What Size Wire for a 100 Amp Breaker?
Conductor size, aluminium equivalent, derating and maximum run length for a 100 amp circuit — all derived from published conductor geometry and the voltage-drop formula.
Quick answer
Copper @ 75 °C
2 AWG
Copper @ 60 °C
1 AWG
Aluminium @ 75 °C
1/0 AWG
3% drop @ 240 V
185ft
Conductor options for 100 A
Estimated ampacity of each candidate size, so you can see the margin you are buying.
| Material / rating | Minimum size | Estimated ampacity | Margin over 100 A |
|---|---|---|---|
| Copper, 60 °C | 1 AWG | 107 A | +7 A |
| Copper, 75 °C | 2 AWG | 108 A | +8 A |
| Copper, 90 °C | 3 AWG | 105 A | +5 A |
| Aluminium, 75 °C | 1/0 AWG | 114 A | +14 A |
| Aluminium, 90 °C | 1 AWG | 111 A | +11 A |
Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.
Maximum run length on 2 AWG copper
One-way distance before voltage drop passes the 3% and 5% guidelines.
| System | 3% limit | 5% limit | Drop @ 100 ft |
|---|---|---|---|
| 120 V 1Ø | 92 ft | 154 ft | 3.24% |
| 240 V 1Ø | 185 ft | 308 ft | 1.62% |
| 208 V 3Ø | 185 ft | 308 ft | 1.62% |
| 480 V 3Ø | 427 ft | 712 ft | 0.7% |
Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 2 AWG is 66,371 circular mils and 0.1563 Ω per 1000 ft at 20 °C.
Wire size by run length for 100 A
Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.
| One-way run | 120 V 1Ø | 240 V 1Ø | 480 V 3Ø |
|---|---|---|---|
| 50 ft | 2 AWG | 2 AWG | 2 AWG |
| 75 ft | 2 AWG | 2 AWG | 2 AWG |
| 100 ft | 1 AWG | 2 AWG | 2 AWG |
| 150 ft | 2/0 AWG | 2 AWG | 2 AWG |
| 200 ft | 3/0 AWG | 1 AWG | 2 AWG |
| 250 ft | 4/0 AWG | 1/0 AWG | 2 AWG |
| 300 ft | 250 kcmil | 2/0 AWG | 2 AWG |
Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.
Hot attics, conduit runs and bundling
What a 100 A circuit actually needs once ambient temperature and conductor count are applied.
| Ambient | 3 conductors | 4–6 conductors | 7–9 conductors |
|---|---|---|---|
| 30 °C | 2 AWG | 1 AWG | 1/0 AWG |
| 40 °C | 1 AWG | 1/0 AWG | 2/0 AWG |
| 50 °C | 1/0 AWG | 2/0 AWG | 3/0 AWG |
| 60 °C | 3/0 AWG | 4/0 AWG | 250 kcmil |
Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 100 A.
Where 100 A circuits are actually used
100 A is the second most common residential service size after 200 A, the standard feed for an accessory dwelling unit or large detached shop, and a frequent commercial subfeeder. On older housing stock it is the existing service that a panel upgrade replaces.
The service and main-feeder allowance is the rule that separates 100 A from ordinary branch-circuit sizing: a dwelling service or main power feeder may be sized at 83% of the rating, which is why 4 AWG copper or 2 AWG aluminium serves a 100 A residential service. That allowance does not extend to the branch circuits or to non-dwelling feeders.
Continuous loads
A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 100 A continuous becomes 125 A of design current, which lands on a 125 A overcurrent device and 1 AWG copper.
Frequently asked
- What size wire do I need for a 100 amp breaker?
- 2 AWG copper is the smallest conductor our model estimates at or above 100 A using a 75 °C insulation rating; 1 AWG is required if the terminations are limited to 60 °C. In aluminium the equivalent is 1/0 AWG. Verify against the code edition adopted locally before installing.
- Can I use aluminium wire on a 100 amp circuit?
- Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 100 A circuit steps up to 1/0 AWG and uses K = 21.2 in the voltage-drop formula instead of 12.9.
- How far can a 100 amp circuit run?
- On 2 AWG copper the 3% voltage-drop guideline is reached near 92 ft one-way at 120 V and 185 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
- Is a 100 amp breaker sized at 100% of the load?
- Only for non-continuous loads. A continuous load is designed at 125%, so 100 A of continuous current becomes 125 A of design current and lands on a 125 A device with conductors sized to match.
- What is typically on a 100 amp circuit?
- Commonly detached garage, shop and ADU feeders, small service. The load type also drives the receptacle and disconnect ratings, not just the conductor size.
Other breaker sizes
More on 2 AWG
Related charts & calculators
- PVC Conduit Fill ChartSchedule 40 and Schedule 80 conductor counts and usable areas.
- Rigid Conduit Fill ChartRMC and IMC conductor counts per trade size, side by side.
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.