2 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 2 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 463 ft one-way. Full table by load, voltage and distance.

Quick answer

2 AWG copper reaches 3% voltage drop at about 463 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.78 V (0.65%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 66,371 circular mils.

3% limit @ 20 A, 120 V

463ft

3% limit @ 20 A, 240 V

926ft

Drop @ 100 ft, 20 A

0.78V

Ω / 1000 ft (Cu)

0.1563

Maximum one-way run length at 3% drop

Copper 2 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A1,852 ft3,704 ft3,707 ft8,555 ft
10 A926 ft1,852 ft1,853 ft4,277 ft
15 A617 ft1,234 ft1,235 ft2,851 ft
20 A463 ft926 ft926 ft2,138 ft
25 A370 ft740 ft741 ft1,711 ft
30 A308 ft617 ft617 ft1,425 ft
40 A231 ft463 ft463 ft1,069 ft
50 A185 ft370 ft370 ft855 ft
60 A154 ft308 ft308 ft712 ft
80 A115 ft231 ft231 ft534 ft
100 A92 ft185 ft185 ft427 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.08%0.12%0.16%0.24%
50 ft0.16%0.24%0.32%0.49%
75 ft0.24%0.36%0.49%0.73%
100 ft0.32%0.49%0.65%0.97%
150 ft0.49%0.73%0.97%1.46%
200 ft0.65%0.97%1.3%1.94%
300 ft0.97%1.46%1.94%2.92%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 2 AWG wire?
At 20 A on a 120 V single-phase circuit, 2 AWG copper stays under 3% voltage drop for about 463 ft one-way. At 240 V the same load reaches roughly 926 ft, because allowable drop scales with system voltage.
What is the voltage drop of 2 AWG wire per 100 feet?
About 0.78 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 2 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.