250 kcmil Voltage Drop — Max Run Length by Load

Voltage drop for 250 kcmil copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 1744 ft one-way. Full table by load, voltage and distance.

Quick answer

250 kcmil copper reaches 3% voltage drop at about 1744 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.21 V (0.17%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 250,000 circular mils.

3% limit @ 20 A, 120 V

1744ft

3% limit @ 20 A, 240 V

3488ft

Drop @ 100 ft, 20 A

0.21V

Ω / 1000 ft (Cu)

0.0415

Maximum one-way run length at 3% drop

Copper 250 kcmil. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A6,976 ft13,953 ft13,964 ft32,225 ft
10 A3,488 ft6,976 ft6,982 ft16,112 ft
15 A2,325 ft4,651 ft4,654 ft10,741 ft
20 A1,744 ft3,488 ft3,491 ft8,056 ft
25 A1,395 ft2,790 ft2,792 ft6,445 ft
30 A1,162 ft2,325 ft2,327 ft5,370 ft
40 A872 ft1,744 ft1,745 ft4,028 ft
50 A697 ft1,395 ft1,396 ft3,222 ft
60 A581 ft1,162 ft1,163 ft2,685 ft
80 A436 ft872 ft872 ft2,014 ft
100 A348 ft697 ft698 ft1,611 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.02%0.03%0.04%0.06%
50 ft0.04%0.06%0.09%0.13%
75 ft0.06%0.1%0.13%0.19%
100 ft0.09%0.13%0.17%0.26%
150 ft0.13%0.19%0.26%0.39%
200 ft0.17%0.26%0.34%0.52%
300 ft0.26%0.39%0.52%0.77%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 250 kcmil wire?
At 20 A on a 120 V single-phase circuit, 250 kcmil copper stays under 3% voltage drop for about 1744 ft one-way. At 240 V the same load reaches roughly 3488 ft, because allowable drop scales with system voltage.
What is the voltage drop of 250 kcmil wire per 100 feet?
About 0.21 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 250 kcmil numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.