What Size Wire for a 200 Amp Breaker?

Conductor size, aluminium equivalent, derating and maximum run length for a 200 amp circuit — all derived from published conductor geometry and the voltage-drop formula.

Quick answer

A 200 amp circuit needs 4/0 AWG copper with 75 °C terminations, or 250 kcmil aluminium. 250 kcmil copper applies where equipment terminals are limited to 60 °C. Voltage drop reaches 3% at roughly 295 ft one-way on 240 V and 147 ft on 120 V.
Formula estimate — source: Power-law ampacity model fitted to conductor heat dissipation; ASTM B258 geometry

Copper @ 75 °C

4/0 AWG

Copper @ 60 °C

250 kcmil

Aluminium @ 75 °C

250 kcmil

3% drop @ 240 V

295ft

Conductor options for 200 A

Estimated ampacity of each candidate size, so you can see the margin you are buying.

Material / ratingMinimum sizeEstimated ampacityMargin over 200 A
Copper, 60 °C250 kcmil217 A+17 A
Copper, 75 °C4/0 AWG230 A+30 A
Copper, 90 °C3/0 AWG223 A+23 A
Aluminium, 75 °C250 kcmil200 A+0 A
Aluminium, 90 °C4/0 AWG202 A+2 A
Ampacity estimated as I = 0.0670 × cmil^0.6505, scaled for insulation rating and material.

Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.

Maximum run length on 4/0 AWG copper

One-way distance before voltage drop passes the 3% and 5% guidelines.

System3% limit5% limitDrop @ 100 ft
120 V 1Ø147 ft246 ft2.03%
240 V 1Ø295 ft492 ft1.02%
208 V 3Ø295 ft492 ft1.02%
480 V 3Ø681 ft1,136 ft0.44%

Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 4/0 AWG is 211,600 circular mils and 0.0490 Ω per 1000 ft at 20 °C.

Hot attics, conduit runs and bundling

What a 200 A circuit actually needs once ambient temperature and conductor count are applied.

Ambient3 conductors4–6 conductors7–9 conductors
30 °C4/0 AWG250 kcmil300 kcmil
40 °C4/0 AWG300 kcmil400 kcmil
50 °C300 kcmil400 kcmil500 kcmil
60 °C400 kcmil600 kcmil750 kcmil

Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 200 A.

Continuous loads

A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 200 A continuous becomes 250 A of design current, which lands on a 250 A overcurrent device and 250 kcmil copper.

Frequently asked

What size wire do I need for a 200 amp breaker?
4/0 AWG copper is the smallest conductor our model estimates at or above 200 A using a 75 °C insulation rating; 250 kcmil is required if the terminations are limited to 60 °C. In aluminium the equivalent is 250 kcmil. Verify against the code edition adopted locally before installing.
Can I use aluminium wire on a 200 amp circuit?
Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 200 A circuit steps up to 250 kcmil and uses K = 21.2 in the voltage-drop formula instead of 12.9.
How far can a 200 amp circuit run?
On 4/0 AWG copper the 3% voltage-drop guideline is reached near 147 ft one-way at 120 V and 295 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
Is a 200 amp breaker sized at 100% of the load?
Only for non-continuous loads. A continuous load is designed at 125%, so 200 A of continuous current becomes 250 A of design current and lands on a 250 A device with conductors sized to match.
What is typically on a 200 amp circuit?
Commonly standard residential service entrance. The load type also drives the receptacle and disconnect ratings, not just the conductor size.

Wire and breakers for a 200 A circuit

Other breaker sizes

More on 4/0 AWG

Related charts & calculators