4/0 AWG Conduit Fill — Wires per Conduit Size

How many 4/0 AWG THHN conductors fit in EMT, IMC, RMC and PVC conduit, from 1/2 inch through 4 inch, with the 40% fill rule applied.

Quick answer

No 4/0 AWG THHN conductors fit in 1/2 inch EMT and 0 fit in 3/4 inch EMT, at 40% fill for three or more conductors. Each conductor consumes 0.3237 sq in from a nominal insulated outside diameter of 0.642 in. Neutrals and grounds count.

4/0 AWG conductors per conduit trade size

Same-size conductors only, at 53% for one, 31% for two and 40% for three or more.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT11147101418
IMC1124691316
RMC1114691215
PVC Sch 401114581215
PVC Sch 801113571013
Published standard — source: Raceway internal areas from product standards (EMT, IMC, RMC, PVC Sch 40, PVC Sch 80); conductor OD from nominal THHN dimensions

Source & method: Counts are the largest whole number where n × conductor area stays inside the raceway area times the applicable fill percentage. Mix conductor sizes in the calculator.

What each raceway type means

  • EMT EMT (electrical metallic tubing)
  • IMC IMC (intermediate metal conduit)
  • RMC RMC (rigid metal conduit)
  • PVC Sch 40 PVC Schedule 40
  • PVC Sch 80 PVC Schedule 80

Frequently asked

How many 4/0 AWG wires fit in 1/2 inch EMT?
None — this size does not fit 1/2 inch EMT; step up a trade size.
How many 4/0 AWG wires fit in 3/4 inch EMT?
0 conductors, using a nominal THHN outside diameter of 0.642 in and the 40% fill rule for three or more conductors.
Do neutrals and grounds count toward fill?
Yes, every conductor in the raceway counts for fill. Grounds are excluded only from the count of current-carrying conductors used for ampacity adjustment.
What is the cross-sectional area of 4/0 AWG THHN?
About 0.3237 square inches, from A = π × (OD / 2)² with a nominal insulated OD of 0.642 in.