350 kcmil Breaker Size — Amps & Overcurrent Rating

350 kcmil copper is estimated at 319 A at 75 °C, which supports a 300 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

350 kcmil copper pairs with a 300 A breaker at 75 °C terminations, from an estimated ampacity of 319 A. Aluminium of the same size is about 249 A. A continuous load on that circuit should not exceed 255 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

300A

Copper 60 / 75 / 90 °C

271 / 319 / 360A

Aluminium 75 °C

249A

Max continuous load

255A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper271 A319 A360 A300 A
Aluminium211 A249 A281 A225 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3360 A → 300 A329 A → 300 A294 A → 250 A255 A → 250 A
6288 A → 250 A263 A → 250 A235 A → 225 A204 A → 200 A
9252 A → 250 A230 A → 225 A206 A → 200 A178 A → 175 A
15180 A → 175 A164 A → 150 A147 A → 125 A127 A → 125 A
25162 A → 150 A148 A → 125 A132 A → 125 A115 A → 110 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 255 A continuous load needs 319 A of design current and a 350 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 350 kcmil wire?
350 kcmil copper at 75 °C terminations supports up to a 300 A overcurrent device, based on an estimated ampacity of 319 A. Aluminium of the same size supports less: about 249 A.
How many amps can 350 kcmil handle?
Estimated 271 A at 60 °C, 319 A at 75 °C and 360 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.

More on 350 kcmil