4/0 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 4/0 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 1476 ft one-way. Full table by load, voltage and distance.
Quick answer
4/0 AWG copper reaches 3% voltage drop at about 1476 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.24 V (0.2%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 211,600 circular mils.
3% limit @ 20 A, 120 V
1476ft
3% limit @ 20 A, 240 V
2952ft
Drop @ 100 ft, 20 A
0.24V
Ω / 1000 ft (Cu)
0.0490
Maximum one-way run length at 3% drop
Copper 4/0 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 5,905 ft | 11,810 ft | 11,819 ft | 27,275 ft |
| 10 A | 2,952 ft | 5,905 ft | 5,909 ft | 13,637 ft |
| 15 A | 1,968 ft | 3,936 ft | 3,939 ft | 9,091 ft |
| 20 A | 1,476 ft | 2,952 ft | 2,954 ft | 6,818 ft |
| 25 A | 1,181 ft | 2,362 ft | 2,363 ft | 5,455 ft |
| 30 A | 984 ft | 1,968 ft | 1,969 ft | 4,545 ft |
| 40 A | 738 ft | 1,476 ft | 1,477 ft | 3,409 ft |
| 50 A | 590 ft | 1,181 ft | 1,181 ft | 2,727 ft |
| 60 A | 492 ft | 984 ft | 984 ft | 2,272 ft |
| 80 A | 369 ft | 738 ft | 738 ft | 1,704 ft |
| 100 A | 295 ft | 590 ft | 590 ft | 1,363 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.03% | 0.04% | 0.05% | 0.08% |
| 50 ft | 0.05% | 0.08% | 0.1% | 0.15% |
| 75 ft | 0.08% | 0.11% | 0.15% | 0.23% |
| 100 ft | 0.1% | 0.15% | 0.2% | 0.3% |
| 150 ft | 0.15% | 0.23% | 0.3% | 0.46% |
| 200 ft | 0.2% | 0.3% | 0.41% | 0.61% |
| 300 ft | 0.3% | 0.46% | 0.61% | 0.91% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 4/0 AWG wire?
- At 20 A on a 120 V single-phase circuit, 4/0 AWG copper stays under 3% voltage drop for about 1476 ft one-way. At 240 V the same load reaches roughly 2952 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 4/0 AWG wire per 100 feet?
- About 0.24 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 4/0 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 4/0 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.