500 kcmil Breaker Size — Amps & Overcurrent Rating
500 kcmil copper is estimated at 403 A at 75 °C, which supports a 400 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.
Quick answer
500 kcmil copper pairs with a 400 A breaker at 75 °C terminations, from an estimated ampacity of 403 A. Aluminium of the same size is about 314 A. A continuous load on that circuit should not exceed 322 A, since continuous loads are sized at 125%.
Max breaker (Cu, 75 °C)
400A
Copper 60 / 75 / 90 °C
341 / 403 / 454A
Aluminium 75 °C
314A
Max continuous load
322A
Ampacity and breaker pairing
Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.
| Material | 60 °C | 75 °C | 90 °C | Max device @ 75 °C |
|---|---|---|---|---|
| Copper | 341 A | 403 A | 454 A | 400 A |
| Aluminium | 266 A | 314 A | 354 A | 300 A |
Formula estimate — source: Ampacity from the site power-law model, not a code table
Derated ampacity and the device that still fits
Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 454 A → 400 A | 415 A → 400 A | 370 A → 350 A | 321 A → 300 A |
| 6 | 363 A → 350 A | 332 A → 300 A | 296 A → 250 A | 257 A → 250 A |
| 9 | 318 A → 300 A | 290 A → 250 A | 259 A → 250 A | 225 A → 225 A |
| 15 | 227 A → 225 A | 207 A → 200 A | 185 A → 175 A | 160 A → 150 A |
| 25 | 204 A → 200 A | 187 A → 175 A | 167 A → 150 A | 144 A → 125 A |
Source & method: Continuous-load example: a 322 A continuous load needs 403 A of design current and a 450 A device. Size your own load.
Neighbouring sizes
Frequently asked
- What breaker size for 500 kcmil wire?
- 500 kcmil copper at 75 °C terminations supports up to a 400 A overcurrent device, based on an estimated ampacity of 403 A. Aluminium of the same size supports less: about 314 A.
- How many amps can 500 kcmil handle?
- Estimated 341 A at 60 °C, 403 A at 75 °C and 454 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
- How does a continuous load change the breaker size?
- Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
- Can the breaker be larger than the wire ampacity?
- Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.
More on 500 kcmil
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.