2 AWG Conduit Fill — Wires per Conduit Size

How many 2 AWG THHN conductors fit in EMT, IMC, RMC and PVC conduit, from 1/2 inch through 4 inch, with the 40% fill rule applied.

Quick answer

1 2 AWG THHN conductors fit in 1/2 inch EMT and 1 fit in 3/4 inch EMT, at 40% fill for three or more conductors. Each conductor consumes 0.1158 sq in from a nominal insulated outside diameter of 0.384 in. Neutrals and grounds count.

2 AWG conductors per conduit trade size

Same-size conductors only, at 53% for one, 31% for two and 40% for three or more.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT112571120303950
IMC113571217273647
RMC113571116253444
PVC Sch 40112561116253343
PVC Sch 801145914223038
Published standard — source: Raceway internal areas from product standards (EMT, IMC, RMC, PVC Sch 40, PVC Sch 80); conductor OD from nominal THHN dimensions

Source & method: Counts are the largest whole number where n × conductor area stays inside the raceway area times the applicable fill percentage. Mix conductor sizes in the calculator.

What each raceway type means

  • EMT EMT (electrical metallic tubing)
  • IMC IMC (intermediate metal conduit)
  • RMC RMC (rigid metal conduit)
  • PVC Sch 40 PVC Schedule 40
  • PVC Sch 80 PVC Schedule 80

Frequently asked

How many 2 AWG wires fit in 1/2 inch EMT?
1 2 AWG THHN conductors fit in 1/2 inch EMT at the applicable fill percentage.
How many 2 AWG wires fit in 3/4 inch EMT?
1 conductors, using a nominal THHN outside diameter of 0.384 in and the 40% fill rule for three or more conductors.
Do neutrals and grounds count toward fill?
Yes, every conductor in the raceway counts for fill. Grounds are excluded only from the count of current-carrying conductors used for ampacity adjustment.
What is the cross-sectional area of 2 AWG THHN?
About 0.1158 square inches, from A = π × (OD / 2)² with a nominal insulated OD of 0.384 in.

More on 2 AWG