10 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 10 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 72 ft one-way. Full table by load, voltage and distance.

Quick answer

10 AWG copper reaches 3% voltage drop at about 72 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 4.97 V (4.14%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 10,383 circular mils.

3% limit @ 20 A, 120 V

72ft

3% limit @ 20 A, 240 V

144ft

Drop @ 100 ft, 20 A

4.97V

Ω / 1000 ft (Cu)

0.9988

Maximum one-way run length at 3% drop

Copper 10 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A289 ft579 ft579 ft1,338 ft
10 A144 ft289 ft289 ft669 ft
15 A96 ft193 ft193 ft446 ft
20 A72 ft144 ft144 ft334 ft
25 A57 ft115 ft115 ft267 ft
30 A48 ft96 ft96 ft223 ft
40 A36 ft72 ft72 ft167 ft
50 A28 ft57 ft57 ft133 ft
60 A24 ft48 ft48 ft111 ft
80 A18 ft36 ft36 ft83 ft
100 A14 ft28 ft28 ft66 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.52%0.78%1.04%1.55%
50 ft1.04%1.55%2.07%3.11%
75 ft1.55%2.33%3.11%4.66%
100 ft2.07%3.11%4.14%6.21%
150 ft3.11%4.66%6.21%9.32%
200 ft4.14%6.21%8.28%12.42%
300 ft6.21%9.32%12.42%18.64%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 10 AWG wire?
At 20 A on a 120 V single-phase circuit, 10 AWG copper stays under 3% voltage drop for about 72 ft one-way. At 240 V the same load reaches roughly 144 ft, because allowable drop scales with system voltage.
What is the voltage drop of 10 AWG wire per 100 feet?
About 4.97 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 10 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.