10 AWG Breaker Size — Amps & Overcurrent Rating
10 AWG copper is estimated at 32 A at 75 °C, which supports a 30 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.
Quick answer
10 AWG copper pairs with a 30 A breaker at 75 °C terminations, from an estimated ampacity of 32 A. Aluminium of the same size is about 25 A. A continuous load on that circuit should not exceed 26 A, since continuous loads are sized at 125%.
Max breaker (Cu, 75 °C)
30A
Copper 60 / 75 / 90 °C
27 / 32 / 37A
Aluminium 75 °C
25A
Max continuous load
26A
Ampacity and breaker pairing
Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.
| Material | 60 °C | 75 °C | 90 °C | Max device @ 75 °C |
|---|---|---|---|---|
| Copper | 27 A | 32 A | 37 A | 30 A |
| Aluminium | 21 A | 25 A | 28 A | 25 A |
Formula estimate — source: Ampacity from the site power-law model, not a code table
Derated ampacity and the device that still fits
Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 37 A → 30 A | 34 A → 30 A | 30 A → 30 A | 26 A → 25 A |
| 6 | 30 A → 30 A | 27 A → 25 A | 24 A → 20 A | 21 A → 20 A |
| 9 | 26 A → 25 A | 24 A → 20 A | 21 A → 20 A | 18 A → 15 A |
| 15 | 19 A → 15 A | 17 A → 15 A | 15 A → 15 A | 13 A → — |
| 25 | 17 A → 15 A | 15 A → 15 A | 14 A → — | 12 A → — |
Source & method: Continuous-load example: a 26 A continuous load needs 32 A of design current and a 35 A device. Size your own load.
Neighbouring sizes
Frequently asked
- What breaker size for 10 AWG wire?
- 10 AWG copper at 75 °C terminations supports up to a 30 A overcurrent device, based on an estimated ampacity of 32 A. Aluminium of the same size supports less: about 25 A.
- How many amps can 10 AWG handle?
- Estimated 27 A at 60 °C, 32 A at 75 °C and 37 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
- How does a continuous load change the breaker size?
- Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
- Can the breaker be larger than the wire ampacity?
- Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.
More on 10 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.