 80 A | 45 ft | 91 ft | 91 ft | 211 ft |
| 100 A | 36 ft | 73 ft | 73 ft | 169 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.2% | 0.31% | 0.41% | 0.61% |
| 50 ft | 0.41% | 0.61% | 0.82% | 1.23% |
| 75 ft | 0.61% | 0.92% | 1.23% | 1.84% |
| 100 ft | 0.82% | 1.23% | 1.64% | 2.46% |
| 150 ft | 1.23% | 1.84% | 2.46% | 3.69% |
| 200 ft | 1.64% | 2.46% | 3.28% | 4.91% |
| 300 ft | 2.46% | 3.69% | 4.91% | 7.37% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 6 AWG wire?
- At 20 A on a 120 V single-phase circuit, 6 AWG copper stays under 3% voltage drop for about 183 ft one-way. At 240 V the same load reaches roughly 366 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 6 AWG wire per 100 feet?
- About 1.97 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 6 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 6 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.