10 AWG Conduit Fill by Conduit Size
How many 10 AWG THHN conductors fit in EMT, IMC, RMC and PVC conduit, 1/2 inch through 4 inch, with the 40% fill rule applied.
Quick answer
10 AWG conductors per conduit trade size
Same-size conductors only, at 53% for one, 31% for two and 40% for three or more.
| Conduit | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| EMT | 5 | 10 | 16 | 28 | 38 | 63 | 110 | 167 | 200 | 200 |
| IMC | 6 | 11 | 18 | 31 | 42 | 68 | 97 | 150 | 200 | 200 |
| RMC | 5 | 10 | 16 | 28 | 39 | 64 | 92 | 142 | 189 | 200 |
| PVC Sch 40 | 5 | 9 | 15 | 27 | 37 | 62 | 88 | 137 | 184 | 200 |
| PVC Sch 80 | 4 | 7 | 13 | 23 | 32 | 54 | 77 | 121 | 164 | 200 |
Source & method: Counts are the largest whole number where n × conductor area stays inside the raceway area times the applicable fill percentage. Mix conductor sizes in the calculator.
Fill behaviour at 10 AWG: 3/4 inch becomes the working minimum
At 10 AWG the counts drop enough that 3/4 inch is the practical floor for anything beyond a single two-wire circuit with a ground. A 30 A water heater or dryer circuit fits 1/2 inch; add a second circuit and the raceway grows.
10 AWG is also frequently stranded, which pulls easier than solid at the same area but occupies the same nominal insulated diameter in the calculation. The table on this page uses nominal THHN outside diameter, so stranded and solid of the same size return the same count.
Source & method: Counts referenced above come from the computed table on this page — how these numbers are derived.
What each raceway type means
- EMT — EMT (electrical metallic tubing)
- IMC — IMC (intermediate metal conduit)
- RMC — RMC (rigid metal conduit)
- PVC Sch 40 — PVC Schedule 40
- PVC Sch 80 — PVC Schedule 80
Full fill charts by raceway
Per-type counts for every trade size, plus the cross-type comparison and reverse lookup.
- EMT conduit fill chart — 1/2" to 4"Electrical metallic tubing, thinnest wall, highest count per trade size.
- Conduit fill chart — all raceway types comparedEMT, IMC, RMC, PVC 40 and PVC 80 side by side with reverse lookup.
- PVC conduit fill chart — Schedule 40 and 80Thicker walls, roughly 15 to 25% fewer conductors than tubing.
- Rigid conduit fill chart — RMC and IMCThreaded metal raceway counts and usable areas.
Frequently asked
- How many 10 AWG wires fit in 1/2 inch EMT?
- 5 10 AWG THHN conductors fit in 1/2 inch EMT at the applicable fill percentage.
- How many 10 AWG wires fit in 3/4 inch EMT?
- 10 conductors, using a nominal THHN outside diameter of 0.164 in and the 40% fill rule for three or more conductors.
- Do neutrals and grounds count toward fill?
- Yes, every conductor in the raceway counts for fill. Grounds are excluded only from the count of current-carrying conductors used for ampacity adjustment.
- What is the cross-sectional area of 10 AWG THHN?
- About 0.0211 square inches, from A = π × (OD / 2)² with a nominal insulated OD of 0.164 in.
More on 10 AWG
Conduit fill for nearby sizes
Same 40% fill rule applied to the sizes either side of this one, wrapping around the range so every size is reachable.
Related charts & calculators
- Wire Gauge ChartAWG diameter, circular mils, resistance and amp capacity in one table.
- Wire Size ChartWhat size wire for each breaker rating and typical circuit.
- kcmil Wire Size ChartMCM to AWG conversion, circular mils, resistance and ampacity for 250-750 kcmil.
- Conduit Fill ChartMaximum THHN conductors per trade size for every raceway type.
- EMT Conduit Fill ChartConductor counts and internal areas for electrical metallic tubing.
- PVC Conduit Fill ChartSchedule 40 and Schedule 80 conductor counts and usable areas.