600 kcmil Breaker Size — Amps & Overcurrent Rating

600 kcmil copper is estimated at 454 A at 75 °C, which supports a 450 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

600 kcmil copper pairs with a 450 A breaker at 75 °C terminations, from an estimated ampacity of 454 A. Aluminium of the same size is about 354 A. A continuous load on that circuit should not exceed 363 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

450A

Copper 60 / 75 / 90 °C

384 / 454 / 511A

Aluminium 75 °C

354A

Max continuous load

363A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper384 A454 A511 A450 A
Aluminium300 A354 A399 A350 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3511 A → 450 A467 A → 450 A417 A → 400 A361 A → 350 A
6409 A → 400 A373 A → 350 A334 A → 300 A289 A → 250 A
9358 A → 350 A327 A → 300 A292 A → 250 A253 A → 250 A
15256 A → 250 A233 A → 225 A208 A → 200 A181 A → 175 A
25230 A → 225 A210 A → 200 A188 A → 175 A163 A → 150 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 363 A continuous load needs 454 A of design current and a 500 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 600 kcmil wire?
600 kcmil copper at 75 °C terminations supports up to a 450 A overcurrent device, based on an estimated ampacity of 454 A. Aluminium of the same size supports less: about 354 A.
How many amps can 600 kcmil handle?
Estimated 384 A at 60 °C, 454 A at 75 °C and 511 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.