500 kcmil Breaker Size — Amps & Overcurrent Rating

500 kcmil copper is estimated at 403 A at 75 °C, which supports a 400 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

500 kcmil copper pairs with a 400 A breaker at 75 °C terminations, from an estimated ampacity of 403 A. Aluminium of the same size is about 314 A. A continuous load on that circuit should not exceed 322 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

400A

Copper 60 / 75 / 90 °C

341 / 403 / 454A

Aluminium 75 °C

314A

Max continuous load

322A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper341 A403 A454 A400 A
Aluminium266 A314 A354 A300 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3454 A → 400 A415 A → 400 A370 A → 350 A321 A → 300 A
6363 A → 350 A332 A → 300 A296 A → 250 A257 A → 250 A
9318 A → 300 A290 A → 250 A259 A → 250 A225 A → 225 A
15227 A → 225 A207 A → 200 A185 A → 175 A160 A → 150 A
25204 A → 200 A187 A → 175 A167 A → 150 A144 A → 125 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 322 A continuous load needs 403 A of design current and a 450 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 500 kcmil wire?
500 kcmil copper at 75 °C terminations supports up to a 400 A overcurrent device, based on an estimated ampacity of 403 A. Aluminium of the same size supports less: about 314 A.
How many amps can 500 kcmil handle?
Estimated 341 A at 60 °C, 403 A at 75 °C and 454 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.