3/0 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 3/0 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 1170 ft one-way. Full table by load, voltage and distance.

Quick answer

3/0 AWG copper reaches 3% voltage drop at about 1170 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.31 V (0.26%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 167,806 circular mils.

3% limit @ 20 A, 120 V

1170ft

3% limit @ 20 A, 240 V

2341ft

Drop @ 100 ft, 20 A

0.31V

Ω / 1000 ft (Cu)

0.0618

Maximum one-way run length at 3% drop

Copper 3/0 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A4,682 ft9,365 ft9,373 ft21,630 ft
10 A2,341 ft4,682 ft4,686 ft10,815 ft
15 A1,560 ft3,121 ft3,124 ft7,210 ft
20 A1,170 ft2,341 ft2,343 ft5,407 ft
25 A936 ft1,873 ft1,874 ft4,326 ft
30 A780 ft1,560 ft1,562 ft3,605 ft
40 A585 ft1,170 ft1,171 ft2,703 ft
50 A468 ft936 ft937 ft2,163 ft
60 A390 ft780 ft781 ft1,802 ft
80 A292 ft585 ft585 ft1,351 ft
100 A234 ft468 ft468 ft1,081 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.03%0.05%0.06%0.1%
50 ft0.06%0.1%0.13%0.19%
75 ft0.1%0.14%0.19%0.29%
100 ft0.13%0.19%0.26%0.38%
150 ft0.19%0.29%0.38%0.58%
200 ft0.26%0.38%0.51%0.77%
300 ft0.38%0.58%0.77%1.15%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 3/0 AWG wire?
At 20 A on a 120 V single-phase circuit, 3/0 AWG copper stays under 3% voltage drop for about 1170 ft one-way. At 240 V the same load reaches roughly 2341 ft, because allowable drop scales with system voltage.
What is the voltage drop of 3/0 AWG wire per 100 feet?
About 0.31 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 3/0 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.

More on 3/0 AWG