600 kcmil Voltage Drop — Max Run Length by Load

Voltage drop for 600 kcmil copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 4186 ft one-way. Full table by load, voltage and distance.

Quick answer

600 kcmil copper reaches 3% voltage drop at about 4186 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.09 V (0.07%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 600,000 circular mils.

3% limit @ 20 A, 120 V

4186ft

3% limit @ 20 A, 240 V

8372ft

Drop @ 100 ft, 20 A

0.09V

Ω / 1000 ft (Cu)

0.0173

Maximum one-way run length at 3% drop

Copper 600 kcmil. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A16,744 ft33,488 ft33,514 ft77,340 ft
10 A8,372 ft16,744 ft16,757 ft38,670 ft
15 A5,581 ft11,162 ft11,171 ft25,780 ft
20 A4,186 ft8,372 ft8,378 ft19,335 ft
25 A3,348 ft6,697 ft6,702 ft15,468 ft
30 A2,790 ft5,581 ft5,585 ft12,890 ft
40 A2,093 ft4,186 ft4,189 ft9,667 ft
50 A1,674 ft3,348 ft3,351 ft7,734 ft
60 A1,395 ft2,790 ft2,792 ft6,445 ft
80 A1,046 ft2,093 ft2,094 ft4,833 ft
100 A837 ft1,674 ft1,675 ft3,867 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.01%0.01%0.02%0.03%
50 ft0.02%0.03%0.04%0.05%
75 ft0.03%0.04%0.05%0.08%
100 ft0.04%0.05%0.07%0.11%
150 ft0.05%0.08%0.11%0.16%
200 ft0.07%0.11%0.14%0.22%
300 ft0.11%0.16%0.22%0.32%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 600 kcmil wire?
At 20 A on a 120 V single-phase circuit, 600 kcmil copper stays under 3% voltage drop for about 4186 ft one-way. At 240 V the same load reaches roughly 8372 ft, because allowable drop scales with system voltage.
What is the voltage drop of 600 kcmil wire per 100 feet?
About 0.09 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 600 kcmil numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.