3/0 AWG Breaker Size — Amps & Overcurrent Rating

3/0 AWG copper is estimated at 198 A at 75 °C, which supports a 175 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

3/0 AWG copper pairs with a 175 A breaker at 75 °C terminations, from an estimated ampacity of 198 A. Aluminium of the same size is about 154 A. A continuous load on that circuit should not exceed 158 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

175A

Copper 60 / 75 / 90 °C

168 / 198 / 223A

Aluminium 75 °C

154A

Max continuous load

158A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper168 A198 A223 A175 A
Aluminium131 A154 A174 A150 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3223 A → 175 A204 A → 175 A182 A → 175 A158 A → 150 A
6178 A → 175 A163 A → 150 A146 A → 125 A126 A → 125 A
9156 A → 150 A143 A → 125 A127 A → 125 A110 A → 110 A
15112 A → 110 A102 A → 100 A91 A → 90 A79 A → 70 A
25100 A → 100 A92 A → 90 A82 A → 80 A71 A → 70 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 158 A continuous load needs 198 A of design current and a 200 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 3/0 AWG wire?
3/0 AWG copper at 75 °C terminations supports up to a 175 A overcurrent device, based on an estimated ampacity of 198 A. Aluminium of the same size supports less: about 154 A.
How many amps can 3/0 AWG handle?
Estimated 168 A at 60 °C, 198 A at 75 °C and 223 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.

More on 3/0 AWG