6 AWG Conduit Fill — Wires per Conduit Size

How many 6 AWG THHN conductors fit in EMT, IMC, RMC and PVC conduit, from 1/2 inch through 4 inch, with the 40% fill rule applied.

Quick answer

1 6 AWG THHN conductors fit in 1/2 inch EMT and 4 fit in 3/4 inch EMT, at 40% fill for three or more conductors. Each conductor consumes 0.0507 sq in from a nominal insulated outside diameter of 0.254 in. Neutrals and grounds count.

6 AWG conductors per conduit trade size

Same-size conductors only, at 53% for one, 31% for two and 40% for three or more.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT146111626466991116
IMC247121728406283107
RMC147121626385979101
PVC Sch 4014611152537577699
PVC Sch 801359132232506888
Published standard — source: Raceway internal areas from product standards (EMT, IMC, RMC, PVC Sch 40, PVC Sch 80); conductor OD from nominal THHN dimensions

Source & method: Counts are the largest whole number where n × conductor area stays inside the raceway area times the applicable fill percentage. Mix conductor sizes in the calculator.

What each raceway type means

  • EMT EMT (electrical metallic tubing)
  • IMC IMC (intermediate metal conduit)
  • RMC RMC (rigid metal conduit)
  • PVC Sch 40 PVC Schedule 40
  • PVC Sch 80 PVC Schedule 80

Frequently asked

How many 6 AWG wires fit in 1/2 inch EMT?
1 6 AWG THHN conductors fit in 1/2 inch EMT at the applicable fill percentage.
How many 6 AWG wires fit in 3/4 inch EMT?
4 conductors, using a nominal THHN outside diameter of 0.254 in and the 40% fill rule for three or more conductors.
Do neutrals and grounds count toward fill?
Yes, every conductor in the raceway counts for fill. Grounds are excluded only from the count of current-carrying conductors used for ampacity adjustment.
What is the cross-sectional area of 6 AWG THHN?
About 0.0507 square inches, from A = π × (OD / 2)² with a nominal insulated OD of 0.254 in.