6 AWG Breaker Size & Ampacity
6 AWG copper is estimated at 59 A at 75 °C, supporting a 50 A overcurrent device. Breaker pairing and derating shown.
Quick answer
6 AWG copper pairs with a 50 A breaker at 75 °C terminations, from an estimated ampacity of 59 A. Aluminium of the same size is about 46 A. A continuous load on that circuit should not exceed 47 A, since continuous loads are sized at 125%.
Max breaker (Cu, 75 °C)
50A
Copper 60 / 75 / 90 °C
50 / 59 / 67A
Aluminium 75 °C
46A
Max continuous load
47A
Ampacity and breaker pairing
Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.
| Material | 60 °C | 75 °C | 90 °C | Max device @ 75 °C |
|---|---|---|---|---|
| Copper | 50 A | 59 A | 67 A | 50 A |
| Aluminium | 39 A | 46 A | 52 A | 45 A |
Formula estimate — source: Ampacity from the site power-law model, not a code table
Derated ampacity and the device that still fits
Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 67 A → 50 A | 61 A → 50 A | 55 A → 50 A | 47 A → 45 A |
| 6 | 54 A → 50 A | 49 A → 45 A | 44 A → 40 A | 38 A → 35 A |
| 9 | 47 A → 45 A | 43 A → 40 A | 38 A → 35 A | 33 A → 30 A |
| 15 | 34 A → 30 A | 31 A → 30 A | 27 A → 25 A | 24 A → 20 A |
| 25 | 30 A → 30 A | 28 A → 25 A | 25 A → 25 A | 21 A → 20 A |
Source & method: Continuous-load example: a 47 A continuous load needs 59 A of design current and a 60 A device. Size your own load.
Neighbouring sizes
Frequently asked
- What breaker size for 6 AWG wire?
- 6 AWG copper at 75 °C terminations supports up to a 50 A overcurrent device, based on an estimated ampacity of 59 A. Aluminium of the same size supports less: about 46 A.
- How many amps can 6 AWG handle?
- Estimated 50 A at 60 °C, 59 A at 75 °C and 67 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
- How does a continuous load change the breaker size?
- Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
- Can the breaker be larger than the wire ampacity?
- Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.
More on 6 AWG
Related charts & calculators
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.
- Allen Wrench Size ChartHex key sizes with SAE and metric cross-reference.
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.