250 kcmil Voltage Drop — Max Run Length by Load
Voltage drop for 250 kcmil copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 1744 ft one-way. Full table by load, voltage and distance.
Quick answer
250 kcmil copper reaches 3% voltage drop at about 1744 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.21 V (0.17%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 250,000 circular mils.
3% limit @ 20 A, 120 V
1744ft
3% limit @ 20 A, 240 V
3488ft
Drop @ 100 ft, 20 A
0.21V
Ω / 1000 ft (Cu)
0.0415
Maximum one-way run length at 3% drop
Copper 250 kcmil. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 6,976 ft | 13,953 ft | 13,964 ft | 32,225 ft |
| 10 A | 3,488 ft | 6,976 ft | 6,982 ft | 16,112 ft |
| 15 A | 2,325 ft | 4,651 ft | 4,654 ft | 10,741 ft |
| 20 A | 1,744 ft | 3,488 ft | 3,491 ft | 8,056 ft |
| 25 A | 1,395 ft | 2,790 ft | 2,792 ft | 6,445 ft |
| 30 A | 1,162 ft | 2,325 ft | 2,327 ft | 5,370 ft |
| 40 A | 872 ft | 1,744 ft | 1,745 ft | 4,028 ft |
| 50 A | 697 ft | 1,395 ft | 1,396 ft | 3,222 ft |
| 60 A | 581 ft | 1,162 ft | 1,163 ft | 2,685 ft |
| 80 A | 436 ft | 872 ft | 872 ft | 2,014 ft |
| 100 A | 348 ft | 697 ft | 698 ft | 1,611 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.02% | 0.03% | 0.04% | 0.06% |
| 50 ft | 0.04% | 0.06% | 0.09% | 0.13% |
| 75 ft | 0.06% | 0.1% | 0.13% | 0.19% |
| 100 ft | 0.09% | 0.13% | 0.17% | 0.26% |
| 150 ft | 0.13% | 0.19% | 0.26% | 0.39% |
| 200 ft | 0.17% | 0.26% | 0.34% | 0.52% |
| 300 ft | 0.26% | 0.39% | 0.52% | 0.77% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 250 kcmil wire?
- At 20 A on a 120 V single-phase circuit, 250 kcmil copper stays under 3% voltage drop for about 1744 ft one-way. At 240 V the same load reaches roughly 3488 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 250 kcmil wire per 100 feet?
- About 0.21 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 250 kcmil numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 250 kcmil
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.