What Size Wire for a 300 Amp Breaker?
Conductor size, aluminium equivalent, derating and maximum run length for a 300 amp circuit — all derived from published conductor geometry and the voltage-drop formula.
Quick answer
Copper @ 75 °C
350 kcmil
Copper @ 60 °C
500 kcmil
Aluminium @ 75 °C
500 kcmil
3% drop @ 240 V
325ft
Conductor options for 300 A
Estimated ampacity of each candidate size, so you can see the margin you are buying.
| Material / rating | Minimum size | Estimated ampacity | Margin over 300 A |
|---|---|---|---|
| Copper, 60 °C | 500 kcmil | 341 A | +41 A |
| Copper, 75 °C | 350 kcmil | 319 A | +19 A |
| Copper, 90 °C | 300 kcmil | 326 A | +26 A |
| Aluminium, 75 °C | 500 kcmil | 314 A | +14 A |
| Aluminium, 90 °C | 400 kcmil | 306 A | +6 A |
Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.
Maximum run length on 350 kcmil copper
One-way distance before voltage drop passes the 3% and 5% guidelines.
| System | 3% limit | 5% limit | Drop @ 100 ft |
|---|---|---|---|
| 120 V 1Ø | 162 ft | 271 ft | 1.84% |
| 240 V 1Ø | 325 ft | 542 ft | 0.92% |
| 208 V 3Ø | 325 ft | 543 ft | 0.92% |
| 480 V 3Ø | 751 ft | 1,253 ft | 0.4% |
Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 350 kcmil is 350,000 circular mils and 0.0296 Ω per 1000 ft at 20 °C.
Wire size by run length for 300 A
Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.
| One-way run | 120 V 1Ø | 240 V 1Ø | 480 V 3Ø |
|---|---|---|---|
| 50 ft | 350 kcmil | 350 kcmil | 350 kcmil |
| 75 ft | 350 kcmil | 350 kcmil | 350 kcmil |
| 100 ft | 350 kcmil | 350 kcmil | 350 kcmil |
| 150 ft | 350 kcmil | 350 kcmil | 350 kcmil |
| 200 ft | 500 kcmil | 350 kcmil | 350 kcmil |
| 250 ft | 600 kcmil | 350 kcmil | 350 kcmil |
| 300 ft | 750 kcmil | 350 kcmil | 350 kcmil |
Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.
Hot attics, conduit runs and bundling
What a 300 A circuit actually needs once ambient temperature and conductor count are applied.
| Ambient | 3 conductors | 4–6 conductors | 7–9 conductors |
|---|---|---|---|
| 30 °C | 350 kcmil | 500 kcmil | 600 kcmil |
| 40 °C | 400 kcmil | 600 kcmil | 750 kcmil |
| 50 °C | 500 kcmil | 750 kcmil | — |
| 60 °C | 750 kcmil | — | — |
Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 300 A.
Where 300 A circuits are actually used
300 A is a service and main-distribution rating: commercial buildings, apartment house services, large process equipment, and multi-panel industrial distribution. It is nearly always fed with parallel sets or a bus rather than a single conductor per phase.
Voltage drop is a function of current, conductor area, one-way length, material and system voltage — there is no drop rule specific to 300 A. What makes it worth checking early here is scale: feeders at this rating are usually long and run in parallel sets, so a size that satisfies ampacity can still exceed the 3% guideline, and the remedy is upsizing every set or moving the distribution point closer. Running the drop calculation before selecting the raceway is cheaper than repulling. Voltage drop limits are recommendations in the code, not enforceable requirements.
Continuous loads
A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 300 A continuous becomes 375 A of design current, which lands on a 400 A overcurrent device and 500 kcmil copper.
Frequently asked
- What size wire do I need for a 300 amp breaker?
- 350 kcmil copper is the smallest conductor our model estimates at or above 300 A using a 75 °C insulation rating; 500 kcmil is required if the terminations are limited to 60 °C. In aluminium the equivalent is 500 kcmil. Verify against the code edition adopted locally before installing.
- Can I use aluminium wire on a 300 amp circuit?
- Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 300 A circuit steps up to 500 kcmil and uses K = 21.2 in the voltage-drop formula instead of 12.9.
- How far can a 300 amp circuit run?
- On 350 kcmil copper the 3% voltage-drop guideline is reached near 162 ft one-way at 120 V and 325 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
- Is a 300 amp breaker sized at 100% of the load?
- Only for non-continuous loads. A continuous load is designed at 125%, so 300 A of continuous current becomes 375 A of design current and lands on a 400 A device with conductors sized to match.
- What is typically on a 300 amp circuit?
- Commonly commercial feeders and distribution panels. The load type also drives the receptacle and disconnect ratings, not just the conductor size.
Other breaker sizes
More on 350 kcmil
Related charts & calculators
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.
- Allen Wrench Size ChartHex key sizes with SAE and metric cross-reference.