750 kcmil Breaker Size — Amps & Overcurrent Rating

750 kcmil copper is estimated at 524 A at 75 °C, which supports a 500 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

750 kcmil copper pairs with a 500 A breaker at 75 °C terminations, from an estimated ampacity of 524 A. Aluminium of the same size is about 409 A. A continuous load on that circuit should not exceed 419 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

500A

Copper 60 / 75 / 90 °C

444 / 524 / 591A

Aluminium 75 °C

409A

Max continuous load

419A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper444 A524 A591 A500 A
Aluminium347 A409 A461 A400 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3591 A → 500 A540 A → 500 A482 A → 450 A418 A → 400 A
6473 A → 450 A432 A → 400 A386 A → 350 A334 A → 300 A
9414 A → 400 A378 A → 350 A338 A → 300 A292 A → 250 A
15296 A → 250 A270 A → 250 A241 A → 225 A209 A → 200 A
25266 A → 250 A243 A → 225 A217 A → 200 A188 A → 175 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 419 A continuous load needs 524 A of design current and a 600 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 750 kcmil wire?
750 kcmil copper at 75 °C terminations supports up to a 500 A overcurrent device, based on an estimated ampacity of 524 A. Aluminium of the same size supports less: about 409 A.
How many amps can 750 kcmil handle?
Estimated 444 A at 60 °C, 524 A at 75 °C and 591 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.