2/0 AWG Breaker Size — Amps & Overcurrent Rating

2/0 AWG copper is estimated at 170 A at 75 °C, which supports a 150 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

2/0 AWG copper pairs with a 150 A breaker at 75 °C terminations, from an estimated ampacity of 170 A. Aluminium of the same size is about 133 A. A continuous load on that circuit should not exceed 136 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

150A

Copper 60 / 75 / 90 °C

144 / 170 / 192A

Aluminium 75 °C

133A

Max continuous load

136A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper144 A170 A192 A150 A
Aluminium113 A133 A150 A125 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3192 A → 150 A175 A → 150 A157 A → 150 A136 A → 125 A
6154 A → 150 A140 A → 125 A125 A → 125 A109 A → 100 A
9134 A → 125 A123 A → 110 A110 A → 110 A95 A → 90 A
1596 A → 90 A88 A → 80 A78 A → 70 A68 A → 60 A
2586 A → 80 A79 A → 70 A71 A → 70 A61 A → 60 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 136 A continuous load needs 170 A of design current and a 175 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 2/0 AWG wire?
2/0 AWG copper at 75 °C terminations supports up to a 150 A overcurrent device, based on an estimated ampacity of 170 A. Aluminium of the same size supports less: about 133 A.
How many amps can 2/0 AWG handle?
Estimated 144 A at 60 °C, 170 A at 75 °C and 192 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.

More on 2/0 AWG