What Size Wire for a 350 Amp Breaker?
Conductor size, aluminium equivalent, derating and maximum run length for a 350 amp circuit — all derived from published conductor geometry and the voltage-drop formula.
Quick answer
Copper @ 75 °C
500 kcmil
Copper @ 60 °C
600 kcmil
Aluminium @ 75 °C
600 kcmil
3% drop @ 240 V
398ft
Conductor options for 350 A
Estimated ampacity of each candidate size, so you can see the margin you are buying.
| Material / rating | Minimum size | Estimated ampacity | Margin over 350 A |
|---|---|---|---|
| Copper, 60 °C | 600 kcmil | 384 A | +34 A |
| Copper, 75 °C | 500 kcmil | 403 A | +53 A |
| Copper, 90 °C | 350 kcmil | 360 A | +10 A |
| Aluminium, 75 °C | 600 kcmil | 354 A | +4 A |
| Aluminium, 90 °C | 500 kcmil | 354 A | +4 A |
Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.
Maximum run length on 500 kcmil copper
One-way distance before voltage drop passes the 3% and 5% guidelines.
| System | 3% limit | 5% limit | Drop @ 100 ft |
|---|---|---|---|
| 120 V 1Ø | 199 ft | 332 ft | 1.51% |
| 240 V 1Ø | 398 ft | 664 ft | 0.75% |
| 208 V 3Ø | 398 ft | 664 ft | 0.75% |
| 480 V 3Ø | 920 ft | 1,534 ft | 0.33% |
Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 500 kcmil is 500,000 circular mils and 0.0207 Ω per 1000 ft at 20 °C.
Wire size by run length for 350 A
Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.
| One-way run | 120 V 1Ø | 240 V 1Ø | 480 V 3Ø |
|---|---|---|---|
| 50 ft | 500 kcmil | 500 kcmil | 500 kcmil |
| 75 ft | 500 kcmil | 500 kcmil | 500 kcmil |
| 100 ft | 500 kcmil | 500 kcmil | 500 kcmil |
| 150 ft | 500 kcmil | 500 kcmil | 500 kcmil |
| 200 ft | 600 kcmil | 500 kcmil | 500 kcmil |
| 250 ft | 750 kcmil | 500 kcmil | 500 kcmil |
| 300 ft | — | 500 kcmil | 500 kcmil |
Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.
Hot attics, conduit runs and bundling
What a 350 A circuit actually needs once ambient temperature and conductor count are applied.
| Ambient | 3 conductors | 4–6 conductors | 7–9 conductors |
|---|---|---|---|
| 30 °C | 500 kcmil | 600 kcmil | 750 kcmil |
| 40 °C | 500 kcmil | 750 kcmil | — |
| 50 °C | 750 kcmil | — | — |
| 60 °C | — | — | — |
Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 350 A.
Where 350 A circuits are actually used
350 A appears on commercial services, industrial machine feeds, chiller and compressor plants, and switchboard sections. It is chosen from a calculated load that fell between the 300 A and 400 A standard devices, usually with parallel conductor sets.
Mechanical constraints often bind before electrical ones do. Bending radius, sidewall pressure at each 90, lug torque and pulling tension apply to any large-conductor pull, not only at 350 A — they simply become harder to satisfy as conductors get stiffer and sets multiply. The same holds for ampacity adjustment: it is triggered by having more than three current-carrying conductors in a raceway or bundle at any rating, but with parallel sets at this size the conductor count crosses that threshold routinely, and the adjustment can erase margin that a single-set calculation appeared to show.
Continuous loads
A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 350 A continuous becomes 437.5 A of design current, which lands on a 450 A overcurrent device and 600 kcmil copper.
Frequently asked
- What size wire do I need for a 350 amp breaker?
- 500 kcmil copper is the smallest conductor our model estimates at or above 350 A using a 75 °C insulation rating; 600 kcmil is required if the terminations are limited to 60 °C. In aluminium the equivalent is 600 kcmil. Verify against the code edition adopted locally before installing.
- Can I use aluminium wire on a 350 amp circuit?
- Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 350 A circuit steps up to 600 kcmil and uses K = 21.2 in the voltage-drop formula instead of 12.9.
- How far can a 350 amp circuit run?
- On 500 kcmil copper the 3% voltage-drop guideline is reached near 199 ft one-way at 120 V and 398 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
- Is a 350 amp breaker sized at 100% of the load?
- Only for non-continuous loads. A continuous load is designed at 125%, so 350 A of continuous current becomes 437.5 A of design current and lands on a 450 A device with conductors sized to match.
- What is typically on a 350 amp circuit?
- Commonly commercial service and switchgear feeders. The load type also drives the receptacle and disconnect ratings, not just the conductor size.
Other breaker sizes
More on 500 kcmil
Related charts & calculators
- Allen Wrench Size ChartHex key sizes with SAE and metric cross-reference.
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.