600 kcmil Breaker Size & Ampacity
600 kcmil copper is estimated at 454 A at 75 °C, supporting a 450 A overcurrent device. Breaker pairing and derating shown.
Quick answer
600 kcmil copper pairs with a 450 A breaker at 75 °C terminations, from an estimated ampacity of 454 A. Aluminium of the same size is about 354 A. A continuous load on that circuit should not exceed 363 A, since continuous loads are sized at 125%.
Max breaker (Cu, 75 °C)
450A
Copper 60 / 75 / 90 °C
384 / 454 / 511A
Aluminium 75 °C
354A
Max continuous load
363A
Ampacity and breaker pairing
Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.
| Material | 60 °C | 75 °C | 90 °C | Max device @ 75 °C |
|---|---|---|---|---|
| Copper | 384 A | 454 A | 511 A | 450 A |
| Aluminium | 300 A | 354 A | 399 A | 350 A |
Formula estimate — source: Ampacity from the site power-law model, not a code table
Derated ampacity and the device that still fits
Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 511 A → 450 A | 467 A → 450 A | 417 A → 400 A | 361 A → 350 A |
| 6 | 409 A → 400 A | 373 A → 350 A | 334 A → 300 A | 289 A → 250 A |
| 9 | 358 A → 350 A | 327 A → 300 A | 292 A → 250 A | 253 A → 250 A |
| 15 | 256 A → 250 A | 233 A → 225 A | 208 A → 200 A | 181 A → 175 A |
| 25 | 230 A → 225 A | 210 A → 200 A | 188 A → 175 A | 163 A → 150 A |
Source & method: Continuous-load example: a 363 A continuous load needs 454 A of design current and a 500 A device. Size your own load.
Neighbouring sizes
Frequently asked
- What breaker size for 600 kcmil wire?
- 600 kcmil copper at 75 °C terminations supports up to a 450 A overcurrent device, based on an estimated ampacity of 454 A. Aluminium of the same size supports less: about 354 A.
- How many amps can 600 kcmil handle?
- Estimated 384 A at 60 °C, 454 A at 75 °C and 511 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
- How does a continuous load change the breaker size?
- Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
- Can the breaker be larger than the wire ampacity?
- Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.
More on 600 kcmil
Related charts & calculators
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.
- Allen Wrench Size ChartHex key sizes with SAE and metric cross-reference.
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.