10 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 10 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 72 ft one-way. Full table by load, voltage and distance.
Quick answer
10 AWG copper reaches 3% voltage drop at about 72 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 4.97 V (4.14%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 10,383 circular mils.
3% limit @ 20 A, 120 V
72ft
3% limit @ 20 A, 240 V
144ft
Drop @ 100 ft, 20 A
4.97V
Ω / 1000 ft (Cu)
0.9988
Maximum one-way run length at 3% drop
Copper 10 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 289 ft | 579 ft | 579 ft | 1,338 ft |
| 10 A | 144 ft | 289 ft | 289 ft | 669 ft |
| 15 A | 96 ft | 193 ft | 193 ft | 446 ft |
| 20 A | 72 ft | 144 ft | 144 ft | 334 ft |
| 25 A | 57 ft | 115 ft | 115 ft | 267 ft |
| 30 A | 48 ft | 96 ft | 96 ft | 223 ft |
| 40 A | 36 ft | 72 ft | 72 ft | 167 ft |
| 50 A | 28 ft | 57 ft | 57 ft | 133 ft |
| 60 A | 24 ft | 48 ft | 48 ft | 111 ft |
| 80 A | 18 ft | 36 ft | 36 ft | 83 ft |
| 100 A | 14 ft | 28 ft | 28 ft | 66 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.52% | 0.78% | 1.04% | 1.55% |
| 50 ft | 1.04% | 1.55% | 2.07% | 3.11% |
| 75 ft | 1.55% | 2.33% | 3.11% | 4.66% |
| 100 ft | 2.07% | 3.11% | 4.14% | 6.21% |
| 150 ft | 3.11% | 4.66% | 6.21% | 9.32% |
| 200 ft | 4.14% | 6.21% | 8.28% | 12.42% |
| 300 ft | 6.21% | 9.32% | 12.42% | 18.64% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 10 AWG wire?
- At 20 A on a 120 V single-phase circuit, 10 AWG copper stays under 3% voltage drop for about 72 ft one-way. At 240 V the same load reaches roughly 144 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 10 AWG wire per 100 feet?
- About 4.97 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 10 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 10 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.