4/0 AWG Breaker Size — Amps & Overcurrent Rating

4/0 AWG copper is estimated at 230 A at 75 °C, which supports a 225 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

4/0 AWG copper pairs with a 225 A breaker at 75 °C terminations, from an estimated ampacity of 230 A. Aluminium of the same size is about 180 A. A continuous load on that circuit should not exceed 184 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

225A

Copper 60 / 75 / 90 °C

195 / 230 / 260A

Aluminium 75 °C

180A

Max continuous load

184A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper195 A230 A260 A225 A
Aluminium152 A180 A202 A175 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3260 A → 225 A237 A → 225 A212 A → 200 A184 A → 175 A
6208 A → 200 A190 A → 175 A170 A → 150 A147 A → 125 A
9182 A → 175 A166 A → 150 A149 A → 125 A129 A → 125 A
15130 A → 125 A119 A → 110 A106 A → 100 A92 A → 90 A
25117 A → 110 A107 A → 100 A95 A → 90 A83 A → 80 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 184 A continuous load needs 230 A of design current and a 250 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 4/0 AWG wire?
4/0 AWG copper at 75 °C terminations supports up to a 225 A overcurrent device, based on an estimated ampacity of 230 A. Aluminium of the same size supports less: about 180 A.
How many amps can 4/0 AWG handle?
Estimated 195 A at 60 °C, 230 A at 75 °C and 260 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.

More on 4/0 AWG