What Size Wire for a 250 Amp Breaker?
Conductor size, aluminium equivalent, derating and maximum run length for a 250 amp circuit — all derived from published conductor geometry and the voltage-drop formula.
Quick answer
Copper @ 75 °C
250 kcmil
Copper @ 60 °C
350 kcmil
Aluminium @ 75 °C
400 kcmil
3% drop @ 240 V
279ft
Conductor options for 250 A
Estimated ampacity of each candidate size, so you can see the margin you are buying.
| Material / rating | Minimum size | Estimated ampacity | Margin over 250 A |
|---|---|---|---|
| Copper, 60 °C | 350 kcmil | 271 A | +21 A |
| Copper, 75 °C | 250 kcmil | 257 A | +7 A |
| Copper, 90 °C | 4/0 AWG | 260 A | +10 A |
| Aluminium, 75 °C | 400 kcmil | 272 A | +22 A |
| Aluminium, 90 °C | 300 kcmil | 254 A | +4 A |
Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.
Maximum run length on 250 kcmil copper
One-way distance before voltage drop passes the 3% and 5% guidelines.
| System | 3% limit | 5% limit | Drop @ 100 ft |
|---|---|---|---|
| 120 V 1Ø | 139 ft | 232 ft | 2.15% |
| 240 V 1Ø | 279 ft | 465 ft | 1.08% |
| 208 V 3Ø | 279 ft | 465 ft | 1.07% |
| 480 V 3Ø | 644 ft | 1,074 ft | 0.47% |
Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 250 kcmil is 250,000 circular mils and 0.0415 Ω per 1000 ft at 20 °C.
Wire size by run length for 250 A
Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.
| One-way run | 120 V 1Ø | 240 V 1Ø | 480 V 3Ø |
|---|---|---|---|
| 50 ft | 250 kcmil | 250 kcmil | 250 kcmil |
| 75 ft | 250 kcmil | 250 kcmil | 250 kcmil |
| 100 ft | 250 kcmil | 250 kcmil | 250 kcmil |
| 150 ft | 300 kcmil | 250 kcmil | 250 kcmil |
| 200 ft | 400 kcmil | 250 kcmil | 250 kcmil |
| 250 ft | 500 kcmil | 250 kcmil | 250 kcmil |
| 300 ft | 600 kcmil | 300 kcmil | 250 kcmil |
Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.
Hot attics, conduit runs and bundling
What a 250 A circuit actually needs once ambient temperature and conductor count are applied.
| Ambient | 3 conductors | 4–6 conductors | 7–9 conductors |
|---|---|---|---|
| 30 °C | 250 kcmil | 350 kcmil | 500 kcmil |
| 40 °C | 300 kcmil | 500 kcmil | 600 kcmil |
| 50 °C | 400 kcmil | 600 kcmil | 750 kcmil |
| 60 °C | 600 kcmil | — | — |
Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 250 A.
Where 250 A circuits are actually used
250 A serves commercial services, large multi-family feeders, machine and process equipment feeds, and elevator or fire-pump distribution. On the residential side it is the size of an all-electric home with heat pumps, an EV and a large PV interconnection.
At 250 A the conductor is normally kcmil rather than AWG, and the design questions shift to raceway family, pull length and available fault current. The overcurrent device must also have an interrupting rating at or above the available fault current at its point of installation — a requirement that applies to overcurrent devices generally, but one that is far more likely to be the binding constraint on service and feeder equipment of this size than on a small branch circuit.
Continuous loads
A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 250 A continuous becomes 312.5 A of design current, which lands on a 350 A overcurrent device and 350 kcmil copper.
Frequently asked
- What size wire do I need for a 250 amp breaker?
- 250 kcmil copper is the smallest conductor our model estimates at or above 250 A using a 75 °C insulation rating; 350 kcmil is required if the terminations are limited to 60 °C. In aluminium the equivalent is 400 kcmil. Verify against the code edition adopted locally before installing.
- Can I use aluminium wire on a 250 amp circuit?
- Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 250 A circuit steps up to 400 kcmil and uses K = 21.2 in the voltage-drop formula instead of 12.9.
- How far can a 250 amp circuit run?
- On 250 kcmil copper the 3% voltage-drop guideline is reached near 139 ft one-way at 120 V and 279 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
- Is a 250 amp breaker sized at 100% of the load?
- Only for non-continuous loads. A continuous load is designed at 125%, so 250 A of continuous current becomes 312.5 A of design current and lands on a 350 A device with conductors sized to match.
- What is typically on a 250 amp circuit?
- Commonly commercial feeders. The load type also drives the receptacle and disconnect ratings, not just the conductor size.
Other breaker sizes
More on 250 kcmil
Related charts & calculators
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.
- Allen Wrench Size ChartHex key sizes with SAE and metric cross-reference.
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.