250 kcmil Breaker Size — Amps & Overcurrent Rating

250 kcmil copper is estimated at 257 A at 75 °C, which supports a 250 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

250 kcmil copper pairs with a 250 A breaker at 75 °C terminations, from an estimated ampacity of 257 A. Aluminium of the same size is about 200 A. A continuous load on that circuit should not exceed 206 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

250A

Copper 60 / 75 / 90 °C

217 / 257 / 289A

Aluminium 75 °C

200A

Max continuous load

206A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper217 A257 A289 A250 A
Aluminium170 A200 A226 A200 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3289 A → 250 A264 A → 250 A236 A → 225 A204 A → 200 A
6231 A → 225 A211 A → 200 A189 A → 175 A163 A → 150 A
9202 A → 200 A185 A → 175 A165 A → 150 A143 A → 125 A
15145 A → 125 A132 A → 125 A118 A → 110 A102 A → 100 A
25130 A → 125 A119 A → 110 A106 A → 100 A92 A → 90 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 206 A continuous load needs 257 A of design current and a 300 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 250 kcmil wire?
250 kcmil copper at 75 °C terminations supports up to a 250 A overcurrent device, based on an estimated ampacity of 257 A. Aluminium of the same size supports less: about 200 A.
How many amps can 250 kcmil handle?
Estimated 217 A at 60 °C, 257 A at 75 °C and 289 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.