4/0 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 4/0 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 1476 ft one-way. Full table by load, voltage and distance.

Quick answer

4/0 AWG copper reaches 3% voltage drop at about 1476 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.24 V (0.2%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 211,600 circular mils.

3% limit @ 20 A, 120 V

1476ft

3% limit @ 20 A, 240 V

2952ft

Drop @ 100 ft, 20 A

0.24V

Ω / 1000 ft (Cu)

0.0490

Maximum one-way run length at 3% drop

Copper 4/0 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A5,905 ft11,810 ft11,819 ft27,275 ft
10 A2,952 ft5,905 ft5,909 ft13,637 ft
15 A1,968 ft3,936 ft3,939 ft9,091 ft
20 A1,476 ft2,952 ft2,954 ft6,818 ft
25 A1,181 ft2,362 ft2,363 ft5,455 ft
30 A984 ft1,968 ft1,969 ft4,545 ft
40 A738 ft1,476 ft1,477 ft3,409 ft
50 A590 ft1,181 ft1,181 ft2,727 ft
60 A492 ft984 ft984 ft2,272 ft
80 A369 ft738 ft738 ft1,704 ft
100 A295 ft590 ft590 ft1,363 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.03%0.04%0.05%0.08%
50 ft0.05%0.08%0.1%0.15%
75 ft0.08%0.11%0.15%0.23%
100 ft0.1%0.15%0.2%0.3%
150 ft0.15%0.23%0.3%0.46%
200 ft0.2%0.3%0.41%0.61%
300 ft0.3%0.46%0.61%0.91%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 4/0 AWG wire?
At 20 A on a 120 V single-phase circuit, 4/0 AWG copper stays under 3% voltage drop for about 1476 ft one-way. At 240 V the same load reaches roughly 2952 ft, because allowable drop scales with system voltage.
What is the voltage drop of 4/0 AWG wire per 100 feet?
About 0.24 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 4/0 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.

More on 4/0 AWG