What Size Wire for a 30 Amp Breaker?

Conductor size, aluminium equivalent, derating and maximum run length for a 30 amp circuit — all derived from published conductor geometry and the voltage-drop formula.

Quick answer

A 30 amp circuit needs 10 AWG copper with 75 °C terminations, or 8 AWG aluminium. 8 AWG copper applies where equipment terminals are limited to 60 °C. Voltage drop reaches 3% at roughly 96 ft one-way on 240 V and 48 ft on 120 V.
Formula estimate — source: Power-law ampacity model fitted to conductor heat dissipation; ASTM B258 geometry

Copper @ 75 °C

10 AWG

Copper @ 60 °C

8 AWG

Aluminium @ 75 °C

8 AWG

3% drop @ 240 V

96ft

Conductor options for 30 A

Estimated ampacity of each candidate size, so you can see the margin you are buying.

Material / ratingMinimum sizeEstimated ampacityMargin over 30 A
Copper, 60 °C8 AWG37 A+7 A
Copper, 75 °C10 AWG32 A+2 A
Copper, 90 °C10 AWG37 A+7 A
Aluminium, 75 °C8 AWG34 A+4 A
Aluminium, 90 °C8 AWG39 A+9 A
Ampacity estimated as I = 0.0670 × cmil^0.6505, scaled for insulation rating and material.

Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.

Maximum run length on 10 AWG copper

One-way distance before voltage drop passes the 3% and 5% guidelines.

System3% limit5% limitDrop @ 100 ft
120 V 1Ø48 ft80 ft6.21%
240 V 1Ø96 ft160 ft3.11%
208 V 3Ø96 ft161 ft3.1%
480 V 3Ø223 ft371 ft1.34%

Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 10 AWG is 10,383 circular mils and 0.9988 Ω per 1000 ft at 20 °C.

Wire size by run length for 30 A

Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.

One-way run120 V 1Ø240 V 1Ø480 V 3Ø
50 ft8 AWG10 AWG10 AWG
75 ft8 AWG10 AWG10 AWG
100 ft6 AWG8 AWG10 AWG
150 ft4 AWG8 AWG10 AWG
200 ft3 AWG6 AWG10 AWG
250 ft2 AWG4 AWG8 AWG
300 ft2 AWG4 AWG8 AWG
Sized on both criteria at once: estimated 75 C ampacity and 3% voltage drop at the stated one-way distance.

Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.

Hot attics, conduit runs and bundling

What a 30 A circuit actually needs once ambient temperature and conductor count are applied.

Ambient3 conductors4–6 conductors7–9 conductors
30 °C10 AWG8 AWG8 AWG
40 °C8 AWG8 AWG6 AWG
50 °C8 AWG6 AWG6 AWG
60 °C6 AWG4 AWG4 AWG

Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 30 A.

Where 30 A circuits are actually used

30 A covers electric water heaters, clothes dryers, well pumps, baseboard heat runs, small subpanels and 30 A RV service. It is the smallest rating that regularly gets its own disconnect and its own dedicated cable, which is why 10 AWG is stocked on every truck.

The consideration that most often decides a 30 A circuit is the small-conductor cap: 10 AWG copper is held to a 30 A device, so 30 A is the ceiling of that conductor rather than a comfortable point in its range. Water heaters and dryers are also sized against nameplate rather than measured draw, and a 30 A dryer circuit with a long basement-to-laundry run is a common place where voltage drop, not ampacity, forces 8 AWG.

Continuous loads

A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 30 A continuous becomes 37.5 A of design current, which lands on a 40 A overcurrent device and 8 AWG copper.

Frequently asked

What size wire do I need for a 30 amp breaker?
10 AWG copper is the smallest conductor our model estimates at or above 30 A using a 75 °C insulation rating; 8 AWG is required if the terminations are limited to 60 °C. In aluminium the equivalent is 8 AWG. Verify against the code edition adopted locally before installing.
Can I use aluminium wire on a 30 amp circuit?
Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 30 A circuit steps up to 8 AWG and uses K = 21.2 in the voltage-drop formula instead of 12.9.
How far can a 30 amp circuit run?
On 10 AWG copper the 3% voltage-drop guideline is reached near 48 ft one-way at 120 V and 96 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
Is a 30 amp breaker sized at 100% of the load?
Only for non-continuous loads. A continuous load is designed at 125%, so 30 A of continuous current becomes 37.5 A of design current and lands on a 40 A device with conductors sized to match.
What is typically on a 30 amp circuit?
Commonly electric dryers, water heaters, 240 V baseboard heat. The load type also drives the receptacle and disconnect ratings, not just the conductor size.