What Size Wire for a 200 Amp Breaker?
Conductor size, aluminium equivalent, derating and maximum run length for a 200 amp circuit — all derived from published conductor geometry and the voltage-drop formula.
Quick answer
Copper @ 75 °C
4/0 AWG
Copper @ 60 °C
250 kcmil
Aluminium @ 75 °C
250 kcmil
3% drop @ 240 V
295ft
Conductor options for 200 A
Estimated ampacity of each candidate size, so you can see the margin you are buying.
| Material / rating | Minimum size | Estimated ampacity | Margin over 200 A |
|---|---|---|---|
| Copper, 60 °C | 250 kcmil | 217 A | +17 A |
| Copper, 75 °C | 4/0 AWG | 230 A | +30 A |
| Copper, 90 °C | 3/0 AWG | 223 A | +23 A |
| Aluminium, 75 °C | 250 kcmil | 200 A | +0 A |
| Aluminium, 90 °C | 4/0 AWG | 202 A | +2 A |
Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.
Maximum run length on 4/0 AWG copper
One-way distance before voltage drop passes the 3% and 5% guidelines.
| System | 3% limit | 5% limit | Drop @ 100 ft |
|---|---|---|---|
| 120 V 1Ø | 147 ft | 246 ft | 2.03% |
| 240 V 1Ø | 295 ft | 492 ft | 1.02% |
| 208 V 3Ø | 295 ft | 492 ft | 1.02% |
| 480 V 3Ø | 681 ft | 1,136 ft | 0.44% |
Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 4/0 AWG is 211,600 circular mils and 0.0490 Ω per 1000 ft at 20 °C.
Wire size by run length for 200 A
Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.
| One-way run | 120 V 1Ø | 240 V 1Ø | 480 V 3Ø |
|---|---|---|---|
| 50 ft | 4/0 AWG | 4/0 AWG | 4/0 AWG |
| 75 ft | 4/0 AWG | 4/0 AWG | 4/0 AWG |
| 100 ft | 4/0 AWG | 4/0 AWG | 4/0 AWG |
| 150 ft | 250 kcmil | 4/0 AWG | 4/0 AWG |
| 200 ft | 300 kcmil | 4/0 AWG | 4/0 AWG |
| 250 ft | 400 kcmil | 4/0 AWG | 4/0 AWG |
| 300 ft | 500 kcmil | 250 kcmil | 4/0 AWG |
Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.
Hot attics, conduit runs and bundling
What a 200 A circuit actually needs once ambient temperature and conductor count are applied.
| Ambient | 3 conductors | 4–6 conductors | 7–9 conductors |
|---|---|---|---|
| 30 °C | 4/0 AWG | 250 kcmil | 300 kcmil |
| 40 °C | 4/0 AWG | 300 kcmil | 400 kcmil |
| 50 °C | 300 kcmil | 400 kcmil | 500 kcmil |
| 60 °C | 400 kcmil | 600 kcmil | 750 kcmil |
Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 200 A.
Where 200 A circuits are actually used
200 A is the standard modern residential service size and a common commercial subfeeder. At this rating you are almost never wiring a load — you are wiring a service entrance or a panel feeder, and the conductor is sized against the calculated service load rather than a single appliance nameplate.
Service and feeder conductors get treatment that branch circuits do not. A dwelling service or main-power feeder is permitted to be sized at 83% of the service rating, which is why 4/0 aluminium is routine on a 200 A residential service even though 200 A of ordinary feeder would call for more copper. That allowance applies to the main service or feeder only, not to the branch circuits downstream.
The practical constraints at 200 A are mechanical and thermal rather than electrical: lug size and termination temperature at the panel, conduit fill and pulling tension on parallel sets, and the 75 °C termination limit that caps what the 90 °C insulation on the conductor would otherwise allow. Voltage drop matters on long rural service laterals, where a 300 ft run can force the next size up on drop alone.
Continuous loads
A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 200 A continuous becomes 250 A of design current, which lands on a 250 A overcurrent device and 250 kcmil copper.
Frequently asked
- What size wire do I need for a 200 amp breaker?
- 4/0 AWG copper is the smallest conductor our model estimates at or above 200 A using a 75 °C insulation rating; 250 kcmil is required if the terminations are limited to 60 °C. In aluminium the equivalent is 250 kcmil. Verify against the code edition adopted locally before installing.
- Can I use aluminium wire on a 200 amp circuit?
- Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 200 A circuit steps up to 250 kcmil and uses K = 21.2 in the voltage-drop formula instead of 12.9.
- How far can a 200 amp circuit run?
- On 4/0 AWG copper the 3% voltage-drop guideline is reached near 147 ft one-way at 120 V and 295 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
- Is a 200 amp breaker sized at 100% of the load?
- Only for non-continuous loads. A continuous load is designed at 125%, so 200 A of continuous current becomes 250 A of design current and lands on a 250 A device with conductors sized to match.
- What is typically on a 200 amp circuit?
- Commonly standard residential service entrance. The load type also drives the receptacle and disconnect ratings, not just the conductor size.
Other breaker sizes
More on 4/0 AWG
Related charts & calculators
- Rigid Conduit Fill ChartRMC and IMC conductor counts per trade size, side by side.
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.