What Size Wire for a 175 Amp Breaker?
Conductor size, aluminium equivalent, derating and maximum run length for a 175 amp circuit — all derived from published conductor geometry and the voltage-drop formula.
Quick answer
Copper @ 75 °C
3/0 AWG
Copper @ 60 °C
4/0 AWG
Aluminium @ 75 °C
4/0 AWG
3% drop @ 240 V
267ft
Conductor options for 175 A
Estimated ampacity of each candidate size, so you can see the margin you are buying.
| Material / rating | Minimum size | Estimated ampacity | Margin over 175 A |
|---|---|---|---|
| Copper, 60 °C | 4/0 AWG | 195 A | +20 A |
| Copper, 75 °C | 3/0 AWG | 198 A | +23 A |
| Copper, 90 °C | 2/0 AWG | 192 A | +17 A |
| Aluminium, 75 °C | 4/0 AWG | 180 A | +5 A |
| Aluminium, 90 °C | 4/0 AWG | 202 A | +27 A |
Source & method: Conductor areas come from the ASTM B258 relationship d = 5 × 92^((36 − n) / 39). Ampacity is a fitted physical model, not a reproduction of any code table, and runs within roughly ±8% of published values.
Maximum run length on 3/0 AWG copper
One-way distance before voltage drop passes the 3% and 5% guidelines.
| System | 3% limit | 5% limit | Drop @ 100 ft |
|---|---|---|---|
| 120 V 1Ø | 133 ft | 222 ft | 2.24% |
| 240 V 1Ø | 267 ft | 445 ft | 1.12% |
| 208 V 3Ø | 267 ft | 446 ft | 1.12% |
| 480 V 3Ø | 618 ft | 1,030 ft | 0.49% |
Source & method: VD = 2 × K × I × L / cmil single phase, 1.732 × K × I × L / cmil three phase, with K = 12.9 for copper. 3/0 AWG is 167,806 circular mils and 0.0618 Ω per 1000 ft at 20 °C.
Wire size by run length for 175 A
Ampacity sets the floor; distance is what actually forces the upsize on long runs. Smallest copper conductor that carries the load and still holds 3% drop.
| One-way run | 120 V 1Ø | 240 V 1Ø | 480 V 3Ø |
|---|---|---|---|
| 50 ft | 3/0 AWG | 3/0 AWG | 3/0 AWG |
| 75 ft | 3/0 AWG | 3/0 AWG | 3/0 AWG |
| 100 ft | 3/0 AWG | 3/0 AWG | 3/0 AWG |
| 150 ft | 4/0 AWG | 3/0 AWG | 3/0 AWG |
| 200 ft | 300 kcmil | 3/0 AWG | 3/0 AWG |
| 250 ft | 350 kcmil | 3/0 AWG | 3/0 AWG |
| 300 ft | 400 kcmil | 4/0 AWG | 3/0 AWG |
Source & method: A dash means no listed size holds 3% at that distance and voltage — split the load, raise the system voltage, or move the panel closer.
Hot attics, conduit runs and bundling
What a 175 A circuit actually needs once ambient temperature and conductor count are applied.
| Ambient | 3 conductors | 4–6 conductors | 7–9 conductors |
|---|---|---|---|
| 30 °C | 3/0 AWG | 4/0 AWG | 250 kcmil |
| 40 °C | 4/0 AWG | 250 kcmil | 300 kcmil |
| 50 °C | 250 kcmil | 350 kcmil | 400 kcmil |
| 60 °C | 350 kcmil | 500 kcmil | 600 kcmil |
Source & method: Ambient correction F = √((Tc − Ta) / (Tc − 30)) with Tc = 75 °C; bundling adjustment uses the standard stepped schedule (1.00 / 0.80 / 0.70). The conductor shown is the smallest copper size whose corrected ampacity still carries 175 A.
Where 175 A circuits are actually used
175 A is a commercial feeder rating used where the calculated load exceeds 150 A but a 200 A device would oversize the equipment being protected. It also appears as the maximum device on some transformer secondary and motor-control feeders.
Transformer secondary conductors are the notable case at this rating: they get specific protection rules rather than ordinary feeder treatment, and the primary device does not automatically protect the secondary conductors. Treat a 175 A transformer feed as a secondary-conductor problem, not a chart lookup.
175 A is common on commercial services and larger dwelling upgrades that stop short of 200 A because the meter base or the utility lateral limits the rating. The termination hardware at this level is normally listed for aluminium as well as copper, and the sizing question turns on whether the service allowance for a main power feeder applies to the specific run.
Continuous loads
A continuous load — one expected to run three hours or more, like commercial lighting or an EV charger — is designed at 125% of the load current. 175 A continuous becomes 218.8 A of design current, which lands on a 225 A overcurrent device and 4/0 AWG copper.
Frequently asked
- What size wire do I need for a 175 amp breaker?
- 3/0 AWG copper is the smallest conductor our model estimates at or above 175 A using a 75 °C insulation rating; 4/0 AWG is required if the terminations are limited to 60 °C. In aluminium the equivalent is 4/0 AWG. Verify against the code edition adopted locally before installing.
- Can I use aluminium wire on a 175 amp circuit?
- Yes, where the terminations are rated for aluminium. Because aluminium carries roughly 78% of the current of the same copper size, a 175 A circuit steps up to 4/0 AWG and uses K = 21.2 in the voltage-drop formula instead of 12.9.
- How far can a 175 amp circuit run?
- On 3/0 AWG copper the 3% voltage-drop guideline is reached near 133 ft one-way at 120 V and 267 ft at 240 V. Longer runs need the next size or two up — length, not ampacity, decides most feeder sizes.
- Is a 175 amp breaker sized at 100% of the load?
- Only for non-continuous loads. A continuous load is designed at 125%, so 175 A of continuous current becomes 218.8 A of design current and lands on a 225 A device with conductors sized to match.
- What is typically on a 175 amp circuit?
- Commonly feeders for light commercial panels. The load type also drives the receptacle and disconnect ratings, not just the conductor size.
Other breaker sizes
More on 3/0 AWG
Related charts & calculators
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.
- Wire Gauge ChartAWG diameter, circular mils, resistance and amp capacity in one table.
- Wire Size ChartWhat size wire for each breaker rating and typical circuit.
- kcmil Wire Size ChartMCM to AWG conversion, circular mils, resistance and ampacity for 250-750 kcmil.
- Conduit Fill ChartMaximum THHN conductors per trade size for every raceway type.