What Size Wire for a 250 Amp Breaker?

Conductor size, aluminium equivalent, derating and maximum run length for a 250 amp circuit — all derived from published conductor geometry and the voltage-drop formula.

Quick answer

A 250 amp circuit needs 250 kcmil copper with 75 °C terminations, or 400 kcmil aluminium. 350 kcmil copper applies where equipment terminals are limited to 60 °C. Voltage drop reaches 3% at roughly 279 ft one-way on 240 V and 139 ft on 120 V.
Formula estimate — source: Power-law ampacity model fitted to conductor heat dissipation; ASTM B258 geometry

Copper @ 75 °C

250 kcmil

Copper @ 60 °C

350 kcmil

Aluminium @ 75 °C

400 kcmil

3% drop @ 240 V

279ft

Conductor options for 250 A

Estimated ampacity of each candidate size, so you can see the margin you are buying.

Material / ratingMinimum sizeEstimated ampacityMargin over 250 A
Copper, 60 °C350 kcmil271 A+21 A
Copper, 75 °C250 kcmil257 A+7 A
Copper, 90 °C4/0 AWG260 A+10 A
Aluminium, 75 °C400 kcmil272 A+22 A
Aluminium, 90 °C300 kcmil254 A+4 A
Ampacity estimated as I = 0.0670 × cmil^0.6505, scaled for insulation rating and material.

Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.

Maximum run length on 250 kcmil copper

One-way distance before voltage drop passes the 3% and 5% guidelines.

System3% limit5% limitDrop @ 100 ft
120 V 1Ø139 ft232 ft2.15%
240 V 1Ø279 ft465 ft1.08%
208 V 3Ø279 ft465 ft1.07%
480 V 3Ø644 ft1,074 ft0.47%

Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 250 kcmil is 250,000 circular mils and 0.0415 Ω per 1000 ft at 20 °C.

Hot attics, conduit runs and bundling

What a 250 A circuit actually needs once ambient temperature and conductor count are applied.

Ambient3 conductors4–6 conductors7–9 conductors
30 °C250 kcmil350 kcmil500 kcmil
40 °C300 kcmil500 kcmil600 kcmil
50 °C400 kcmil600 kcmil750 kcmil
60 °C600 kcmil

Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 250 A.

Continuous loads

A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 250 A continuous becomes 312.5 A of design current, which lands on a 350 A overcurrent device and 350 kcmil copper.

Frequently asked

What size wire do I need for a 250 amp breaker?
250 kcmil copper is the smallest conductor our model estimates at or above 250 A using a 75 °C insulation rating; 350 kcmil is required if the terminations are limited to 60 °C. In aluminium the equivalent is 400 kcmil. Verify against the code edition adopted locally before installing.
Can I use aluminium wire on a 250 amp circuit?
Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 250 A circuit steps up to 400 kcmil and uses K = 21.2 in the voltage-drop formula instead of 12.9.
How far can a 250 amp circuit run?
On 250 kcmil copper the 3% voltage-drop guideline is reached near 139 ft one-way at 120 V and 279 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
Is a 250 amp breaker sized at 100% of the load?
Only for non-continuous loads. A continuous load is designed at 125%, so 250 A of continuous current becomes 312.5 A of design current and lands on a 350 A device with conductors sized to match.
What is typically on a 250 amp circuit?
Commonly commercial feeders. The load type also drives the receptacle and disconnect ratings, not just the conductor size.

Wire and breakers for a 250 A circuit

Other breaker sizes

More on 250 kcmil

Related charts & calculators