350 kcmil Voltage Drop — Max Run Length by Load
Voltage drop for 350 kcmil copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 2441 ft one-way. Full table by load, voltage and distance.
Quick answer
350 kcmil copper reaches 3% voltage drop at about 2441 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.15 V (0.12%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 350,000 circular mils.
3% limit @ 20 A, 120 V
2441ft
3% limit @ 20 A, 240 V
4883ft
Drop @ 100 ft, 20 A
0.15V
Ω / 1000 ft (Cu)
0.0296
Maximum one-way run length at 3% drop
Copper 350 kcmil. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 9,767 ft | 19,534 ft | 19,549 ft | 45,115 ft |
| 10 A | 4,883 ft | 9,767 ft | 9,774 ft | 22,557 ft |
| 15 A | 3,255 ft | 6,511 ft | 6,516 ft | 15,038 ft |
| 20 A | 2,441 ft | 4,883 ft | 4,887 ft | 11,278 ft |
| 25 A | 1,953 ft | 3,906 ft | 3,909 ft | 9,023 ft |
| 30 A | 1,627 ft | 3,255 ft | 3,258 ft | 7,519 ft |
| 40 A | 1,220 ft | 2,441 ft | 2,443 ft | 5,639 ft |
| 50 A | 976 ft | 1,953 ft | 1,954 ft | 4,511 ft |
| 60 A | 813 ft | 1,627 ft | 1,629 ft | 3,759 ft |
| 80 A | 610 ft | 1,220 ft | 1,221 ft | 2,819 ft |
| 100 A | 488 ft | 976 ft | 977 ft | 2,255 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.02% | 0.02% | 0.03% | 0.05% |
| 50 ft | 0.03% | 0.05% | 0.06% | 0.09% |
| 75 ft | 0.05% | 0.07% | 0.09% | 0.14% |
| 100 ft | 0.06% | 0.09% | 0.12% | 0.18% |
| 150 ft | 0.09% | 0.14% | 0.18% | 0.28% |
| 200 ft | 0.12% | 0.18% | 0.25% | 0.37% |
| 300 ft | 0.18% | 0.28% | 0.37% | 0.55% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 350 kcmil wire?
- At 20 A on a 120 V single-phase circuit, 350 kcmil copper stays under 3% voltage drop for about 2441 ft one-way. At 240 V the same load reaches roughly 4883 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 350 kcmil wire per 100 feet?
- About 0.15 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 350 kcmil numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 350 kcmil
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.